UPS5000-E-(360 kVA-480 kVA)
User Manual (40 kVA Power Modules)
5 Operations
Issue 07 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
155
Figure 5-7
System Param. screen 2
Step 3
If no exception alarm is reported on the monitoring page after you specify settings on the
Settings Wizard
screen, perform subsequent steps. If exception alarms are reported on the
monitoring page, clear all the alarms.
Tap
System Info
>
Settings
>
Dry contacts
. Set the dry contacts that are used to
Enabled
and the
dry contacts that are not used to
Disabled
.
Step 4
Check that the bypass input is normal and the system has transferred to bypass mode. You can
confirm this by viewing the system running diagram on the LCD.
Step 5
Start the inverter.
Method for starting the inverter on the LCD
a.
On the main screen, tap
Common Functions
. Tap
Inv. ON
.
b.
If you have not logged in, enter a user name and password, and tap
on
the login screen displayed.
Figure 5-8
Login
c.
In the displayed dialog box, tap
Yes
to start the inverter.