UPS5000-E-(360 kVA-480 kVA)
User Manual (40 kVA Power Modules)
5 Operations
Issue 07 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
182
Figure 5-47
Associated intelligent power supply parameters on the LCD 6
Table 5-2
Associated intelligent power supply parameters
Parameter
Automatic Settings
Remarks
Working mode
ECO
N/A
D.G. mode
Enable
You cannot modify this
parameter if it is set
automatically.
Intra-rack power module
start delay (s)
5
N/A
Input adaptability
Strong
N/A
Output freq. track rate
(Hz/s)
0.6
N/A
D.G. connection [GEN]
Enable
N/A
MUS05A DO_4
D.G. control
N/A
ATS
Connected
N/A
D.G. startup batt. volt.
(V/cell)
1.80
N/A
D.G. power limiting (kVA)
N/A
Set this parameter to the actual
power of the D.G.
D.G. charger power ratio
(%)
N/A
Set this parameter to the
percentage of the power
provided by the charger for
batteries.
In battery mode (non-battery test), if the battery voltage reaches the value specified by
D.G. startup
batt. volt.
or
Low battery voltage
, the signal for starting the D.G. is triggered.