Electrical Connection of the CSM
Electrical Connection of the CSM
DANGER
Exposed electrical components in the switch
cabinet
Danger of fatal injury due to electric shock
►
Any work involving the electrical system may only
be done by a properly trained, certified electrician.
Compare the voltage and frequency specifications on the type label with the
specifications for the available network.
The pump motor must be protected from overloading, in accordance with VDE 0113.
Check the direction of rotation of the motor by switching it on briefly (jog mode). An
arrow on the ventilator hood shows the sense of rotation.
To change the direction of rotation, commutate two phases.
Depending on the network voltage, connect the motor in a star or delta connection.
Check the type label on the motor to accomplish this.