EDS 3400
11
Status: 2018-07-30
HYDAC INTERNATIONAL GMBH
Part No.: 670000 E
10.1.2 Setting of the pre-charge pressure monitoring
The pre-charge pressure monitoring is determined by the switching value ("FL1). This is
calculated as described in the following and can be checked in the main menu.
FL1
= T.VAL – Td.Lo
The output switches as soon as p
0
leaves this range. The output will switch back when the
pressure enters this range. The lower switch-back value is just below the lower switch
value.
Example:
Abbreviations:
"FL1"
=Lower switch value 1
10.2 SETTING RANGES FOR THE SWITCHING OUTPUTS
Measuring range Lower limit of
RP2 / FL1
Upper limit of
SP2
Minimum
difference betw.
RP2 and SP2
Increment*
in bar
in bar
in bar
in bar
in bar
0 ... 40
0.4
40
0.4
0.1
0 ... 100
1
100
1
0.2
0 ... 250
2.5
250
2.5
0.5
0 ... 400
4
400
4
1
0 ... 690
7
690
7
1
* All ranges shown in the table can be adjusted by the increments shown.
10.3 ANALOGUE OUTPUT
The universal output "ou2" can be set to 4 ... 20 mA or 0 ... 10 V (corresponding to
measuring range).
P
FL1 minus 1% FS
FL 1
T
Safety zone
Off
On
On
Off
Switch-back value
Switching value