4
USAGE AND OPERATION
11
4.5. Parameter Table
Digit
meaning
default
Adjust(yes/no)
0
Return water temp.
Setting(cooling mode)
27 °C
yes
1
Return water temp.
Setting(heating mode)
27 °C
yes
2
Turnround of dehumidifying
under heating mode frost
45MIN
yes
3
Defrosting start temperature
-7 °C
yes
4
Terms of exit defrost under
heating model
13 °C
yes
5
time of exit defrost under
heating mode
8MIN
yes
6
System number
1
yes
7
Automatic restarting
0
yes
8
Model(cooling only/heat pump/
auxiliary electrical heating/hot
water
3
yes
9
Water pump model
0
yes
10
Fan mode
3
yes
11
Fan type
1
yes
*Remark:
Parameter 06:
1: means one system;
2: means two system.
Parameter 07:
0: the unit can not restart automatically
1: the unit can restart automatically
Parameter 08:
0: the mode of the unit is cooling only
1: the mode of the unit is heat pump
2: the mode of the unit is auxiliary electrical heating;
3: the mode of the unit is heating only.
Parameter 09:
0: always open.
1: 60 seconds start before compressors starting.
30 seconds stop after compressors stopping.
Parameter10:
0: low fan speed
1: high fan speed
2: automatic fan speed(high speed when air temperature is below 10 ,low speed when air
temperature is above 15 );
3: low fan speed during 9PM~8AM,high speed at other time;
4: automatic running according to above condition 2and 3.
Summary of Contents for Hydro-Pro+ Premium 22M
Page 2: ......
Page 12: ...9 ...
Page 24: ......
Page 25: ...code 20141120 0001 ...
Page 27: ......
Page 39: ...4 VERWENDUNG UND BETRIEB 11 Verdampfungstemp Umgebungstemp ...
Page 53: ......
Page 54: ...Code 20141120 0001 ...
Page 56: ......
Page 68: ...4 GEBRUIK EN BEDIENING 11 Verdampingstemp Omgevingstemp ...
Page 82: ......
Page 83: ...code 20141120 0001 ...
Page 85: ......
Page 89: ...Chauffage température de l air extérieur 15 C température de l entrée d eau 26 C ...
Page 98: ...3 INSTALLATION ET RACCORDEMENT 15 Temp d évaporation Temp ambiante ...
Page 114: ...6 ANNEXES 31 ...
Page 115: ...6 ANNEXES 32 code 20141120 0001 ...
Page 117: ......
Page 121: ...opakowaniu Ogrzewanie Temperatura powietrza na zewnątrz 15 C temperatura wody wlotowej 26 C ...
Page 129: ...3 INSTALACJA I PODŁĄCZENIE 14 Temperatura parowania Temperatura otoczenia ...
Page 144: ...6 DODATEK 29 ...
Page 145: ...6 DODATEK 30 kod 20141120 0001 ...