Section 5 Synchronous Test
This module is used to test the operation voltage, operating frequency, the action angle
of the synchronization device as well as automatically adjusting test quasi-synchronization
test.
1. Interface Instruction
(1) Use this procedure; the tester only output voltage, no output current. General system
side elect UA, the shunt side elect UB, input terminal choose from 1-8. [Manual test] or
[automatic test] 2 methods. Automatic synchronizing adjusted only [ automatic test ] way
(2) Basic conditions of the synchronization device action
When the shunt side and the system side of the frequency is substantially equal, the
voltage amplitude is substantially equal, and the angle deviation is less than a certain value
while satisfying these three conditions, the synchronizing device is issued immediately closed
signal.
(3) Test item
3.1 Test operation voltage