HydrINS 2 / HydrINS 2 Mini flow meter
Installation Manual
Page 11 / 79
2.4
Safety
:
A danger arises during the physical installation of the
HydrINS 2/HydrINS 2 Mini probe. Because of the intrusive nature of
the procedure, the probe can be ejected if there is excessive
pressure inside the pipe. The probe is supplied with a safety chain,
which must be used. Ensure compliance with the installation
conditions (pumps shut off, wait for night-time conditions before
installing, etc.).
ENSURE THAT THE CHAIN IS OPERATIONAL BEFORE OPENING THE
INSERT VALVE
PROPERTY DAMAGE CAUSED BY EJECTION OF THE PROBE IS NOT
UNDER ANY CIRCUMSTANCES COVERED BY THE GUARANTEE
THE CONDUCTIVITY OF THE WATER PASSING THROUGH THE PIPE
MUST BE GREATER THAN 20µS/cm.
NOTE: It is essential to avoid sites where the pipes vibrate. If the
probe vibrates excessively after installation, the measurement will
not be correct. In this case, remove the probe.