Maintenance

General

Prolong the life of the BP3 By-Pass switch
with a periodic inspection and maintenance
program. Although the switch is designed for
long-term exposure in all weather condi-
tions, certain environments may reduce its
life without periodic maintenance. Following
these minimum inspection and maintenance
procedures will help ensure long service life.

!

 

  DANGER

Hazardous voltage.

Contact with energized lines will result in death, personal injury or
property damage.

All maintenance work should be performed on de-energized switches. If
work must be performed on live lines, follow your company’s standard
safe operating procedures.

Hazardous voltage.

Can cause death, severe personal injury.

Contact with the switch bases, hardware or crossarm could result in
electrical shock. Ground the switch bases and mounting hardware prior
to maintenance.

!

 

 WARNING

Note: It is recommended that all switches
go through a maintenance check at least
once a year; more frequently if located in
a contaminated area.

For additional recommendations, refer to
ANSI C37.35 “IEEE Guide for the Applica-
tion, Installation, Operation, And Mainte-
nance of High Voltage Air Disconnect and
Load Interrupter Switches."

Switch

Operate the switch periodically to clean con-
tact surfaces to keep parts moving freely.

• Check for burned or pitted contacts and

replace if necessary. Lubricate if neces-
sary with Optimol

® 

grease C600-2870

• Check the hinge bolts for looseness.  If

loose, clean bolt threads, apply Loctite

®

-

271 and torque to 40-in-lb.

• Inspect all blade rivets for tightness and

replace blade assembly if loose.

• Inspect the mounting hardware and

tighten according to specifications located
in the Installation Section of the manual.

• Replace any damaged or tracked insula-

tors. Clean or replace if heavily contami-
nated. Consult your factory representative
for authorized replacement insulators.

Conductors

• Be sure all conductors are routed so they

do not interfere with switch operation

• Inspect all conductors to be sure termina-

tions are tight and corrosion free

• If necessary, clean and apply contact

sealing paste (A.B. Chance Z.L.N. or
equivalent) and retighten terminations.

Summary of Contents for Chance BP3

Page 1: ...pe BP3 3 Pull By Pass Switch for Distribution Switching HUBBELL POWER SYSTEMS INC 210 North Allen Street Centralia MO 65240 1395 U S A Telephone 573 682 5521 IMPORTANT Keep this manual readily availab...

Page 2: ...with established safety practices c trained in the proper care and use of protective equipment such as rubber gloves hard hat safety glasses or face shields flash clothing etc in accordance with estab...

Page 3: ...ified for capacities other than what was shipped with the units If a different capacity is desired contact your supervisor or factory representative to se cure the appropriate unit Overview Function T...

Page 4: ...ing without the use of a back strap or pole mounting bracket The structure must be drilled to match the base mounting holes or slots The user supplies the mounting hard ware 3 Terminal Connectors 3 va...

Page 5: ...ch base Leave switch on its pallet until ready to install Compare switch with the photo to be sure all items have been included Contact your factory representative if any parts are missing If desired...

Page 6: ...vided back strap and appropriate length bolts Adjust the bolts in the switch base and back strap slots to fit close to the vertical structure Torque mounting hardware nuts to 60 ft lb Leave bolt head...

Page 7: ...onductors will be secured Wire brush conductor surfaces Apply a contact sealing paste to the cleaned surfaces A B Chance Z L N or equivalent Assemble connectors conductors and hardware to the switch t...

Page 8: ...rmal Operating Position By Pass Operating Position Recloser Recloser By Pass Switch By Pass Blade Source Load Disconnect Blade Disconnect Blade Recloser Recloser By Pass Switch By Pass Blade Source Lo...

Page 9: ...ead and look away from the switch Quickly firmly and without hesitation pull down and towards the hinge end of the switch at about a 45 angle Figure 8 Once the switch is open complete the blade travel...

Page 10: ...single sided loadbreak hooks The loadbreak hooks allow the use of a loadbreak tool for the switching of load capacitor line cable charging and magnetizing currents To open loadbreak hook equipped disc...

Page 11: ...enance check at least once a year more frequently if located in a contaminated area For additional recommendations refer to ANSI C37 35 IEEE Guide for the Applica tion Installation Operation And Maint...

Page 12: ...12 of 12 P805 0011 Rev A 2002 Hubbell Power Systems Inc 210 North Allen Street Centralia MO 65240 U S A Notes Records...

Reviews: