Reading the analog output
HDA.ISO Signal 5 (Status)
The current or voltage of the output signal 5 is, depending on the status of
the CS1000, described as shown in the table below.
Current I
Status
Voltage U
I = 5.0 mA
The CS is functioning correctly
U = 2.5 V
I = 6.0 mA
Device error /
The CS is not ready
U = 3.0 V
I = 7.0 mA
The flow rate is too low
U = 3.5 V
I = 8.0 mA
ISO <9.<8.<7
U = 4.0 V
I = 9.0 mA
No measured value
(The flow rate is not defined)
U = 4.5 V
If the status signal is 6.0 / 7.0 / 9.0 mA or 3.0 / 3.5 / 4.5 V, signals 1 to 4 are
output with 20 mA or 10 V. Example: