Hubbel Chance BP3 Installation, Operation And Maintenance Manual Download Page 3

3 of 12

P805-0011 Rev. A

©

2002 Hubbell Power Systems, Inc., 210 North Allen Street, Centralia, MO 65240 U.S.A.

Hazardous voltage.

Will cause severe personal injury, death, or property damage.

Only qualified personnel should work on or around this equipment after
becoming thoroughly familiar with this document and other publications
regarding this equipment.

!

 

  DANGER

Qualified Person

Only qualified trained and competent
personnel that understand proper safety
procedures must select, install and service
this equipment.

Read and understand these instructions be-
fore installing, operating or maintaining this
equipment.

This guide is not a substitute for adequate
training and experience in safety procedures
for this type of equipment.

Signal Words

The signal words “DANGER,” “WARNING”
and “CAUTION” (along with their assigned
symbol) throughout this manual indicate the
degree of hazard the user may encounter.
These symbols and words are defined as:

DANGER indicates an imminently hazardous
situation which, if not avoided, will result in
death or serious injury.

WARNING indicates a potentially hazardous
situation which, if not avoided, could result in
death or serious injury.

CAUTION indicates a potentially hazardous
situation which, if not avoided, may result in
minor or moderate injury.

CAUTION used without the safety alert sym-
bol indicates a potentially hazardous situation
which, if not avoided, may result in property
damage.

!

 

  DANGER

!

 

 WARNING

!

 

 CAUTION

CAUTION

Product

The products covered by this manual are
the BP3 3-Pull overhead by-pass switches
for medium voltage electrical distribution
switching.

These products are designed for distribution
switching only at their rated capacities. They
cannot be field modified for capacities other
than what was shipped with the units. If a
different capacity is desired, contact your
supervisor or factory representative to se-
cure the appropriate unit.

Overview

Function

These products are non-loadbreak discon-
nect switches designed to provide a means
for by-passing, disconnecting and isolating
reclosers or similar devices on the electrical
distribution system.

General

The BP3 By-Pass Switch is a single-phase
3-blade, 3-pull, hookstick operated switch.  It
is used for manually disconnecting a
recloser without interrupting normal electri-
cal service.  Standard variations are:

1. Right or left opening by-pass blade

operation

2. Switch mounting

3. Terminal connections

4. Loadbreak hooks on disconnect blades.

The BP3 switch has no inherent current
making or breaking capacity. The by-pass
blade includes a hook for use with a load-
break tool. The BP3 has no deadending pro-
visions.

Specifications

Select the proper BP3 switch for each instal-
lation with consideration to voltage, continu-
ous current, short time current withstand, light-
ning impulse withstand and variations. If there
is concern about the use of this switch as rated,
consult your supervisor before installation.

Nominal voltage ratings of 14.4 kV, 25
kV or 34.5 kV (model dependent)

Lightning impulse peak withstand ratings
of 110 kV, 125kV or 150 kV (model
dependent)

Continuous current rating of 600
amperes

Short time current withstand rating:
25 kA symmetrical, 1 second
65 kA peak

Switch Variations

1. Right or Left By-Pass Blade Opening

Right or left by-pass blade opening may be
specified. A right opening by-pass blade
opens to the right of the operator when
standing in front of the switch.  A left open-
ing by-pass blade opens to the left.  Illustra-
tions in this manual show only right by-pass
blade opening. Left by-pass blade opening
will be opposite as shown but does not
change installation or operation procedures.

Summary of Contents for Chance BP3

Page 1: ...pe BP3 3 Pull By Pass Switch for Distribution Switching HUBBELL POWER SYSTEMS INC 210 North Allen Street Centralia MO 65240 1395 U S A Telephone 573 682 5521 IMPORTANT Keep this manual readily availab...

Page 2: ...with established safety practices c trained in the proper care and use of protective equipment such as rubber gloves hard hat safety glasses or face shields flash clothing etc in accordance with estab...

Page 3: ...ified for capacities other than what was shipped with the units If a different capacity is desired contact your supervisor or factory representative to se cure the appropriate unit Overview Function T...

Page 4: ...ing without the use of a back strap or pole mounting bracket The structure must be drilled to match the base mounting holes or slots The user supplies the mounting hard ware 3 Terminal Connectors 3 va...

Page 5: ...ch base Leave switch on its pallet until ready to install Compare switch with the photo to be sure all items have been included Contact your factory representative if any parts are missing If desired...

Page 6: ...vided back strap and appropriate length bolts Adjust the bolts in the switch base and back strap slots to fit close to the vertical structure Torque mounting hardware nuts to 60 ft lb Leave bolt head...

Page 7: ...onductors will be secured Wire brush conductor surfaces Apply a contact sealing paste to the cleaned surfaces A B Chance Z L N or equivalent Assemble connectors conductors and hardware to the switch t...

Page 8: ...rmal Operating Position By Pass Operating Position Recloser Recloser By Pass Switch By Pass Blade Source Load Disconnect Blade Disconnect Blade Recloser Recloser By Pass Switch By Pass Blade Source Lo...

Page 9: ...ead and look away from the switch Quickly firmly and without hesitation pull down and towards the hinge end of the switch at about a 45 angle Figure 8 Once the switch is open complete the blade travel...

Page 10: ...single sided loadbreak hooks The loadbreak hooks allow the use of a loadbreak tool for the switching of load capacitor line cable charging and magnetizing currents To open loadbreak hook equipped disc...

Page 11: ...enance check at least once a year more frequently if located in a contaminated area For additional recommendations refer to ANSI C37 35 IEEE Guide for the Applica tion Installation Operation And Maint...

Page 12: ...12 of 12 P805 0011 Rev A 2002 Hubbell Power Systems Inc 210 North Allen Street Centralia MO 65240 U S A Notes Records...