Hussmann MZ3-S Installation & Operation Manual Download Page 5

Rev. 0909 

5

6 .  Prevent condensate drains from freezing:

a. Do not install condensate drains in contact with 

non-insulated suction lines. Suction lines should 

be insulated with a nonabsorbent insulation 

material such as Armstrong’s Armaflex.

b. Where condensate drains are located in dead 

air spaces (between refrigerators or between a 

refrigerator and a wall), provide means to prevent 

freezing. The water seal should be insulated to 

prevent condensation.

Refrigeration

Refrigerant type

The standard refrigerant will be R-404 unless otherwise 

specified on the customer order. Check the serial plate on 

the case for information.
Piping for more than one case on a condensing unit is run 

underground with either common suction and liquid lines 

from the machine room or individual suction and liquid lines 

joined together in the machine room.

Refrigeration lines

 

LIQUID  

SUCTION

 

3/8” O.D.  

5/8” O.D.

note:  the standard coil is piped at 5/8” (suction); however, 

the store tie-in may vary depending on the number 

of coils and the draw the case has. depending on the 

case setup, the connecting point in the store may be 

5/8”, 7/8”, or 1 1/8”. Refer to the particular case you are 

hooking up.

Refrigerant  lines  should  be  sized  as  shown  on  the 

refrigeration legend furnished by the store.
Install 

P-tRaPS

 (oil traps) at the base of all suction line 

vertical risers.

Pressure drop

 can rob the system of capacity. To keep the 

pressure drop to a minimum, keep refrigerant line run as 

short as possible, using the minimum number of elbows. 

Where elbows are required, use long radius elbows only.

control Settings - Remote

See the MZ3-S Technical Data Sheet for the appropriate 

settings for your merchandiser. Maintain these parameters 

to achieve near constant product temperatures. Product 

temperature should be measured first thing in the morning, 

after  having  been  refrigerated  overnight.  Defrost  times 

should  as  directed  in  the  MZ3-S Technical  Data  Sheet. 

The  number  of  defrosts  per  day  should  never  change. 

The duration of the defrost cycle may be adjusted to meet 

conditions present at your location.

control Settings-self contained

All functions are controlled by Omni-Stat Controllers. See  

MZ3-S Technical Data Sheet for proper temperature and 

defrost  settings.

access to tX valves and drain lines

MECHANICAL

  -  Remove  product  from  end  of  case. 

Remove  product  racks.  Remove  refrigeration  and  drain 

access panels (labeled). TX valve (mechanical only) and 

drain are located under each access panel at end of the 

case.

ELECTRONIC

 - The Electronic Expansion valve master 

and  slave  cylinder(s)  are  located  within  the  electrical 

access panel(s).

electronic expansion valve (optional)

A  wide  variety  of  electronic  expansion  valves  and  case 

controllers  can  be  utilized.  Please  refer  to  EEV  and 

controller  manufacturers  information  sheet.  Sensors  for 

electronic expansion valves will be installed on the coil inlet, 

coil outlet, and in the discharge air. (Some supermarkets 

require a 4th sensor in the return air). Case controllers will 

be located in the electrical raceway or under the case.

thermostatic expansion valve location

This device is located on the same side as the refrigeration 

stub. An Alco  balanced  port  expansion  valve  model 

is  furnished  as  standard  equipment,  unless  otherwise 

specified by customer.

expansion valve adjustment

Expansion  valves  must  be  adjusted  to  fully  feed  the 

evaporator. Before attempting any adjustments, make sure 

the evaporator is either clear or very lightly covered with 

frost, and that the fixture is within 10° F of its expected 

operating temperature.

Measuring the operating Superheat

1.   Determine the suction pressure with an accurate 

pressure gauge at the evaporator outlet.

.   From a refrigerant pressure temperature chart, 

determine the saturation temperature at the 

observed suction pressure.

3.   Measure the temperature of the suction gas at the 

thermostatic remote bulb location.

4.   Subtract the saturation temperature obtained in step 

No.  from the temperature measured in step No. 3. 

The difference is superheat.

5.   Set the superheat for 5°F - 7° F

omni-Stat location

The Omni-Stat case controllers are located in the access 

area in the right end panel. To gain access, remove the 

right louvered panel. Please refer to the MZ3-S Technical 

Data Sheet for the proper recommended temperature and 

defrost settings.

Plumbing (cont'd)

Summary of Contents for MZ3-S

Page 1: ...S Multi zone Refrigerated Self Service Self Contained P N IGSS MZ3 S 0909 INSTALLATION OPERATION GUIDE CHINO MZ3 S MULTI ZONE REFRIGERATED SELF SERVICE SELF CONTAINED Rev 0909 Installation Operation Manual ...

Page 2: ...ely and request an inspection Hussmann Chino will acknowledge shortages within ten days from receipt of equipment HUSSMANN CHINO PRODUCT CONTROL The serial number and shipping date of all equipment has been recorded in Hussmann s files for warranty and replacement part purposes All correspondence pertaining to warranty or parts ordering must include the serial number of each piece of equipment inv...

Page 3: ...71 6 20 1 4 18 1 4 16 1 4 37 1 4 30 7 8 27 5 8 19 3 4 10 7 8 9 3 8 9 3 8 1 5 8 1 7 8 1 7 8 1 5 8 50 3 8 47 1 4 37 1 4 6 ELECTRICAL CONNECTION 2 POWER CORDS 1 NEMA 5 15P 2 NEMA L5 20P MZ3 4S PLAN VIEW RCD FMSS LT Condensing Unit MZ3 SELF SERVICE MERCHANDISER ...

Page 4: ...Case must be raised correctly under legs where support is best to prevent damage to case 1 Check level of floor where cases are to be set Determine the highest point of the floor cases will be set off this point 2 Level and set the case Case must be raised under legs where support is best to prevent damage to case Internal bracing may be removed at this time It is the contractor s responsibility t...

Page 5: ...r location Control Settings self Contained All functions are controlled by Omni Stat Controllers See MZ3 S Technical Data Sheet for proper temperature and defrost settings Access to TX Valves and Drain Lines MECHANICAL Remove product from end of case Remove product racks Remove refrigeration and drain access panels labeled TX valve mechanical only and drain are located under each access panel at e...

Page 6: ...rol temp Btu hr ft Parallel 400 Conventional 460 Low Temp Discharge Air F 10 Evaporator F 20 Note Not recommended to control temp by regulating coil temp allow T STAT to cycle and control temp Btu hr ft Parallel 600 Conventional 690 For all refrigeration equipment other than Hussmann use conventional Btu values Defrost Data Frequency Hrs 8 OFFTIME Temp Term F 54 Failsafe Minutes 30 ELECTRIC or GAS...

Page 7: ...both cords before moving or servicing this equipment Attachment Plugs This unit contains two power supply cords Each cord is a different type Connect each plug to a single outlet circuit The first attachment plug is a NEMA 5 15P type plug with a 15 amp rating A 15 amp line is required for the NEMA 5 15P plug The second is a NEMA L5 20P type plug with a 20 amp rating A 20 amp line is require for th...

Page 8: ...t dehydration Recommended Omni Stat Temperature Control Settings RCD 26 FMSS LT 15 See Case Specifications for Details 2 Temperature control is adjusted by the Omni Stat Temperature Controller Case Cleaning Long life and satisfactory performance of any equipment are dependent upon the care given to it To insure long life proper sanitation and minimum maintenance costs the refrigerator should be th...

Page 9: ...t in damage to equipment serious personal injury This includes but not limited to Fans Heaters Thermostats and Lights Replacing Fluorescent Lamps Fluorescent lamps are furnished with moisture resistant lamp holders shields and end caps Whenever a florescent lamp is replaced be certain to reinstall the lamp shield and end caps over the lamp The lamps supplied are single slim line or bi pin type wit...

Page 10: ...t safe and use a soft cloth or plastic scouring pad 3 Use Alkaline Alkaline Chlorinated or Non chloride Containing Cleaners While many traditional cleaners are loaded with chlorides the industry is providing an ever increasing choice of non chloride cleaners If you are not sure of your cleaner s chloride content contact your cleaner supplier If they tell you that your present cleaner contains chlo...

Page 11: ...15V 60 Hz 952892 125 01 2304 AIR TEMP DEFROST TEMP 125 01 2301A MAX 16 FEET N GROUND FAN COMP 1 DEFROST SOLENOID 225 01 6004 225 01 6005 M M PRESSURE SAFETY CONDENSING UNIT C R BLACK 14 WHITE 14 LOWER HOT GAS DEFROST SECTION CONDUCTIVE GLASS HEATER 10 W FT 120VAC 40W 33A 150 01 7850 WARMER 4ft 125 01 0767 10BTV1 CR 40 WATTS 0 33AMP 120V BLACK 14 L1 N OMNI STAT PN 952896 120VAC POWER SUPPLY 115Vac ...

Page 12: ...YELLOW DM10W 1D 1000W 120 VAC 8 33A 125 01 0758 SAFETY SWITCH FLOAT SWITCH PLUG NEMA 5 15P G BLACK 14 WHITE 14 DUPLEX 125 01 0096 CIRCUIT 2 PLUG NEMA 5 15P 125 01 0986 CIRCUIT 1 F28T5 48 125 03 1132 BALLAST 125 01 3266 FULHAM LH3 120 L TOGGLE SWITCH 125 01 0307 BALLAST 125 01 3266 FULHAM LH3 120 L LIGHT CIRCUIT 1 56A 168W BALLAST 125 01 3266 FULHAM LH3 120 L F28T5 48 125 03 1132 F28T5 48 125 03 11...

Page 13: ...v 0 F v 10 F v 30 F v 110 F v 90F 0 F v 106 F v 80 F v 80 F v 80 F v 2000 BTU h 15 F v 2000 BTU h 20 F v ZONE 1 ZONE 2 Condenser Heat Exchanger Compressor Evaporator Evaporator Check Valve TXV TXV 4 way valve Accumulator Receiver EPR Liquid Stop Check Valve Check Valve ...

Page 14: ...ete start up evaluation prior to the loading of food into the refrigerator which includes such items as a Initial temperature performance Coils should be properly fed with a refrigerant according to Hussmann recommendations b Observation of outside influences such as drafts radiant heating from the ceiling and from lamps Such influence should be properly corrected or compensated for c At the same ...

Page 15: ...Are spotlights or other high intensity lighting directed onto the product 7 Are there unusual draft conditions from heating air conditioning ducts open doors etc 8 Is there exposure to direct sunlight 9 Are display signs blocking or diverting airflow 10 Are the coils of the refrigerator iced up 11 Is the store ambient over 75 F 55 RH as set forth in ASHRAE Standard 72 and ASHRAE Standard 117 12 Ar...

Page 16: ...Care must be taken when cross merchandising products to ensure that potentially hazardous vegetable products are not placed in non refrigerated areas e Display and storage equipment doors should be kept closed during periods of inactivity f Minimize the transfer time of perishables from storage to display g Keep meat under refrigeration in meat cutting and processing area except for the few moment...

Page 17: ..._________________________________ _______________ ___________________________________________________________________________________________________ _______________ ___________________________________________________________________________________________________ _______________ ___________________________________________________________________________________________________ _______________ __...

Reviews: