56
AK-CC 210
Manual RS8EP502 © Danfoss 12-2015
15
Copy from the programming key
This function downloads a set of settings earlier saved in the controller. Select the
relevant number.
All settings except for Application (o61) and Address (o03) will be copied. When copy-
ing has started the display returns to o66. After two seconds you can move back into
the menu again and check whether the copying was satisfactory. Showing of a nega-
tive figure spells problems. See the significance in the Fault Message section.
o66
-
Save as factory setting
With this setting you save the controller’s actual settings as a new basic setting (the
earlier factory settings are overwritten).
o67
-
- - - Night Setback
0=Day
1=Night
Service
Service
Temperature measured with S5 sensor
u09
S5 temp.
Status on DI1 input. on/1=closed
u10
DI1 status
Temperature measured with S3 sensor
u12
S3 air temp
Status on night operation (on or off ) 1=closed
u13
Night Cond.
Temperature measured with S4 sensor
u16
S4 air temp
Thermostat temperature
u17
Ther. air
Read the present regulation reference
u28
Temp. ref.
Status on DI2 output. on/1=closed
u37
DI2 status
Temperature shown on display
u56
Display air
Measured temperature for alarm thermostat
u57
Alarm air
** Status on relay for cooling
u58
Comp1/LLSV
** Status on relay for fan
u59
Fan relay
** Status on relay for defrost
u60
Def. relay
** Status on relay for railheat
u61
Railh. relay
** Status on relay for alarm
u62
Alarm relay
** Status on relay for light
u63
Light relay
** Status on relay for valve in suction line
u64
SuctionValve
** Status on relay for compressor 2
u67
Comp2 relay
*) Not all items will be shown. Only the function belonging to the selected applica-
tion can be seen.