39
Select ‘Add Sequence’ button, then pop-up dialog to
select a set of brake current: ‘original value’ and ‘final
value’; step size is generally 2.00A. After completing the
set of parameters, click ‘Add’ for putting the data in the
testing data list, then select ‘start’.
2
Ratio Restraint Setting Point Search
Move the mouse to the coordinate system of the characteristic curve, click the left mouse
button, then select ‘Add setting point’ button for putting this point in the testing data list, repeat
the above operation to add multiple test points, as shown in the figure. The test points should
be selected in the action area and non-operating area, in order to verify whether the curve is
correct. Click the ‘start test’ button to start.
3
Harmonic Restraint Boundary Search
Select ‘Add Sequence’ button, then pop-up dialog to select a set of differential current:
‘original value’ is threshold value of differential current; ‘final value’ is quick break value of
differential current; step size is generally 1.00A. After completing the set of parameters, click
‘Add’ for putting the data in the testing data list, then click ‘start’.
Summary of Contents for HT-802