background image

Diagnostic functions 

Chapter 7 

TECHNICAL BULLETIN 

 

V1.2.0en/05.02.16 

Liability for errors and misprints excluded. 

Profibus® Gateway SE 

11 

7

 

Diagnostic functions 

7.1

 

On commissioning 

The LEDs 1 (LSB), 2, 4 and 8 show the binary value of the version stored in the module if the Profibus 

plug is unplugged and the position of the two switches S4 and S5 is set to zero. The standard version 

has the number 1. The module immediately goes into communication mode with the device con-

nected to the serial interface if switch S4 is set to zero and the switch S5 to one before applying the 

operating voltage. This tests the wiring to the temperature control unit. LED “8” has a special role. It 

is illuminated when a command is sent from the Profibus Gateway SE via the serial interface and 

turns off after a response has been received. 

 

The Profibus plug must not be plugged in when in this mode! 

To exit this mode, reset the two switches S4 and S5 to zero and interrupt the operating voltage for 

about 30 seconds. 

7.2

 

During operation 

When communication is transmitted via the Profibus - recognizable by the green illuminated LEDs 

Bus and State - LED “8” signals a communication of the Profibus Gateway SE via the serial interface. 

The procedure is the same as described above. 

7.3

 

Troubleshooting 

Verify on the Profibus side whether the bus termination is set correctly. A difference between the 

GSD file and the program in the Profibus Gateway SE may cause bus errors or incorrect data content. 

The version is specified in the GSD file. It can be checked with the diagnostics function. 

Summary of Contents for Profibus SE

Page 1: ...Technical Bulletin Profibus Gateway SE V1 2 0...

Page 2: ...TECHNICAL BULLETIN Profibus Gateway SE Liability for errors and misprints excluded V1 2 0en 05 02 16 2...

Page 3: ...TECHNICAL BULLETIN V1 2 0en 05 02 16 Liability for errors and misprints excluded Profibus Gateway SE 3 Profibus Gateway SE...

Page 4: ...TECHNICAL BULLETIN Profibus Gateway SE Liability for errors and misprints excluded V1 2 0en 05 02 16 4...

Page 5: ...into the process automation system 8 5 1 Basic mode of operation of the Profibus Gateway SE 8 5 2 Description of the standard variant 8 6 Properties of standard variables 9 6 1 vSP Setpoint temperatur...

Page 6: ...standard version presented is designed to cover a large number of process requirements We can offer a customized version if you have addi tional requirements Please note the inherent restrictions of E...

Page 7: ...topology in accordance with the requirements of the PROFIBUS user organization A bus termination can be enabled on the Pro fibus Gateway SE The Profibus Gateway SE has been built and qualified in acc...

Page 8: ...fore always available when retrieving the process image The temperature control unit can immediately return the current process values when a Profibus frame is received On the other hand the update lo...

Page 9: ...lute Absolute pump pressure at the pressure sensor in the thermal fluid circuit of the thermostat only if there is a pressure sensor 6 4 vError Error report The number of the error report that appeare...

Page 10: ...e activated not activated 14 Restart electronics Power failure no restart restart 15 Freeze protection not available on all devices active inactive This bit is reset to 0 when the control is restarted...

Page 11: ...illuminated when a command is sent from the Profibus Gateway SE via the serial interface and turns off after a response has been received The Profibus plug must not be plugged in when in this mode To...

Page 12: ...Diagnostic functions TECHNICAL BULLETIN Chapter 7 Profibus Gateway SE Liability for errors and misprints excluded V1 2 0en 05 02 16 12...

Page 13: ......

Page 14: ...Peter Huber K ltemaschinenbau AG Werner von Siemens Stra e 1 D 77656 Offenburg Germany tel 49 781 9603 0 fax 49 781 57211 e mail info huber online com www huber online com Hotline 49 781 9603 244...

Reviews: