ETS 4000 Ex ia HART ATEX / IECEx
Page 8 of 30
Status: 2016-06-07
HYDAC ELECTRONIC GMBH
Part No.: 669918
6.2
ETS 4000 with pressure measurement as an option
General parameters: See 6.1 ETS 4100 / ETS 4500 Standard
Additional technical data with pressure measurement as an option:
Input parameters
ETS 4100
ETS 4500
Measuring range
bar
16
40
60
100
250
400
600
Overload range
bar
32
80
120
200
500
800
1000
Burst pressure
bar
100
200
300
500
1000
2000
2000
Measuring range
psi
300
500
1000
3000
5000
6000
9000
Overload range
psi
725
1160
2900
7250
11600
11600
14500
Burst pressure
psi
1800
2900
7250
14500
29000
29000
29000
Mechanical Connection
G1/2 A DIN 3852 with probe (45 Nm)
Torque value
see dimensions
Parts in contact with fluid
Stainless steel: 1.4542(630); 1.4548(630)
Seal: FPM
Probe length
7 mm
Output data
Output signal Pressure
The pressure signal is available as a secondary variable via HART protocol as a
digital signal.
Accuracy to DIN 16086
limit setting
Typ.
Max.
≤
±
0.25 % FS
≤
±
0.5 % FS
≤
±
0.5 % FS
≤
±
1.0 % FS
Accuracy at minimum setting
(B.F.S.L)
Typ.
Max.
≤
±
0.15 % FS
≤
±
0.25 % FS
≤
±
0.25 % FS
≤
±
0.5 % FS
Temperature compensation
Typ.
≤
±
0.008 % /°C [0.004% FS /°F]
≤
±
0.015 % /°C [0.008% FS /°F]
Zero point
max
≤
±
0.015 % /°C [0.008% FS /°F]
≤
±
0.025 % /°C [0.014% FS /°F]
Temperature compensation
Typ.
≤
±
0.008 % /°C [0.004% FS /°F]
≤
±
0.015 % /°C [0.008% FS /°F]
Span
max
≤
±
0.015 % /°C [0.008% FS /°F]
≤
±
0.025 % /°C [0.014% FS /°F]
Non-linearity at max. setting
to DIN 16086
max
≤
±
0.3 % FS
≤
±
0.3 % FS
Hysteresis
max
≤
±
0.1 % FS
≤
±
0.4 % FS
Repeatability
≤
±
0.05 % FS
≤
±
0.1 % FS
Long-term drift
Typ.
≤
±
0.1 % FS / year
≤
±
0.3 % FS / year
Ambient conditions
Compensated temperature range
-25 .. +85° C
Protection class to IEC 60529
1)
ISO 20653
IP 65 (with 1/2 NPT Conduit
≤
100 bar)
IP 67 (connector M12x1, EN175301-803)
IP 6K9K (with 1/2 NPT Conduit
>
100 bar)
Life expectancy
> 10 million load cycles 0 .. 100 % FS
1)
with mounted mating connector with appropriate protection class
6.3
Measuring Range Limits
By means of HART Common Practice Commands, you have the opportunity to adjust the following measuring
ranges:
Measuring range limits of the primary variable, temperature:
Lower measuring range limit
Upper measuring range limit
Measuring span
min
max
min
max
min
max
-25 °C
75°C
0°C
100°C
25°C
125°C
-13°F
167°F
32°F
212°F
-13°F
257°F
For devices with pressure measurement option ETS 4000-P: Measuring range limits of the secondary variable,
pressure:
Lower measuring range limit
Upper measuring range limit
Measuring span
min
max
min
max
min
max
0 % FS
112.5% FS
37.5% FS
150% FS
37.5% FS
150% FS
6.4
Protocol Data
HART Version: 7
Manufacturer Code: 0x605E
Manufacturer String: HYDAC ELECTRONIC
Device Type Code: 0xE2A8 Variant with temperature as PV and as the only measured value
0xE2A9 Variant with temperature as PV and pressure as SV