background image

3

data on the relationship between ionization charge and vacuum degree of almost all

vacuum interrupters at home and abroad, and send their characteristic parameters to

this series through mathematical processing. product. Therefore, this series of products

have built-in measurement curves of almost all vacuum interrupters at home and abroad,

which is unique among similar products at home and abroad.

4. Treatment of leakage current

When a negative ion current is applied to the moving contact of the vacuum interrupter in

the breaking state, the static contact end will have a leakage current of several

microamps, even if it is the same type of vacuum. The interrupter also has large

individual differences. Especially for the vacuum interrupter installed on the complete

machine, because of the leakage of the surrounding insulating supports, the sum of

these leakages has greater instability and unpredictability. And the value is equivalent to

the ionization current of the vacuum interrupter of the order of 10E-4Pa. We adopt the

method of secondary starting high voltage, deducting the leakage current, and guarantee

the vacuum measurement accuracy of the vacuum interrupter whether installed on the

whole machine or to be installed.

5. Identify the completely leaking vacuum interrupter

In this machine, it is judged whether the vacuum interrupter is completely leaking by

means of high pressure breakdown.

6. Complete input protection circuit

When the vacuum degree of the vacuum interrupter is very low, the vacuum interrupter

will be broken down by high voltage during the measurement, and the instant high

voltage is directly applied to the negative ion current sampling circuit, making it bear a

very strong electrical shock. The sampling circuit adds a complete protection circuit.

Even if the instrument is the first time because the high voltage at the input terminal is

directly applied to the negative ion current sampling terminal, the microcomputer

protection device will immediately start to control and enter the protection state without

causing serious damage to the circuit.

7. Data recording

Built-in micro-printer can print out the measured data at any time.

Summary of Contents for HZ-ZKD

Page 1: ...HZ ZKD Vacuum switch vacuum tester User Manual Huazheng Electric Manufacturing Baoding Co Ltd...

Page 2: ...and operate and maintain the instrument according to the manual to prolong its service life Just a light press the test will be completed automatically is the operating characteristics of this instrum...

Page 3: ...ntents I Overview II Key Function And Feature III Major Technical Indicators IV Operational Approach V Precautions VI Maintenance VII Oil Cup Cleaning Method and Common Fault Clearances IX Packing Lis...

Page 4: ...grid voltage matches the power supply voltage of the machine AC 220 10 50 60HZ 7 Please be careful not to use the machine under thunderstorm conditions 8 Please do not damage the cables that come wit...

Page 5: ...vacuum degree in the vacuum interrupter has a very accurate correspondence with the amount of ionized charge The peak value of ionization current is only indirectly related to probability Therefore o...

Page 6: ...errupter of the order of 10E 4Pa We adopt the method of secondary starting high voltage deducting the leakage current and guarantee the vacuum measurement accuracy of the vacuum interrupter whether in...

Page 7: ...ollide with residual gas molecules to ionize The ion current generated is approximately proportional to the residual gas density that is the degree of vacuum For vacuum tubes with different diameters...

Page 8: ...put the magnetron current required for the test to accelerate the electron flow to reduce the influence of various external factors on the measurement accuracy 3 High voltage output terminal used to o...

Page 9: ...rint key After the measurement is over print out the measured data The print button light is on and effective Check key If there is no alternative parameter you can use the check key This can directly...

Page 10: ...the on position and the word P appears in the first digit of the digital display After verification step 3 2 is normal the instrument is operating normally and it can be started after 5 minutes of wa...

Page 11: ...ubble tube type into the tube type of the instrument display window If the tube type to be measured is not indicated in the manual the diameter outer diameter of the vacuum bubble can be measured on s...

Page 12: ...ean because the surface is dirty which may cause the leakage current to change value greater than the ionization current value In this way the measured value after subtracting the leakage current is l...

Reviews: