Maintenance
OXiStop OXS-LID/-C202
en-US
Page 67 / 96
MoWa OXS-LID-C202 4461688 en-us 2019-07-08.docx
2019-07-08
Replacing the breather filter element
Replace the filter element on the breather filter if the clogging indicator shows
50 mbar and at least once a year. If the unit is in a very dusty/damp
environment, the replacement intervals shorten accordingly.
Replace the filter element of the breather filter BF7 as follows:
1.
Unscrew cover (6.41) of the breather filter by hand in counterclockwise
direction.
2.
Remove used filter element (6.42) and dispose of it in an
environmentally correct manner.
3.
Insert new filter element (6.42) and screw on cover (6.41) by hand in
clockwise direction.
4.
Press the reset button on the clogging indicator (6.45)