FluidMonitoring Module – FMM-O-M
FMM hydraulic installation
FMM hydraulic installation
To minimize measurement errors resulting from trapped air in the system, we
recommend that the flow direction through the FMM is from bottom (IN) to top
(OUT).
Determine the operating pressure of the hydraulic system and see whether it is
within the permissible flow range for the FMM inlet.
The FMM comes delivered with two test connectors (type 1604), one at the inlet (IN)
and one at the outlet (OUT) port. If the hydraulic connection is done via the
connector thread G 1/4 according to ISO 228, the test connectors must be removed.
The mounting holes on the FMM are through-holes. There are three connection
possibilities:
IN / TP1 / OUT Connections on the "back side"
IN / TP1 / OUT connections on the "side"
IN / TP1 / OUT connections on the "front side" (position at delivery time)
IN
IN
IN
OUT
OUT
OUT
TP1
TP1
TP1
A
C
B
HYDAC FILTER SYSTEMS GMBH
en(us)
Page 19 / 28
MoWa FMM-O-M 3492448a en-us 2010-12-15.doc
2010-12-15
The screw plugs can be exchanged for the test connectors and vice versa.