Sensors 

 

 
 
 
 

 - Scans for changes in connected sensors  

 

 
Note: 

After connecting a new sensor or exchanging an existing one, always click 

Find Sensors

 
 
 
Hysteresis 

Hysteresis prevents receiving tens and hundreds of alarm messages about start and ending of alarm 
while the value oscillates around the Safe Range threshold. 
Set the value in °C or %RH, mostly using 1 to 4°C or approximately 5 %RH is enough.  
 
 
You can find more on HWg websites in 

AN35: Poseidon 

– Preventing false alarms

”:  

 

 

Deletes the sensor from the list

 

Safe Range - device sends 

an email when this 

threshold is exceeded

 

 

Inactivity period before and 

after each alarm

 

 

Summary of Contents for HWg-STE plus

Page 1: ...HWg STE plus HWg STE plus PoE MANUAL ...

Page 2: ...ice Factory defaults settings is restored POWER input 5V DC power supply Use the supplied power adapter ETHERNET 100 Mbps PoE power only for HWg STE PoE JUMPER for restoring factory default settings DO NOT KEEP THE JUMPER PERMANENTLY SET SENSORS S1 and S2 ports for connecting temperature or humidity sensors Max distance 60m for both sensors in total Power Ethernet Sensors SET RJ45 RJ11 RJ11 LED in...

Page 3: ...HWg STE plus manual HW group Page 3 www HW group com Recommended connection options Sensors connection options Smoke sensor connection ...

Page 4: ...e for download at www HW group com Software UDP Config Click the icon to launch UDP Config The program automatically looks for connected devices To search for devices click the Find Devices icon The program looks for devices on your local network Double click a MAC address to open a basic device configuration dialog Configure network parameters IP address HTTP port 80 by default Network mask Gatew...

Page 5: ...er the IP address into a web browser o Click the IP address in UDP Config o Click the underlined IP address in UDP SETUP The WWW page displays current states of inputs and outputs Device IP address Sensors overview IP address DHCP setup Outgoing e mail parameters Sensors settings Current sensor reading User defined text for service purposes ...

Page 6: ...ry page except the main page Without entering the password it is then possible to read the current connected sensors values User defined footer For example administrator s contact details Device name Identifies the device in e mails and SNMP Temperature unit for display and alarm inputs Password for configuration access ...

Page 7: ...us manual HW group Page 7 www HW group com SNMP Email SNMP device identification same as the device name Port for SNMP polling SMTP server to use for sending e mails Sends a test e mail to all entered recipients ...

Page 8: ...W group Page 8 www HW group com Time Digital Inputs Alarm settings active disabled Digital Input ID Log0 Log1 state names For example fuel tank Full Empty or front door Open Closed Sends an email in case of alarm if ticked ...

Page 9: ...ving tens and hundreds of alarm messages about start and ending of alarm while the value oscillates around the Safe Range threshold Set the value in C or RH mostly using 1 to 4 C or approximately 5 RH is enough You can find more on HWg websites in AN35 Poseidon Preventing false alarms Deletes the sensor from the list Safe Range device sends an email when this threshold is exceeded Inactivity perio...

Page 10: ... period depends on the time set on a server that operates the portal AutoPush is a function allowing sending of measured data in case of value increase decrease larger than AutoPush delta parameter Portal communication status AutoPush function and sensitivity settings delta value change Target portal settings with login details ...

Page 11: ... www HW group com Graph Choose a sensor to show its graph Values are stored on RAM memory Safe range threshold set for the sensor Graph of the measured values Mouse over to show the time and value at the point Graph actualization period s ...

Page 12: ...HWg STE plus manual HW group Page 12 www HW group com System Text list of most frequent SNMP variables Firmware update SNMP MIB ...

Page 13: ...r I1 I2 socket clamp ø2mm Type Digital Input supports NO NC Dry contact Sensitivity 1 On 0 500 Ω Right pin on the terminal block can be connected to 12V GND Max distance Up to 50m Power Supply Power Supply 5V DC 250 mA Connector Jack Ø3 5 x 1 35 10 mm PoE Power over Ethernet RJ45 IEEE 802 3af only with HWg STE plus PoE version LED POWER status Green power OK status DHCP Local alarm LINK Activity Y...

Page 14: ...p Page 14 www HW group com Connecting HWg STE plus and STE Push to SensDesk portal 1 Connect the device to your network and set the network parameters First Steps chapter in the user manual 2 Then open the WWW setup of the device ...

Page 15: ...e Home tab click the Activate button in Portal Message section 4 This will get you to a Portal tab and at the same time the portal function will be activated By clicking the link SensDesk com register your IP sensor a login window on www Sensdesk com will be show ...

Page 16: ...new account and a correct e mail address E mail address has to be unique for the server cannot be already registered under another account Company name field allows you to create your own 3rd level domain usually company sensdesk com A user name will be used if the Company name field is left empty After clicking Create new account button a user account will be created and at the same time a confir...

Page 17: ...only for approximately 15 minutes after the activation then the logging period changes to 15 minutes In your user account configuration My Account link you can find your Push Device Password This password together with your login name identifies the device in communication with your account and in communication of mobile applications with SensDesk The password cannot be changed and for a security ...

Page 18: ...ing assigning a device to your portal account without going through the logging process Using the mobile phone Application Username and PUSH Device Password can be used also for setting the mobile application Contact details HW group s r o Rumunská 26 122 Praha 2 120 00 Tel 420 222 511 918 Fax 420 222 513 833 http www HW group com ...

Page 19: ...HWg STE plus manual HW group Page 19 www HW group com ...

Reviews: