5
area must be at least 30mm.
• The sauna stove must be installed on a non-combustible surface
with the required carrying capacity.
• Electrical equipment and wiring are not permitted in the safety area
f the sauna stove.
Table 1
Power
kW
Room
m
3
A
mm
B
mm
C
mm
D
mm
E
mm
F
mm
Ø
mm
H
mm
HIVE Heat 12 /
LS
12
6-13
250 900 240 425 5/
155
300/
450
450 750
Installing Hive Heat 12
LS
to be heated from another
room
• The furnace bushing of the sauna stove must be made through a
non-combustible wall (stone, concrete, etc.).
• The furnace bushing of the sauna stove must be made through a
non-combustible wall (stone, concrete, etc.) that extends 600 mm to
the sides of and 1,400 mm above the opening.
• It is advisable to leave a 50 mm air gap between the bushing and the
stove; therefore, add 100 mm to height
D
and width
C
given in table 1
when calculating the dimensions for the opening.
• If the floor in front of the furnace is made from combustible material,
fire-resistant floor protection must be installed in front of the furnace
door. The protection must be 600 mm wider than door width
C
, with
a depth of at least 400 mm.