16 Error Messages
If an error is detected, a corresponding error message appears which must be
acknowledged by pressing any key.
Possible error messages are as follows:
E.10
A data error has been detected in the saved settings. Possible causes are
strong electromagnetic interference or a defective component.
Action
:
Press "Mode" and confirm "RES" by pressing "Yes". The factory settings will
be restored for all adjustable parameters and all minimum and maximum
values will be deleted.
Enter the data again from the beginning.
E.12
An error was detected in the saved calibration data. Possible causes are
strong electromagnetic interference or a defective component.
Action
:
Disconnect then reconnect the supply voltage to the instrument. If the error
persists, the instrument must be returned to the factory for recalibration or
repair.
E.21
A communication error within the unit has been detected. Possible causes are
strong electromagnetic interference or a defective component.
Solution
: Press "Mode". If the error persists, disconnect then reconnect the supply
voltage to the instrument. If the error still persists, please contact our service
department.
17 Pin Assignment
M 12x1, 4 pole
Pin Signal Designation
1 L+ +U
B
2
Q2/QA Switching output (SP2) /
Analogue output
3 L- 0
V
4
Q1/C
IO-Link communication /
switching output (SP1)
Q2/QA
Q1/C