background image

1

I.Preface

During the processing of the semi-finished products and the finished products in

transformer production, the transformer newly installation before using, or according to

IEC and national standard, the turns ratio or voltage ratio should be tested in the circle

rate. Traditional bridge method is complicated, and can’t read the data directly, and you

have to make conversion, the testing results are data of one phase. Turns ratio tester of

HZBB-10A overcomes the shortcomings of traditional bridge method. The monitor adopts

big screen with lattice liquid crystal, which has the function of indicating by menu,

operating easily and directly. It finishes test of three-phase voltage ratio or turns ratio once,

fast testing and high precise.

II. Functions And Characters

1. The three-phase precision inverter power supply is used inside the instrument, which

eliminates the influence of harmonics of the mains voltage during measurement, and the

measurement is more accurate. When the working power source is a generator, there is no

impact.

2. Three-phase output voltage is adopted to improve the test speed. The angle between

phases can be measured, and the wiring group 0-11 can be automatically identified. For

low-voltage rectifier transformers with multiple windings, the low-voltage side does not

need to be disconnected to measure the transformation ratio and 7.5° Angle deviation.

3. It is suitable for a wide variety of transformers, especially suitable for the measurement

of Z-type transformers, rectifier transformers, grounding transformers, electric furnace

transformers, phase shifting transformers, balance transformers, etc.

4. It has high and low voltage reverse connection protection, transformer turn short circuit

protection, tap switch failure protection, output full short circuit protection, and increased

instrument stability.

5. After inputting the rated parameter, it can automatically measure the transformer ratio

value, error value and on-load tap-changer position.

6. Adopt 7-inch high-definition color touch-screen LCD, modular display, clear display even

Summary of Contents for HZBB-10A

Page 1: ...HZBB 10A Transformer Turns Ratio Tester Huazheng Electric Manufacturing Baoding Co Ltd...

Page 2: ...al and operate and maintain the instrument according to the manual to prolong its service life Just a light press the test will be completed automatically is the operating characteristics of this inst...

Page 3: ...d Characters 1 III Technical Index 2 IV Operating Panel Instructions 2 V Operating Instructions VI Connecting Method 3 VII Notice 9 VIII Instrument Common Problems And Inspection Methods 10 VIII After...

Page 4: ...ement and the measurement is more accurate When the working power source is a generator there is no impact 2 Three phase output voltage is adopted to improve the test speed The angle between phases ca...

Page 5: ...0000 Angle 0 360 2 Angle measurement 0 360 3 Accuracy 0 1 below500 0 2 501 2000 0 5 2001 10000 4 Output voltage automatically adjusted according to load 5 Resolution Minimum is 0 0001 Angle 0 01 6 Wor...

Page 6: ...220V frequency power supply 5 Protective grounding column 6 Communication serial communication 7 USB U disk storage 8 Printer Print the testing results after tested V Instructions Menu description Fig...

Page 7: ...e phase measurement z type transformer Scott transformer setting method are basically the same no longer repeat Test completion interface as shown below Figure 3 test completion interface 2 After the...

Page 8: ...4 Click Time Setting to enter the time setting interface as shown in Figure 5 Figure 5 Click Year Month Day Hour Minute Second and the keyboard will pop up to set the time After entering the value cli...

Page 9: ...Figure 7 Transformation ratio Click the transformation ratio button to switch to turns ratio data Previous Next You can view and print historical data Dump is to store the current data to the U disk P...

Page 10: ...ord input and the user does not need to modify it Bluetooth Click Bluetooth to pop up the QR code as shown in Figure 9 scan the QR code with the corresponding software downloaded in the mobile phone t...

Page 11: ...ing Object The Tester Idle Black 2 525 3 4 2 50 20 Single Phase Transformer and High Voltage connecting is according to the Diagram 2 as follows A O a b O Green Black Black Yellow Yellow Low Voltage H...

Page 12: ...tapping the voltage combination of 110 8 1 25 10 0 transformers the rated tapping is 8 1 means 9 Enter the rated bit This gives an accurate measurement of the tapping position of the transformer whos...

Page 13: ...sition and actual position inversion 8 Low voltage level of the transformer when the input voltage value is not enough the high and low voltage can be multiplied by 10 or 100 and so on 9 To test the S...

Page 14: ...e side VIII After sale Service The product can be repaired free of charge or changed by a new one if it has quality problem for one year from sale We can provide reparation and technical services for...