Reading the analog output
HDA.NAS – Analog signal NAS for HDA 5500
The HDA.NAS signal consists of 4 measured values (Start / NAS 2 / NAS 5 /
NAS 15 / NAS 25 / Status) which are output sequentially. Synchronization
with the downstream control unit is a prerequisite.
The signal output is as follows:
Time
Measured
variable
Signal duration
in s
Current/Voltage
Start signal 0
--
2
20 mA / 10 V
Pause
2
4 mA / 2 V
Signal 1
2-5 µm
2
Current / Voltage for signal
Pause
2
4 mA / 2 V
Signal 2
5-15 µm
2
Current / Voltage for signal
Pause
2
4 mA / 2 V
Signal 3
15-25 µm
2
Current / Voltage for signal
Pause
2
4 mA / 2 V
Signal 4
> 25 µm
2
Current / Voltage for signal
Pause
2
4 mA / 2 V
Signal 5
Status
2
Current/voltage for signal
Pause
30
4 mA / 2 V