1 Precise point operation procedure

When you are close to the point of failure, please follow the sequence of procedures

below

Steps

Action

1

Place the HZ-B's ground-penetrating microphone in the starting

position.

2

If HZ-B cannot pick up any sound signal at this measuring point.

Please follow the path of the cable under test. When you find that HZ-B

receives the first useful impact discharge sound signal, the left side of

the LCD of HZ-B host will automatically display the sound level of the

measurement point.

If you are unable to pick up the shock discharge sound signal

through a ground-penetrating microphone or headphones in a long area,

you should try to make a precise point from the starting point in the

opposite direction.

3

Please continue to follow the path of the cable under test and move

one step at a time. If necessary, adjust the position of the central axis of

the cable under test at any time. At each measurement point, please

stay a few impulse discharge pulse signals.

When you are near the cable fault point, you will hear a stronger

knocking sound, and the sound level of the current measurement point

displayed by HZ-B will suddenly increase.

4

Please rotate the HZ-B ground-penetrating microphone 180 ° and

use a smaller step to approach the fault point again.

5

Please continue to reduce the step distance, look for the place

where the fault is the loudest, and determine the location of the fault

point as accurately as possible. Then make an accurate mark on the

ground.

Summary of Contents for HZ-B

Page 1: ...HZ B Cable Fault Precise Determination Point Tester Huazheng Electric Manufacturing Baoding Co Ltd...

Page 2: ...II Technical characteristics 1 III Technical parameter 1 IV On site installation and operation of HZ B cable fault precise determination point tester 3 V Start to use cable fault HZ B pinpoint tester...

Page 3: ...at the front end the impulse discharge sound of the fault point within the distance of the thick side propagates on the ground above the cable and is recorded by the ground penetrating sensor on the...

Page 4: ...microphone One height adjustable handle height range 450 750 mm One headphone with sound quality One signal line connecting the main unit of the receiver with the sensor 1 20 m long One hard ground p...

Page 5: ...s turned on sensor preparation 1 Connect the sensor to a suitable probe or probe The HZ B sensor can be connected to two different probes The standard configuration includes an 18mm long hard ground p...

Page 6: ...power on off key of the receiver After more than ten seconds the host computer of the receiver is ready to use then the test interface will be displayed 5 2 Battery self test When you turn it on pleas...

Page 7: ...le fault HZ B pinpoint tester Please connect the high voltage integrated impulse generator high voltage unit to the faulty cable and start to apply the appropriate impulse voltage to cause flashover b...

Page 8: ...a you should try to make a precise point from the starting point in the opposite direction 3 Please continue to follow the path of the cable under test and move one step at a time If necessary adjust...

Page 9: ...ument This instrument can only be used by authorized electrical professional staff The electrical professional staff refers to holding the high voltage electrician license and above qualification issu...

Reviews: