5

Test setting interface

● Battery power indicator: , , , ,

When the battery voltage display shows only one bar left, it should be charged in time.

When the battery display flashes, the power supply will be automatically cut off at any time

and the battery should be charged immediately.

● Charging: Provide the AC power source that meets the requirements for the panel AC

socket to charge the instrument. When charging, the power indicator light is on, and the

battery indicator on the display screen displays from (0 grid) to (full grid). When it is full, it

displays (full grid).

● System help menu description

Help: Record the product number, production date, and version information.

● Insulation test interface

V.Instrument use

● Voltage measurement:

1. The L end of the test line of the instrument is connected to the tested product, and the E

end is grounded.

0

100k

1M 10M 100M 1G

100G

10G

1T 10T

5000V

10:00

>10.0TΩ

set:
5100

A:  10.00nA

C:   1.00uF

01:00

  R15:  1.000G
  R30:  1.500G

R60:  2.00G

R600:  3.00G

DAR: 2.00

PI:  1.5

关 机

保 存

打 印

返 回

Summary of Contents for HZJY-10K-IA

Page 1: ...HZJY 10K IA Insulation Resistance Tester User Manual Huazheng Electric Manufacturing Baoding Co Ltd...

Page 2: ...al and operate and maintain the instrument according to the manual to prolong its service life Just a light press the test will be completed automatically is the operating characteristics of this inst...

Page 3: ...Contents I Safe Use Items 1 II Features 2 III Technical specifications 3 IV Instrument introduction 4 V Instrument use 5 VI Appendix 7...

Page 4: ...erious or fatal damage Before use please wear insulated gloves Please do not over AC DC600V measurement circuit Please do not test in flammable places spark could cause an explosion please do not hand...

Page 5: ...nt and capacitance as well as dielectric discharge test DD step voltage test SV ramp test the instrument automatically boosts Until the set value it is qualified If it is not reached there is a breakd...

Page 6: ...l value Output voltage monitoring accuracy 5 10V Voltage measurement range AC 30 600V 50HZ 60HZ DC 30 600V Voltage measurement accuracy 2 3dgt Current test range 10mA Current measurement accuracy 5 0...

Page 7: ...utton 6 High voltage indicator Keys and function description There are 5 buttons in total from left to right The first one is the power on button in the shutdown state Button No Instruction 1 Power on...

Page 8: ...When charging the power indicator light is on and the battery indicator on the display screen displays from 0 grid to full grid When it is full it displays full grid System help menu description Help...

Page 9: ...stance values of 15S 60S and 600S and calculates the polarization index after 600 seconds Polarization index calculation method PI R600 R60 DD test This test is suitable for the diagnosis of multilaye...

Page 10: ...should be connected to the G terminal of the meter with a test wire to eliminate the leakage current caused by the surface of the test product The measurement error ensures the accuracy of the test Es...

Reviews: