background image

Rev. 0909 

15

appendices (cont'd)

1.1  The following recommendations are made for the 

purpose of arriving at easily taken and understood 

data which, coupled with other observations, 

may be used to determined whether a display 

refrigerator is working as intended:

a)  INSTRUMENT - A stainless steel stem-type 

thermometer is recommended and it should 

have a dial a minimum of 1 inch internal 

diameter. A test thermometer scaled only 

in Celsius or dually scaled in Celsius and 

Fahrenheit shall be accurate to 1°C (1.8°F). 

Temperature measuring devices that are 

scaled only in Fahrenheit shall be accurate to 

°F. The thermometer should be checked for 

proper calibration. (It should read 3°F when 

the stem is immersed in an ice water bath).

b)  LOCATION - The probe or sensing element 

of the thermometer should be located in 

the airstream where the air first enters the 

display or storage area, and not more than 1 

inch away from the surface and in the center 

of the discharge opening.

c)  READING - It should first be determined 

that the refrigerator is refrigerating and has 

operated at least one hour since the end 

of the last defrost period. The thermometer 

reading should be made only after it has 

been allowed to stabilize, i.e., maintain a 

constant reading.

d)  OTHER OBSERVATIONS - Other 

observations should be made which may 

indicate operating problems, such as 

unsatisfactory product, feel/appearance.

e)  CONCLUSIONS - In the absence of any 

apparent undesirable conditions, the refrigerator 

should be judged to be operating properly. If it is 

determined that such condition is undesirable, 

i.e., the product is above proper temperature, 

checks should be made for the following:

1.  Has the refrigerator been loaded with 

warm product?

.  Is the product loaded beyond the “Safe 

Load Line” markers?

3.  Are the return air ducts blocked?

4.  Are the entering air ducts blocked?

5.  Is a dumped display causing turbulent air 

flow and mixing with room air?

6.  Are spotlights or other high intensity 

lighting directed onto the product?

7.  Are there unusual draft conditions (from 

heating /air-conditioning ducts, open 

doors, etc.)?

8.  Is there exposure to direct sunlight?

9.  Are display signs blocking or diverting 

airflow?

10. Are the coils of the refrigerator iced up?

11. Is the store ambient over 75°F, 55% RH 

as set forth in ASHRAE Standard 7 and 

ASHRAE Standard 117?

1. Are the shelf positions, number, and size 

other than recommended by Hussmann?

13. Is there an improper application or control 

system?

14. Is the evaporator fan motor/blade 

inoperative?

15. Is the defrost time excessive?

16. Is the defrost termination, thermostat  

(if used) set too high?

17. Are the refrigerant controls incorrectly 

adjusted?

18. Is the air entering the condenser above 

design conditions? Are the condenser fins 

clear of dirt, dust, etc.?

19. Is there a shortage of refrigerant?

20. Has the equipment been modified to use 

replacements for CFC-1,  

CFC-50 or other refrigerant? If so, 

have the modifications been made in 

accordance with the recommendations 

of Hussmann’s equipment? Is the 

refrigerator charged with the proper 

refrigerant and lubricant? Does the system 

use the recommended compressor?

appendix d. - Recommendations to user

1.0  Hussmann should provide instructions and 

recommendations for proper periodic cleaning. 

The user will be responsible for such cleaning, 

including the cleaning of low temperature 

equipment within the compartment and the 

cooling coil area(s). Cleaning practices, 

particularly with respect to proper refrigerator 

unloading and warm-up, must be in accordance 

with applicable recommendations.

es continued

1.1  Cleaning of non frozen food equipment 

should include a weekly cleaning of the food 

compartment as a minimum to prevent bacteria 

growth from accumulating. Actual use and 

products may dictate more frequent cleaning. 

Circumstances of use and equipment design 

must also dictate the frequency of cleaning the 

display areas. Weekly washing down of the 

storage compartment is also recommended, 

especially for equipment subject to drippage 

of milk or other liquids, or the collection of 

Summary of Contents for MZ3-S

Page 1: ...S Multi zone Refrigerated Self Service Self Contained P N IGSS MZ3 S 0909 INSTALLATION OPERATION GUIDE CHINO MZ3 S MULTI ZONE REFRIGERATED SELF SERVICE SELF CONTAINED Rev 0909 Installation Operation Manual ...

Page 2: ...ely and request an inspection Hussmann Chino will acknowledge shortages within ten days from receipt of equipment HUSSMANN CHINO PRODUCT CONTROL The serial number and shipping date of all equipment has been recorded in Hussmann s files for warranty and replacement part purposes All correspondence pertaining to warranty or parts ordering must include the serial number of each piece of equipment inv...

Page 3: ...71 6 20 1 4 18 1 4 16 1 4 37 1 4 30 7 8 27 5 8 19 3 4 10 7 8 9 3 8 9 3 8 1 5 8 1 7 8 1 7 8 1 5 8 50 3 8 47 1 4 37 1 4 6 ELECTRICAL CONNECTION 2 POWER CORDS 1 NEMA 5 15P 2 NEMA L5 20P MZ3 4S PLAN VIEW RCD FMSS LT Condensing Unit MZ3 SELF SERVICE MERCHANDISER ...

Page 4: ...Case must be raised correctly under legs where support is best to prevent damage to case 1 Check level of floor where cases are to be set Determine the highest point of the floor cases will be set off this point 2 Level and set the case Case must be raised under legs where support is best to prevent damage to case Internal bracing may be removed at this time It is the contractor s responsibility t...

Page 5: ...r location Control Settings self Contained All functions are controlled by Omni Stat Controllers See MZ3 S Technical Data Sheet for proper temperature and defrost settings Access to TX Valves and Drain Lines MECHANICAL Remove product from end of case Remove product racks Remove refrigeration and drain access panels labeled TX valve mechanical only and drain are located under each access panel at e...

Page 6: ...rol temp Btu hr ft Parallel 400 Conventional 460 Low Temp Discharge Air F 10 Evaporator F 20 Note Not recommended to control temp by regulating coil temp allow T STAT to cycle and control temp Btu hr ft Parallel 600 Conventional 690 For all refrigeration equipment other than Hussmann use conventional Btu values Defrost Data Frequency Hrs 8 OFFTIME Temp Term F 54 Failsafe Minutes 30 ELECTRIC or GAS...

Page 7: ...both cords before moving or servicing this equipment Attachment Plugs This unit contains two power supply cords Each cord is a different type Connect each plug to a single outlet circuit The first attachment plug is a NEMA 5 15P type plug with a 15 amp rating A 15 amp line is required for the NEMA 5 15P plug The second is a NEMA L5 20P type plug with a 20 amp rating A 20 amp line is require for th...

Page 8: ...t dehydration Recommended Omni Stat Temperature Control Settings RCD 26 FMSS LT 15 See Case Specifications for Details 2 Temperature control is adjusted by the Omni Stat Temperature Controller Case Cleaning Long life and satisfactory performance of any equipment are dependent upon the care given to it To insure long life proper sanitation and minimum maintenance costs the refrigerator should be th...

Page 9: ...t in damage to equipment serious personal injury This includes but not limited to Fans Heaters Thermostats and Lights Replacing Fluorescent Lamps Fluorescent lamps are furnished with moisture resistant lamp holders shields and end caps Whenever a florescent lamp is replaced be certain to reinstall the lamp shield and end caps over the lamp The lamps supplied are single slim line or bi pin type wit...

Page 10: ...t safe and use a soft cloth or plastic scouring pad 3 Use Alkaline Alkaline Chlorinated or Non chloride Containing Cleaners While many traditional cleaners are loaded with chlorides the industry is providing an ever increasing choice of non chloride cleaners If you are not sure of your cleaner s chloride content contact your cleaner supplier If they tell you that your present cleaner contains chlo...

Page 11: ...15V 60 Hz 952892 125 01 2304 AIR TEMP DEFROST TEMP 125 01 2301A MAX 16 FEET N GROUND FAN COMP 1 DEFROST SOLENOID 225 01 6004 225 01 6005 M M PRESSURE SAFETY CONDENSING UNIT C R BLACK 14 WHITE 14 LOWER HOT GAS DEFROST SECTION CONDUCTIVE GLASS HEATER 10 W FT 120VAC 40W 33A 150 01 7850 WARMER 4ft 125 01 0767 10BTV1 CR 40 WATTS 0 33AMP 120V BLACK 14 L1 N OMNI STAT PN 952896 120VAC POWER SUPPLY 115Vac ...

Page 12: ...YELLOW DM10W 1D 1000W 120 VAC 8 33A 125 01 0758 SAFETY SWITCH FLOAT SWITCH PLUG NEMA 5 15P G BLACK 14 WHITE 14 DUPLEX 125 01 0096 CIRCUIT 2 PLUG NEMA 5 15P 125 01 0986 CIRCUIT 1 F28T5 48 125 03 1132 BALLAST 125 01 3266 FULHAM LH3 120 L TOGGLE SWITCH 125 01 0307 BALLAST 125 01 3266 FULHAM LH3 120 L LIGHT CIRCUIT 1 56A 168W BALLAST 125 01 3266 FULHAM LH3 120 L F28T5 48 125 03 1132 F28T5 48 125 03 11...

Page 13: ...v 0 F v 10 F v 30 F v 110 F v 90F 0 F v 106 F v 80 F v 80 F v 80 F v 2000 BTU h 15 F v 2000 BTU h 20 F v ZONE 1 ZONE 2 Condenser Heat Exchanger Compressor Evaporator Evaporator Check Valve TXV TXV 4 way valve Accumulator Receiver EPR Liquid Stop Check Valve Check Valve ...

Page 14: ...ete start up evaluation prior to the loading of food into the refrigerator which includes such items as a Initial temperature performance Coils should be properly fed with a refrigerant according to Hussmann recommendations b Observation of outside influences such as drafts radiant heating from the ceiling and from lamps Such influence should be properly corrected or compensated for c At the same ...

Page 15: ...Are spotlights or other high intensity lighting directed onto the product 7 Are there unusual draft conditions from heating air conditioning ducts open doors etc 8 Is there exposure to direct sunlight 9 Are display signs blocking or diverting airflow 10 Are the coils of the refrigerator iced up 11 Is the store ambient over 75 F 55 RH as set forth in ASHRAE Standard 72 and ASHRAE Standard 117 12 Ar...

Page 16: ...Care must be taken when cross merchandising products to ensure that potentially hazardous vegetable products are not placed in non refrigerated areas e Display and storage equipment doors should be kept closed during periods of inactivity f Minimize the transfer time of perishables from storage to display g Keep meat under refrigeration in meat cutting and processing area except for the few moment...

Page 17: ..._________________________________ _______________ ___________________________________________________________________________________________________ _______________ ___________________________________________________________________________________________________ _______________ ___________________________________________________________________________________________________ _______________ __...

Reviews: