UPS2000-G-(3 kVA-20 kVA)-V2 
User Manual (Two Live Wires) 

4 Control Panel 

 

Issue 07 (2019-12-19) 

Copyright © Huawei Technologies Co., Ltd. 

62 

 

 

Multiple statuses can be associated with one dry contact, but one status cannot be associated with 
multiple dry contacts. 

 

Normal mode

 parameter 

Set the output dry contact associated with normal mode. When the UPS is in normal 
or ECO mode, this dry contact is enabled. The value ranges from 

Dry contact1

 to 

Dry contact6

. The default value is 

Dry contact1

 

Battery mode

 parameter 

Set the output dry contact associated with battery mode. When the UPS is in battery 
or ECO mode, this dry contact is enabled. The value ranges from 

Dry contact1

 to 

Dry contact6

. The default value is 

Dry contact2

 

Bypass mode

 parameter 

Set the output dry contact associated with bypass mode. When the UPS is in bypass 
or ECO mode, this dry contact is enabled. The value ranges from 

Dry contact1

 to 

Dry contact6

. The default value is 

Dry contact3

 

Batt. undervolt

 parameter 

Set the output dry contact associated with low battery voltages. When the system 
battery voltage is low, this dry contact is enabled. The value ranges from 

Dry 

contact1

 to 

Dry contact6

. The default value is 

Dry contact4

 

BPS backfeed

 parameter 

Set the output dry contact associated with bypass backfeed. When a bypass 
backfeed alarm is generated, this dry contact is enabled. The value ranges from 

Dry 

contact1

 to 

Dry contact6

. The default value is 

Dry contact5

 

Faulty UPS

 parameter 

Set the output dry contact associated with UPS faults. When a critical alarm is 
generated, this dry contact is enabled. The value ranges from 

Dry contact1

 to 

Dry 

contact6

. The default value is 

Dry contact6

System Parameters Screen 

 

Parallel 

screen 

Figure 4-30

 

Parallel screen 

 

 

 

Single/Parallel

 parameter 

The values include 

Single

 and 

Parallel

. The default value is 

Single

. The parameter 

is configurable after the inverter shuts down. 

 

Redundant UPSs

 parameter 

Set the number of redundant UPSs. The value ranges from 0 to 3. The default value 
is 0. The parameter is configurable after the inverter shuts down. 

 

Output 

screen 

Summary of Contents for UPS2000-G-10KRTLV2

Page 1: ...UPS2000 G 3 kVA 20 kVA V2 User Manual Two Live Wires Issue 07 Date 2019 12 19 HUAWEI TECHNOLOGIES CO LTD ...

Page 2: ...tomer All or part of the products services and features described in this document may not be within the purchase scope or the usage scope Unless otherwise specified in the contract all statements information and recommendations in this document are provided AS IS without warranties guarantees or representations of any kind either express or implied The information in this document is subject to c...

Page 3: ...ioning Engineer Data Configuration Engineer Maintenance Engineer Symbol Conventions The symbols that may be found in this document are defined as follows Symbol Description Indicates a hazard with a high level of risk which if not avoided will result in death or serious injury Indicates a hazard with a medium level of risk which if not avoided could result in death or serious injury Indicates a ha...

Page 4: ...ontains all the changes made in earlier issues Issue 07 2019 12 19 Added the USB port description for the new product structure Issue 06 2019 05 05 Updated the section Operating Environment Issue 05 2018 01 16 Added the description of device application scenarios Issue 04 2017 11 27 Updated the section Operating Environment Issue 03 2017 07 03 This is the third release Issue 02 2016 01 06 The shor...

Page 5: ... 11 1 8 Others 13 2 Quick Introduction 15 2 1 Model Description 15 2 2 Working Principle 16 2 2 1 Conceptual Diagram 16 2 2 2 Working Modes 17 2 3 Appearance 17 2 4 Optional Components 21 3 Installation 28 3 1 Preparations 28 3 1 1 Site 28 3 1 2 Tools 30 3 1 3 Power Cables 31 3 1 4 Unpacking and Checking 37 3 2 Installation Procedure 38 3 3 Installing a Backfeed Protection Device 38 3 3 1 Feedback...

Page 6: ...PS 80 5 2 3 Performing EPO 81 5 3 Parallel System Operations 81 5 3 1 Starting the Parallel System 82 5 3 2 Shutting down the Parallel System 85 5 3 3 Performing EPO 86 6 Communications 87 6 1 Optional Communications Components 87 6 2 SNMP Card 87 6 3 Modbus Card 88 6 4 Dry Contact Card 88 7 Routine Maintenance 89 7 1 UPS Maintenance 89 7 2 Battery Maintenance 90 8 Troubleshooting 95 9 Technical S...

Page 7: ...9 12 19 Copyright Huawei Technologies Co Ltd vi A Parallel Parameter List 110 B LCD Menus and Parameters 111 C Alarm Handling 120 D Alarm Handing of Battery Maintenance Notification 142 E Battery Shallow Discharge Test 144 F Capacity Test 147 G Acronyms and Abbreviations 150 ...

Page 8: ...g or maintaining the equipment The safety instructions in this document are only supplements to local laws and regulations Huawei will not be liable for any consequences of the following circumstances Operation beyond the conditions specified in this document Installation or use in environments which are not specified in relevant international or national standards Unauthorized modifications to th...

Page 9: ...ctor surface or terminal measure the contact point voltage and ensure that there is no risk of electric shock After installing the equipment remove idle packing materials such as cartons foam plastics and cable ties from the equipment area In the case of a fire immediately leave the building or the equipment area and turn on the fire alarm bell or make an emergency call Do not enter the building o...

Page 10: ...cratches cannot be exposed to an outdoor environment for a long period of time Before operations ensure that the equipment is firmly secured to the floor or other solid objects such as a wall or an installation rack Do not use water to clean electrical components inside or outside of a cabinet Do not change the structure or installation sequence of equipment without permission Do not touch a runni...

Page 11: ...lear of the sources and degree of various potential hazards in equipment installation operation maintenance Trained personnel personnel who are technically trained have required experience are aware of possible hazards on themselves in certain operations and are able to take protective measures to minimize the hazards on themselves and other people Operators operation personnel who may come in con...

Page 12: ... ensure that a distance of at least 30 mm exists between the cables and heat generating components or areas This prevents damage to the insulation layer of the cables Do not route cables behind the air intake and exhaust vents of the equipment Ensure that cables meet the VW 1 flame spread rating requirements Bind cables of the same type together When routing cables of different types ensure that t...

Page 13: ... Requirements To prevent fire due to high temperature ensure that the ventilation vents or heat dissipation system are not blocked when the equipment is running Install the equipment in an area far away from liquids Do not install it under areas prone to condensation such as under water pipes and air exhaust vents or areas prone to water leakage such as air conditioner vents ventilation vents or f...

Page 14: ... irrelevant personnel Carry the operation machinery and tools properly to prevent them from falling off and causing injuries Personnel involving working at heights are not allowed to throw objects from the height to the ground or vice versa Objects should be transported by tough slings hanging baskets highline trolleys or cranes Ensure that guard rails and warning signs are set at the edges and op...

Page 15: ...intact and confirm its load bearing capacity Do not overload it Ensure that the ladder is securely positioned The recommended angle for a ladder against the floor is 75 degrees as shown in the following figure An angle rule can be used to measure the angle Ensure that the wider end of the ladder is at the bottom or protective measures have been taken at the bottom to prevent the ladder from slidin...

Page 16: ...n moving heavy objects When moving the equipment by hand wear protective gloves to prevent injuries Move or lift the equipment by holding its handles or lower edges Do not hold the handles of modules such as power supply units fans and boards that are installed in the equipment because they cannot support the weight of the equipment Avoid scratching the cabinet surface or damaging cabinet componen...

Page 17: ...ries are stored for more than 90 days charge them in time Otherwise the battery lifespan may be affected Install the UPS in an area far away from liquids Do not install it under areas prone to water leakage such as air conditioner vents ventilation vents or feeder windows of the equipment room Ensure that no liquid enters the UPS to prevent short circuits Ensure that there is no condensation insid...

Page 18: ...ry Safety Basic Requirements Before operating batteries carefully read the safety precautions for battery handling and master the correct battery connection methods Do not expose batteries at high temperatures or around heat generating devices such as sunlight fire sources transformers and heaters Excessive heat exposure may cause the batteries to explode Do not burn batteries Otherwise the batter...

Page 19: ...ures Place and secure batteries horizontally Note the polarities when installing batteries Do not short circuit the positive and negative poles of the same battery or battery string Otherwise the battery may be short circuited Check battery connections periodically ensuring that all bolts are securely tightened When installing batteries do not place installation tools on the batteries Battery Shor...

Page 20: ...note the precautions described in this section There is a risk of explosion if a battery is replaced with an incorrect model A battery can be replaced only with a battery of the same or similar model recommended by the manufacturer When handling a lithium battery do not place it upside down tilt it or bump it with other objects Keep the lithium battery loop disconnected during installation and mai...

Page 21: ... User Manual Two Live Wires 1 Safety Information Issue 07 2019 12 19 Copyright Huawei Technologies Co Ltd 14 Exercise caution when setting battery parameters Incorrect settings will affect the power supply and battery lifespan ...

Page 22: ... long backup time model The model is represented by UPS2000 G 6 kVA in the description of their common features and parameters UPS2000 G 10KRTL V2 UPS2000 G 10 kVA long backup time model The model is represented by UPS2000 G 10 kVA in the description of their common features and parameters UPS2000 G 15KRTL V2 UPS2000 G 15 kVA long backup time model The model is represented by UPS2000 G 15 kVA in t...

Page 23: ...ory G 4 Output capacity 3K 3 kVA 6K 6 kVA 10K 10 kVA 15K 15 kVA 20K 20 kVA 5 UPS type RT rack and tower mounted unit RR rack mounted unit TT tower mounted unit TM modular tower mounted unit RM modular rack mounted unit 6 Built in battery optional S standard model which provides only a standard battery pack L long backup time model You need to use an external large capacity battery pack 7 Input mod...

Page 24: ...ower into stable AC power for powering loads Bypass mode The mains supplies power directly to loads after filtering The UPS transfers to bypass mode when overload overtemperature or faults occur This mode does not provide battery backup capability Economy control operation ECO mode If the bypass voltage and frequency are in the specified range the UPS supplies power to loads over the bypass If the...

Page 25: ...t circuited with a short circuit busbar to live wire L1 and connect the input N and N with a short circuit busbar to live wire L2 In addition if the AC input and AC output uses two live wires the input and output ends must connect to two pole circuit breakers that provided by the user Figure 2 3 shows the front and rear views of the UPS2000 G 3 kVA 6 kVA Figure 2 4 shows the front and rear views o...

Page 26: ... output sockets C13 cannot exceed 10 A The fuse used on the UPS2000 G 3 kVA 6 kVA meets the 250V 10A IEC specifications Figure 2 4 Front and rear views of the UPS2000 G 10 kVA 1 Control panel 2 AC input ports 3 AC output ports pL and sL 4 Parallel ports 5 CAN communications ports MON1 and MON2 6 Optional card slot 7 Battery temperature sensor port 8 USB porta security protection mechanism supporte...

Page 27: ...bypass 3 Battery terminals 4 EPO port 5 Maintenance bypass port MBS 6 Parallel ports 7 CAN communications ports MON1 and MON2 8 USB porta security protection mechanism supported 9 Battery temperature sensor port 10 Optional card slot 11 AC output ports pL and sL a The USB port supports the standard Modbus protocol and connects to a PC through a USB cable so that you can access the NMS configure pa...

Page 28: ... temperature sensor TE820E10B W103 B02 L1 Measures the ambient temperature of the external power module and battery pack The temperature ranges from 40º C to 80º C The standard cable is 2 meters long To increase the length install a magnetic ring at the sensor plug Ambient temperature and humidity sensor WS302M2A 5 ENR1DETA MODULE Measures the UPS ambient temperature and humidity The ambient tempe...

Page 29: ...atteries ESS 240V12 7AhBPVBA0 1 ESS 240V12 7AhBPVBA0 2 Each battery pack consists of twenty 12 V 7 Ah VRLA batteries connected in series It is a standard configuration for the UPS2000 G 6 kVA A maximum of four battery packs are connected in parallel The UPS2000 G 15 kVA 20 kVA uses at least two battery packs Standard battery pack 9 Ah 20 batteries ESS 240V12 9AhBPVBA0 1 ESS 240V12 9AhBPVBA0 2 Each...

Page 30: ...tenance The PDU is designed for a 1 1 UPS2000 G 15 kVA 20 kVA parallel system three phase input three phase output PDU PDC 0091V 2ACIOA PDC 0091V2ACIOA The PDU is designed for a 1 1 UPS2000 G 15 kVA 20 kVA parallel system three phase input single phase output and single phase input single phase output It can also be used in a UPS2000 G 6 kVA single phase input single phase output UPS2000 G 10 kVA ...

Page 31: ...m in the parallel system scenario In a UPS2000 G 15 kVA 20 kVA parallel system using the TN C power distribution system install four magnetic rings on the PE cables on each UPS bind the four magnetic rings together using binding tape and secure them to the nearest place It is recommended that you install the battery temperature sensor secured with an adhesive on the surface of batteries in the mid...

Page 32: ...er Manual Two Live Wires 2 Quick Introduction Issue 07 2019 12 19 Copyright Huawei Technologies Co Ltd 25 Figure 2 6 Installing magnetic rings numbered 1 on branch PE cables 1 Magnetic rings 1 2 Magnetic rings 2 3 Magnetic rings 3 ...

Page 33: ...n system Short circuit battery terminals N in the parallel system It is recommended that you connect AC loads and battery packs only to the UPS PE terminal If you have directly grounded AC loads and battery packs and connected them to the UPS PE terminal install magnetic rings 2 and 3 on the PE3 PE4 PE5 and PE6 ground cables You need to purchase magnetic rings 2 and 3 The recommended type for magn...

Page 34: ... 2019 12 19 Copyright Huawei Technologies Co Ltd 27 The magnetic conductivity of manganese and zinc magnetic rings is greater than 10 000 and the recommended internal diameter of magnetic rings is greater than 10 mm easy for wire coiling The number of coiling circles is 5 or greater ...

Page 35: ...the rack Environment Do not install the UPS in an environment outside the specifications Keep the UPS far away from water heat sources and flammable and explosive substances Install the UPS in an environment free of dust volatile gas salt and corrosive materials Avoid direct sunlight Do not install the UPS in environments with conductive metal scraps in the air The ideal operating temperature for ...

Page 36: ...sue 07 2019 12 19 Copyright Huawei Technologies Co Ltd 29 UPS2000 G 3 kVA 6 kVA 10 kVA Dimensions Figure 3 1 UPS2000 G 3 kVA 6 kVA 10 kVA installation dimensions UPS2000 G 15 kVA 20 kVA Dimensions Figure 3 2 UPS2000 G 3 kVA 6 kVA 10 kVA installation dimensions Clearances ...

Page 37: ...than or equal to 500 mm Reserve a clearance of at least 500 mm respectively from the front and rear panels of the UPS to the wall or adjacent equipment to facilitate ventilation and heat dissipation Figure 3 3 Reserved clearances 3 1 2 Tools Get installation tools insulated to prevent electric shocks Table 3 1 lists the installation tools Table 3 1 Tools Tools Clamp meter Multimeter Label Phillips...

Page 38: ...crewdriver PH 2 x 150 mm or PH 3 x 250 mm Flat head screwdriver 2 mm x 80 mm Torque screwdriver Crimping tool Diagonal pliers Wire stripper Polyvinyl chloride PVC insulation tape Cotton cloth Brush Heat shrink tubing Heat gun Electrician s knife Protective gloves ESD gloves Insulated gloves Hydraulic pliers Cable tie 3 1 3 Power Cables ...

Page 39: ...lowed for only the N wire For 15 kVA 20 kVA model use ground cables that have a cross sectional area of 25 mm2 and M6 OT terminals that are 90 bent and have a cross sectional area of 25 mm2 For 15 kVA 20 kVA model use battery cables that have a cross sectional area of 16 mm2 and M6 OT terminals that are 90 bent and have a cross sectional area of 16 mm2 For 3 kVA model use ground cables that have a...

Page 40: ...wire output 2 50 A the characteri stics of D Battery N A 240 V DC 50 A 6 mm2 N A 6 kVA single ph ase input single pha se output Input 1 220 V AC 230 V AC or 240 V AC 50 A the characteri stics of D 6 mm2 6 mm2 M4 OT terminal 1 4 N m Output 1 50 A the characteri stics of D Battery N A 240 V DC 50 A 6 mm2 N A 10 kVA dual live wire input dual live wire output Dual liv e wire input 2 208 V AC 220 V AC ...

Page 41: ...ire output Dual liv e wire input 2 208 V AC 220 V AC 100 A the characteri stics of D 25 mm2 25 mm2 M6 OT terminal 4 8 N m Battery N A 240 V DC 63 A 16 mm2 16 mm2 M6 90 OT terminal 4 8 N m Dual liv e wire Output 2 208 V AC 220 V AC 100 A the characteri stics of D 25 mm2 25 mm2 M6 OT terminal 4 8 N m 15 kVA single ph ase input single pha se output Input 1 220 V AC 230 V AC or 240 V AC 100 A the char...

Page 42: ...ics of D 25 mm2 25 mm2 M6 OT terminal 4 8 N m 15 kVA three pha se input three phas e output Bypass input 3 380 V AC 400 V AC or 415 V AC 50 A the characteri stics of D 10 mm2 10 mm2 M6 OT terminal 2 8 N m Mains input 3 Battery N A 240 V DC 63 A 16 mm2 16 mm2 M6 90 OT terminal 4 8 N m Output 3 380 V AC 400 V AC or 415 V AC 50 A the characteri stics of D 10 mm2 10 mm2 M6 OT terminal 2 8 N m 20 kVA d...

Page 43: ... characteri stics of D 25 mm2 25 mm2 M6 OT terminal 4 8 N m 20 kVA three pha se input single pha se output Bypass input 1 220 V AC 230 V AC or 240 V AC 125 A the characteri stics of D 25 mm2 25 mm2 M6 OT terminal 4 8 N m Mains input 3 380 V AC 400 V AC or 415 V AC 63 A the characteri stics of D 10 mm2 10 mm2 M6 OT terminal 2 8 N m Battery N A 240 V DC 63 A 16 mm2 16 mm2 M6 90 OT terminal 4 8 N m O...

Page 44: ...nput single phase output 3 1 4 Unpacking and Checking Figure 3 4 shows the transportation safety requirements Figure 3 4 Transportation safety requirements Only trained personnel are allowed to move the UPS Do not move the UPS by holding its mounting ears front panel terminal cover or monitoring module At least two persons are required to move the battery pack and transformer because they are heav...

Page 45: ... backfeed protection device on the input front side attach a warning label to the main power isolation device The label reads like this This circuit supplies power to the UPS Before cable connection disconnect the UPS and check the voltage across wiring terminals When battery mode is unavailable or the mains fails the UPS internal voltages or energy may flow back directly or through a leakage path...

Page 46: ...2 A LC1 DT60A for three phase input N A N A UPS2000 G 20KRTL three phas e input 220 V AC 230 V AC 240 V AC 40 A N A N A UPS2000 G 15KRTL single pha se input UPS2000 G 20KRTL single pha se input 220 V AC 230 V AC 240 V AC 125 A LC1 D80 for single phase input 208 V AC 220 V AC 125 A AF110 30 11 70 Table 3 4 Control relay parameters Recommended Model Parameters HF18FF 012 HONGFA control relay Dry con...

Page 47: ...A V2 User Manual Two Live Wires 3 Installation Issue 07 2019 12 19 Copyright Huawei Technologies Co Ltd 40 Figure 3 5 Bypass backfeed protection connections for the UPS2000 G 3 kVA 6 kVA 10 kVA 15 kVA 20 kVA two live wires ...

Page 48: ...nual Two Live Wires 3 Installation Issue 07 2019 12 19 Copyright Huawei Technologies Co Ltd 41 Figure 3 6 Bypass backfeed protection connections for the UPS2000 G 3 kVA 6 kVA 10 kVA 15 kVA 20 kVA single phase input single phase output ...

Page 49: ...kVA V2 User Manual Two Live Wires 3 Installation Issue 07 2019 12 19 Copyright Huawei Technologies Co Ltd 42 Figure 3 7 Bypass backfeed protection connections for the UPS2000 G 10 kVA three phase input single phase output ...

Page 50: ... V2 User Manual Two Live Wires 3 Installation Issue 07 2019 12 19 Copyright Huawei Technologies Co Ltd 43 Figure 3 8 Bypass backfeed protection connections for the UPS2000 G 15 kVA 20 kVA three phase input three phase output ...

Page 51: ...ter Installation Table 3 5 lists the check items Table 3 5 Post installation check items No Item Expected Result 1 Cable routing Cable routing meets engineering requirements 2 Cable connections Input cables output cables and battery cables are tightened to specified torques using a torque wrench connected correctly and free of damage 3 Cable connections for USB ports and network ports Cables to US...

Page 52: ...ormation on the labels is concise and understandable 5 Ground cable connection The ground cable is securely connected to the equipment room ground bar Measure the resistance between the UPS ground cable and the equipment room ground bar which must be less than 0 1 ohm 6 Distances between cable ties Distances between cable ties are the same and no burr exists 7 Operating environment Clean the condu...

Page 53: ...he UPS controls UPS running displays running data and allows you to set parameters and view alarms Figure 4 1 shows the control panel Figure 4 1 Control panel 1 Mains indicator 2 Battery indicator 3 Bypass indicator 4 Fault indicator INFO button 5 Startup Enter Battery Self Check Mute button 6 Down button 7 Up button 8 Shutdown Back button 4 2 Indicators Table 4 1 describes the indicators on the c...

Page 54: ...The UPS is in ECO mode when the mains indicator and bypass indicator are both on 4 3 Functional Buttons The control panel provides five buttons to start and shut down the UPS and set parameters Table 4 2 describes the buttons Table 4 2 Button description Button Meaning Description ESC Shutdown Back On the default screen press ESC for more than 5 seconds Release the button when you hear a beep soun...

Page 55: ...i to view the active alarm information When no alarm is generated press i to return to the default screen Battery self check After the UPS starts in normal mode it transfers to battery mode for 10 seconds to check that the battery status if no battery is connected No battery is displayed and that the UPS can transfer to battery mode The purpose is to prevent power backup failure when the UPS needs...

Page 56: ...creen 1 Normal mode The solid line indicates normal mode The dotted line indicates non normal mode 2 Input voltage and frequency 3 Load power 4 Output voltage current and frequency 5 Bypass mode The solid line indicates bypass mode The dotted line indicates non bypass mode 6 Battery voltage and capacity displayed during charge Battery discharge time and capacity displayed during discharge 7 Batter...

Page 57: ... Startup The settings wizard starts automatically when you start the UPS for the first time or when you restart the UPS after restoring factory settings The settings wizard provides the Language System Parameters and Battery Parameters screens Figure 4 3 Settings wizard After you complete the settings press The standby screen is displayed Figure 4 4 Standby screen displayed after initial startup N...

Page 58: ... 2 Starting the UPS in Battery Mode Initial Startup The settings wizard starts automatically when you start the UPS for the first time or when you restart the UPS after restoring factory settings The settings wizard provides the Language System Parameters and Battery Parameters screens After you complete the settings press The standby screen is displayed Figure 4 7 Standby screen displayed after i...

Page 59: ...ght Huawei Technologies Co Ltd 52 Figure 4 8 Standby screen displayed after non initial startup After the UPS starts it enters battery mode Figure 4 9 Battery mode Press The main menu screen is displayed 4 6 LCD Menu Hierarchy Figure 4 10 Main Menu screen Figure 4 11 shows the LCD menu hierarchy ...

Page 60: ...UPS2000 G 3 kVA 20 kVA V2 User Manual Two Live Wires 4 Control Panel Issue 07 2019 12 19 Copyright Huawei Technologies Co Ltd 53 Figure 4 11 LCD menu hierarchy ...

Page 61: ... and Vcn in the case of three phase input Frequency parameter Frequency displayed on the Mains Input screen Vab Vbc and Vca parameters Line voltages displayed on the Mains Input screen The parameters are not displayed in the case of single phase input Bypass Input Screen Figure 4 13 shows the Bypass Input screen Figure 4 13 Bypass Input screen Voltage parameter Phase voltages displayed on the Bypa...

Page 62: ...tus is NA battery not connected or reversely connected Equalized charging Float charging Hibernating or Discharging Capacity parameter Remaining battery capacity Backup time parameter Estimated backup time The value is NA during battery charge Inverter Output Screen Figure 4 15 shows the Inverter Output screen Figure 4 15 Inverter Output screen Voltage parameter Phase voltages displayed on the Inv...

Page 63: ...een Figure 4 17 shows the Local UPS Load screen Figure 4 17 Local UPS Load screen Single UPS Running screen A single UPS is running Sout parameter Phase A B and C apparent power displayed on the Local UPS Load screen The parameter is Sout_A Sout_ B and Sout_C in the case of three phase input Pout parameter Phase A B and C active power displayed on the Local UPS Load screen The parameter is Pout_A ...

Page 64: ...Parallel System Load screen The parameter is Sys Pout_A Sys Pout_ B and Sys Pout_C in the case of three phase input the parameters are not displayed in single UPS mode Sys Load ratio parameter System phase A B and C load ratio displayed on the Parallel System Load screen The parameter is Sys Load ratio_A Sys Load ratio_B and Sys Load ratio_C in the case of three phase input and the parameters are ...

Page 65: ... the buzzer buzzes hold down for 2 5 seconds to mute it The buzzer is muted when you release the button When the buzzer is mute it cannot be buzzes again until a new alarm is generated Active Alarms Screen The Active Alarms screen displays the active alarm information such as the alarm serial number severity ID and name as shown in Figure 4 21 Figure 4 21 Active Alarms screen If an alarm is genera...

Page 66: ...me or severity as shown in Figure 4 23 Figure 4 23 Sort Alarms screen Occurrence latest first parameter Alarms are sorted by occurrence time The latest alarms are listed first Level highest first parameter Active alarms are displayed by severity The most critical alarms are listed first is displayed next to a selected Sort Alarms Clear Alarms Screen Clear the alarms that you can clear manually as ...

Page 67: ...Figure 4 25 Settings screen Basic Settings Screen Figure 4 26 Basic Settings screen Language parameter You can select Chinese English preset Spain French and Russian Change Password parameter You can change the password by choosing Settings Basic Settings Change Password The preset password is 000001 The password allows you to enter the Settings screen Change Feature Code parameter You can change ...

Page 68: ...255 The default value is 255 255 255 0 Gateway parameter Set a gateway address for the SNMP card The value ranges from 0 0 0 0 to 255 255 255 255 The default value is 192 168 0 1 If a Modbus card is connected the following parameters are displayed Figure 4 28 Modbus card settings Comm address parameter Set a communications address for the Modbus card over the dual in line package DIP switch on the...

Page 69: ...is Dry contact3 Batt undervolt parameter Set the output dry contact associated with low battery voltages When the system battery voltage is low this dry contact is enabled The value ranges from Dry contact1 to Dry contact6 The default value is Dry contact4 BPS backfeed parameter Set the output dry contact associated with bypass backfeed When a bypass backfeed alarm is generated this dry contact is...

Page 70: ... After you change the voltage level the upper thresholds for bypass voltages restore to default values 15 and 20 respectively The parameter is configurable after the inverter shuts down Frequency level parameter Set the system output frequency level The values include 50 Hz default 60 Hz and Automatic If the value is Automatic the power on bypass frequency ranges from 40 Hz to 55 Hz and the system...

Page 71: ...10 and 15 The parameter is configurable after the inverter shuts down Min voltage parameter Lower threshold for the bypass voltage If the difference between the bypass voltage and the rated output voltage exceeds this value the system determines that the bypass voltage is abnormal and that the bypass is unavailable The values include 10 20 default 30 40 50 and 60 The parameter is configurable afte...

Page 72: ...ass frequency range The values include 0 5 Hz 1 Hz 2 Hz default and 3 Hz The parameter is configurable after the inverter shuts down Single UPS ECO parameter Determine whether to support ECO mode on a single UPS ECO mode is not supported in a parallel system The values include Disabled and Enabled The default value is Disabled The parameter is configurable after the inverter shuts down Power Segme...

Page 73: ...d The default value is Disabled The parameter is configurable after the inverter shuts down Self Load screen Figure 4 35 Self Load screen Output power ratio parameter This parameter is used during the tests before shipment The value ranges from 20 to 100 The default value is 80 The parameter is configurable after the inverter shuts down Self load mode parameter This parameter is used during the te...

Page 74: ...the quality is average for example the mains input is from a high performance generator or a common power grid select Balance mode when the quality is poor for example the mains input is from a common generator select Strong adaptability mode The parameter is configurable after the inverter shuts down Auto check bus capa parameter Determine whether to automatically check the bus capacitance upon p...

Page 75: ...o 32 Ah if the calculated maximum current is 0 1 x 65 x 1 2 3 25 set it to 3 0 A If a single 15 kVA 20 kVA UPS connects to two battery packs the maximum charge current must be less than or equal to 2 0 A Basic screen Figure 4 37 Basic screen Batteries Positive battries Negative battries parameters Set the number of batteries The value ranges from 16 to 20 The default value is 20 When the number of...

Page 76: ... 0 A and the default value is 6 0 A The parameter is configurable in any mode Equalized Charge screen Figure 4 38 Equalized Charge screen Equalized charging parameter Determine whether to enable equalized charging The values include Disabled and Enabled The default value is Enabled The parameter is configurable in any mode Time interval parameter Set the time interval for equalized charging The va...

Page 77: ...urable in non battery mode or non battery ECO mode If you expect the battery discharge time to be greater than 24 hours set Max time to 0 hour Otherwise the system may power off If you set Max time to 0 hour the battery string may remain in the small current discharge state according to the proportion of the battery capacity to the load power which affects the battery lifecycle EOD mode parameter ...

Page 78: ... threshold V cell 1 80 1 75 1 70 1 67 1 65 EOD auto start parameter Determine whether to automatically start inverter output after the mains becomes normal The values include Disabled and Enabled The default value is Enabled The parameter is configurable after the inverter shuts down Shutdown delay parameter When the delay time reaches the value after UPS transfers to battery mode the UPS powers o...

Page 79: ...ifications The parameter is configurable in any mode Time interval parameter Set the time interval for shallow discharge tests The value ranges from 30Day to 90Day The default value is 60Day The parameter is configurable in any mode Discharge ratio parameter Set the proportion of the discharge capacity to the total discharge capacity The value ranges from 10 to 50 The default value is 20 The param...

Page 80: ...o clear all the battery data after you replace batteries Figure 4 44 Replace Batteries screen Maintain Batteries Menu Shallow Discharge Test menu Figure 4 45 Shallow Discharge Test screen Capacity Test menu After you completely discharge batteries the load ratio must be in the range of 20 80 Stop Test Figure 4 46 Stop Test screen Stop the shallow discharge test or capacity test Manual EC for Pos m...

Page 81: ...pectively Manual FC for Pos menu Figure 4 48 Manual FC for Pos screen Perform float charging on batteries forcibly For the 3 kVA 6 kVA and 10 kVA UPSs perform manual float charging For the 15 kVA and 20 kVA UPSs batteries in positive and negative groups are manually switched to float charging respectively Sync Paral Param Menu The menu allows you to synchronize the parameters from one UPS to the o...

Page 82: ... 51 Buzzer off If Control Buzzer is used for muting the alarm tone the alarm tone should be unmuted by using Control Buzzer or power on the UPS again Otherwise when a new alarm is generated it cannot be buzzes again If the buzzer off click Control Buzzer transfers to Buzzer on Figure 4 52 Buzzer on 4 6 5 About Screen On the Main Menu screen select About and press The About screen is displayed as s...

Page 83: ...r the 3 kVA 6 kVA and 10 kVA UPS Model parameter The UPS model is 20K UPS ESN parameter This item provides the UPS ESN Version parameter This item provides the UPS version MU1MSW1 parameter This item provides the main monitoring software version PU1RSW1 parameter This item provides rectifier power software version PU1RSW2 parameter This item provides the rectifier logic software version PU1ISW1 pa...

Page 84: ...es Input circuit breakers and load circuit breakers are OFF Power cables and signal cables are correctly identified The input phase sequence is correct Cables are neatly routed and securely bound Devices are installed and cables are routed in ways that facilitate modification capacity expansion and maintenance Parallel cables are properly connected The UPS is properly grounded The voltage between ...

Page 85: ...t Output mode to Three phase Set Voltage level and Frequency level based on the rated voltage and frequency In the case of single phase output set Voltage level to 208 V 220 V default 230 V or 240 V in the case of three phase output set Voltage level to 380 V default 400 V or 415 V Battery parameters are configurable in non battery mode or non battery ECO mode Set Positive batteries and Negative b...

Page 86: ...f the system uses three phase input single phase output or single phase input single phase output Output mode is set to Single phase if the system uses three phase input three phase output Output mode is set to Three phase Voltage level and Frequency level are set based on the rated voltage and frequency Press ESC to return to the standby screen Step 4 Start the UPS in normal mode by using one of ...

Page 87: ...perations on the UPS The UPS runs in battery mode Step 4 When the UPS runs properly close the UPS AC output circuit breaker Q and start the loads To prevent triggering overload protection start the loads with higher power and then loads with lower power End 5 2 2 Shutting down the UPS Shutting down the Inverter To shut down the inverter perform any of the following operations On the default screen...

Page 88: ...tion on a single UPS Figure 5 2 EPO cable connection on a single UPS Connect an external switch to the EPO port on the UPS After you turn on the switch the inverter shuts down and the UPS will not transfer to bypass mode Output terminals completely power off which meets the EPO purpose The external EPO switch switch or dry contact signals controlled by a switch is provided by the customer 5 3 Para...

Page 89: ...el system dual live wire input dual live wire output 5 3 1 Starting the Parallel System The configured number of batteries must match the actual number When the actual number changes change the configured number If the configured number is less than the actual number the battery lifespan is shortened If the configured number is greater than the actual number battery leakage may cause a fire ...

Page 90: ... displayed The parallel system supplies no power Perform Step 2 when there are two mains inputs In the case of one mains input you need only to close the UPS mains input circuit breakers and general mains input circuit breaker If a PDU is configured close the following circuit breakers general mains input circuit breaker general bypass input circuit breaker mains input circuit breakers for all UPS...

Page 91: ...trol panel The initialization screen is displayed on each LCD On the standby screen press to enter the main menu Choose Main Menu Settings System Parameters Output to view output settings if the system uses three phase input single phase output or single phase input single phase output Output mode is set to Single phase if the system uses three phase input three phase output Output mode is set to ...

Page 92: ...rs turn off and fans stop the UPS shuts down Step 3 Open the external battery circuit breaker if there is or disconnect battery cables The UPS exits the parallel system To merely shut down the UPS perform Step 1 only End Transferring the Parallel System to Bypass Mode Perform shutdown operations on each UPS in the parallel system All inverters shut down at the same time and the parallel system tra...

Page 93: ... provided by the customer The parallel system enters the EPO state That is the inverters shut down and the parallel system will not transfer to bypass mode Figure 5 4 shows the EPO cable connection in a parallel system Figure 5 4 EPO cable connection in a parallel system Connect an external switch to the EPO port on the UPS After you turn on the switch the UPS stops inverter output and does not tr...

Page 94: ...s parallel system management using only one SNMP card Adapts to the 10 Mbit s 100 Mbit s fast Ethernet FE by using an IP address that is configurable on the LCD Supports SNMP Hypertext Transfer Protocol Secure HTTPS and Secure Shell SSH Supports SNMP agent v1 v2c and v3 The UPS MIB library can be downloaded from its own web page instead of any CD ROM Enables remote management on Windows or Linux u...

Page 95: ...he specified time 6 3 Modbus Card The RMS MODBUS01A provides an RS485 networking solution to remotely manage the UPS The card implements the following functions by setting the DIP switches Selects the Modbus protocol by using a DIP switch over the RS485 communications protocol Uses a DIP switch to select a two wire or four wire system Provides a DIP switch to select a build out resistor Provides a...

Page 96: ...ed to perform maintenance Maintain UPSs regularly based on the following requirements Otherwise the UPSs may fail to operate properly and the lifespan may be shortened Table 7 1 Routine maintenance items for UPSs Check Item Expected Result Troubleshooting Maintenance Interval Operating environment Ambient temperature 0 40 C Humidity 0 95 RH non condensing If the humidity and temperature are abnorm...

Page 97: ...ency the number of batteries and the actual battery capacity Reset the parameters Quarterly Power cables and terminals between the UPS and the power distribution cabinet The insulation layers of cables are intact and terminals are free from noticeable sparks Replace the cables Secure the output terminals Quarterly EPO if configured Check the reliability of the EPO cable connection Secure the termi...

Page 98: ...t been discharged for a long time discharge and charge them in equalized mode at least once every three months to activate them Each charge should last at least 4 hours Normally discharge and charge batteries once every four to six months Each charge should last at least 4 hours In high temperature areas discharge and charge batteries once every two months Each charge should last at least 4 hours ...

Page 99: ...of the battery string voltage check whether the cable between the battery string and the UPS is excessively long or the cable diameter is excessively small 2 Check whether the equalized charging voltage and float charging voltage are correctly set for the UPS 3 If the fault persists contact Huawei technical support Monthly Battery temperature sensor measurement accuracy The difference between the ...

Page 100: ... to verify that the batteries can discharge normally 1 Locate the cause when an exception is identified 2 If the fault persists contact Huawei technical support Quarterly Capacity Test recommended When the UPS is backed up discharge a battery to the undervoltage alarm threshold to refresh the capacity of the battery 1 Locate the cause when an exception is identified 2 If the fault persists contact...

Page 101: ...UPS2000 G 3 kVA 20 kVA V2 User Manual Two Live Wires 7 Routine Maintenance Issue 07 2019 12 19 Copyright Huawei Technologies Co Ltd 94 Item Expected Result Measures Maintenance Interval later check ...

Page 102: ...er supply is not connected Check the input power cable connection The input voltage exceeds the limit Use a multimeter to check that the UPS input voltage meets specifications 2 The mains is normal but the AC input indicator is off The UPS runs in battery mode The mains switch is OFF Turn on the mains switch The input power cable is not securely connected Check the input power cable connection 3 T...

Page 103: ... faulty Shut down the UPS immediately and cut off the input power supply Contact local Huawei technical support 8 The battery indicator is blinking yellow The buzzer buzzes 1 second and then stops 1 second The battery capacity is insufficient The UPS is shutting down The remaining battery capacity is insufficient The UPS is shutting down and the loads are powering off Parameters settings of batter...

Page 104: ... Dimensions H x W x D 430 mm x 86 mm x 615 mm 430 mm x 130 mm x 757 mm Weight 14 kg 14 kg 16 kg 32 kg 32 kg 9 2 Environmental Specifications Table 9 2 Environmental specifications Item 3 kVA 6 kVA 10 kVA 15 kVA 20 kVA Operating temperature 0 40 C Humidity 0 95 RH non condensing Altitude 1000 meters When the altitude is 1000 4000 meters see IEC62040 3 to check how the UPS power is derated Storage a...

Page 105: ...m 3 kVA 6 kVA 10 kVA 15 kVA 20 kVA Input power cable Single p hase L N input PE cable Single pha se L N input PE cable Single phase L N input PE cable Three phase L1 L2 L3 N input PE cable Single phase L N input PE cable Three phase L1 L2 L3 N input PE cable Single phase L N input PE cable Three phase L1 L2 L3 N input PE cable Rated input voltage 208 V AC 220 V AC 230 V AC or 240 V AC 208 V AC 220...

Page 106: ...e phase input 0 99 0 99 No load loss 54 W 54 W 90 W 180 W Double power input Disabled Disabled Disabled Enabled Enabled Startup voltage 120 280 V AC Diesel generator input capacity Minimum 1 5 times the UPS rated capacity 9 4 Bypass Input Electrical Specifications Table 9 4 Bypass input electrical specifications Item 3 kVA 6 kVA 10 kVA 15 kVA 20 kVA Bypass voltage Upper threshold 10 15 20 25 30 20...

Page 107: ...0 kVA Output PF 0 9 Rated output voltage 208 V AC 220 V AC 230 V AC or 240 V AC single phase output select a voltage system by setting a voltage level on the LCD 208 V AC 220 V AC 230 V AC or 240 V AC single phase output select a voltage system by setting a voltage level on the LCD 380 V AC 400 V AC or 415 V AC three phase output select a voltage system by setting a voltage level on the LCD Output...

Page 108: ... 9 6 Battery Specifications Table 9 6 Battery specifications Item 3 kVA 6 kVA 10 kVA 15 kVA 20 kVA Rated battery voltage 240 V DC 240 V DC Number of batteries 16 20 each 12 V DC If the smaller value between the numbers of batteries N is less than 20 the battery power is derated to N 20 16 20 respectively in the positive and negative battery strings The rated number is 20 If the smaller value betwe...

Page 109: ...ime It depends on battery capacity forlong backup time models Charger rated charge voltage Each cell has an equalized voltage of 2 35 V and a float voltage of 2 25 V Both are configurable on the LCD The parameters in Figure 9 1 Figure 9 2 Figure 9 3 and Figure 9 4 are provided based on the new battery pack used first The ESS 240V12 7AhBPVBA01 part number is 02310PFD The ESS 240V12 9AhBPVBA01part n...

Page 110: ...up time parameters for the ESS 240V12 7AhBPVBA01 battery pack 6 kVA battery efficiency assumed as 94 Table 9 8 Backup time parameters for the ESS 240V12 9AhBPVBA01 battery pack 10 kVA battery efficiency assumed as 94 Load Load W One Battery pack min Two Battery packs min Three Battery packs min Four Battery packs min 100 9000 4 12 23 32 80 7200 7 17 29 44 ...

Page 111: ... Copyright Huawei Technologies Co Ltd 104 Load Load W One Battery pack min Two Battery packs min Three Battery packs min Four Battery packs min 50 4500 12 32 53 70 30 2700 26 57 88 125 Figure 9 2 Backup time parameters for the ESS 240V12 9AhBPVBA01 battery pack 10 kVA battery efficiency assumed as 94 ...

Page 112: ...hnologies Co Ltd 105 Table 9 9 Backup time parameters for the ESS 240V12 9AhBPVBA01 battery pack 15 kVA battery efficiency assumed as 94 Load Load W Two Battery packs min Four Battery packs min Six Battery packs min Eight Battery packs min 100 13500 7 19 32 48 80 10800 9 26 44 57 50 6750 18 48 70 96 30 4050 35 79 125 171 ...

Page 113: ... time parameters for the ESS 240V12 9AhBPVBA01 battery pack 15 kVA battery efficiency assumed as 94 Table 9 10 Backup time parameters for the ESS 240V12 9AhBPVBA01 battery pack 20 kVA battery efficiency assumed as 94 Load Load W Two Battery packs min Four Battery packs min Six Battery packs min Eight Battery packs min 100 18000 4 12 23 32 80 14400 7 17 29 44 ...

Page 114: ...Copyright Huawei Technologies Co Ltd 107 Load Load W Two Battery packs min Four Battery packs min Six Battery packs min Eight Battery packs min 50 9000 12 32 53 70 30 5400 26 57 88 125 Figure 9 4 Backup time parameters for the ESS 240V12 9AhBPVBA01 battery pack 20 kVA battery efficiency assumed as 94 ...

Page 115: ...Parallel Feature Table 9 12 Parallel feature Item 3 kVA 6 kVA 10 kVA 15 kVA 20 kVA Number of UPSs in parallel two live wires N A 1 1 Number of UPSs in parallel other mode except two live wires N A 4 The UPS2000 G 15 kVA 20 kVA single phase input single phase output supports 3 1 parallel systems at most instead of 4 0 parallel systems 9 9 Safety Regulations and EMC Table 9 13 Safety regulations and...

Page 116: ...awei Technologies Co Ltd 109 Item Standards Compliance Remarks Harmonic interference 16 A I 75 A IEC EN61000 3 12 N A Impact current lightning protection IEC EN60240 2 IEC EN61000 4 5 YD T1095 2000 YD T944 2007 The AC input side meets Level D lightning protection differential mode and common mode 5 kA and 8 20 µs ...

Page 117: ...age level Yes ECO max voltage Yes Volt adj coef Yes ECO min voltage Yes Frequency level Yes Output mode Yes ECO enabled Yes Auto check bus capa Yes Output transformer Yes Auto start Yes Recovery delay time Yes Bypass max voltage Yes Bypass frequency range Yes Bypass min voltage Yes Self load output power ratio Yes Generator mode Yes Max BPS transfers Yes EOD auto start Yes Converter mode Yes Self ...

Page 118: ... Third Level Menu Fourth Level Menu Value Range Preset Value Status Mains Input Voltage N A N A N A Frequency Bypass Input Voltage Frequency Battery Status Battery voltage Battery current Status Capacity Backup time Inverter Output Voltage Current Frequency UPS Output Voltage Current Frequency Local UPS Load Single UPS Running N X Parallel System Sout Pout Load ratio Parallel System Single UPS ...

Page 119: ...arms Active alarms Details N A N A Historical Alarms Historical alarms Details Sort Alarms Occurrence latest first N A Level highest first Clear Alarms N A Settings Basic Settings Language N A English Chinese Spanish French and Russian English Change Password N A 000000 999999 000001 Change Feature Code N A 000000 999999 999999 Communicatio n Card IP address SNMP Card N A 0 0 0 0 255 255 255 255 1...

Page 120: ... 1 6 Dry contact 6 System Parameters Parallel configurable after the inverter shuts down Single Parallel Single and Parallel Single Redundant UPSs 0 3 0 Output configurable after the inverter shuts down Output mode configurable only on the UPS2000 G 15 kVA 20 kVA Single phase Three phase Three phase on the UPS2000 G 15 kVA 20 kVA Voltage level 208 V 220 V 230 V and 240 V on the UPS2000 G 6 kVA 10 ...

Page 121: ...0 Min voltage 5 6 7 8 9 and 10 10 Frequency range 0 5 Hz 1 Hz 2 Hz and 3 Hz 2 Hz Single UPS ECO Enabled and Disabled Disabled Power segment Dis time thres configurable in non battery mode 0 999 minutes 30 Min Dis volt thres configurable in non battery mode 1 90 2 25 V cell 2 00 V cell Power Segment configurable after the inverter shuts down Enabled and Disabled Disabled Self Load configurable afte...

Page 122: ...gurable in non battery mode 16 20 monoblocs 20 Monobloc Battery capacity configurable in non battery mode 7 1000 Ah For the UPS2000 G 3 kVA 6 kVA the default value is 7 Ah on a standard model and 40 Ah on a long backup time model For the UPS2000 G 1 0 kVA the default value is 9 Ah on a standard model and 65 Ah on a long backup time model For the UPS2000 G 1 5 kVA 20 kVA the default value is 65 Ah ...

Page 123: ...cell 3 3 mV C cell Discharge Max time configurable in non battery mode 0 24 hours 16 Hour EOD mode configurable in non battery mode Batt protect first Backup time first and Balanced mode Backup time first EOD auto start configurable after the inverter shuts down Enabled and Disabled Enabled Shutdown delay 0 600 seconds 0S Shallow Discharge Test notification Enabled and Disabled Disabled Time inter...

Page 124: ... 50 Hz Output mode configurable only on the UPS2000 G 15 kVA 20 kVA Single phase and Three phase Three phase on the UPS2000 G 15 kVA 20 kVA Battery Parameters Batteries Positive batteries Negative batteries 16 20 monoblocs 20 Monobloc Battery capacity 7 1000 Ah For the UPS2000 G 3 kVA 6 kVA the default value is 7 Ah on a standard model and 40 Ah on a long backup time model For the UPS2000 G 1 0 kV...

Page 125: ...Neg Sync Paral Param N A Reset Password About Model N A N A N A N A ESN Version The bypass frequency range is associated with the ECO frequency range the bypass frequency range is 0 5 Hz 1 Hz 2 Hz 3 Hz 4 Hz 5 Hz or 6 Hz the ECO frequency range is 0 5 Hz 1 Hz 2 Hz or 3 Hz The bypass frequency range must be greater than or equal to the current ECO frequency range if the ECO frequency range is 3 Hz t...

Page 126: ...old for bypass voltages is 10 15 default 20 25 or 30 If the voltage level is 220 V line voltage 380 V the upper threshold for bypass voltages is 10 15 default 20 or 25 If the voltage level is 230 V line voltage 400 V the upper threshold for bypass voltages is 10 15 default or 20 If the voltage level is 240 V line voltage 415 V the upper threshold for bypass voltages is 10 or 15 default ...

Page 127: ... range of 40 Hz to 70 Hz Measures Check whether the mains input voltage is less than 272 V If not wait until the mains recovers Check whether the mains input voltage is greater than 88 V If not wait until the mains recovers Check the mains input frequency If the mains input frequency is abnormal wait until the mains input recovers 0001 02 Abnormal mains volt Minor 0001 03 Abnormal mains volt Minor...

Page 128: ... transfer back to normal mode even when the mains is normal Possible cause The mains voltage fluctuates frequently The UPS has transferred from normal mode to battery mode within 2 minutes for 10 consecutive times The rectifier locks out in battery mode Measure Check the mains 0008 01 Rect start overlimit Minor Manual clear Power off clear The UPS cannot start Possible cause The mains voltage freq...

Page 129: ...inverter still works properly but the system cannot transfer to bypass mode Possible cause The bypass input three phase sequence is incorrect Measure Check that bypass input power cables are correctly connected 0012 01 BPS neutral loss Minor Automatic clear If the inverter has not started the system has no output and inverter startup is prohibited If the inverter has started the inverter still wor...

Page 130: ...em is not affected Possible causes Batteries are not connected Batteries are not securely connected Measures Connect batteries Check that batteries are securely connected 0023 01 Batt overtemp Minor Automatic clear An alarm is generated and the battery lifespan is affected Possible causes The ambient temperature exceeds the battery high temperature alarm threshold default value 50º C The battery c...

Page 131: ...sure If possible connect to the mains power when the UPS is in non battery test state 0027 01 Batt overcurrent Minor Automatic clear An alarm is generated and the battery lifespan is affected Possible causes The charger is abnormal Measure Contact Huawei technical support for repair 0028 01 Breaker OFF Critical Automatic clear N A Possible causes The mains input power cables are incorrectly connec...

Page 132: ...ther the circuit breaker downstream load is short circuited using a multimeter Check whether cable connections are correct If yes switch on the output circuit breaker 0029 01 Maintain batt Minor Automatic clear The battery backup time is affected Possible causes The battery capacity is incorrectly set The battery loop cannot be discharged The battery capacity is low Measures Check whether the conf...

Page 133: ...d the battery lifespan is affected Possible causes The configured number of batteries is less than the actual number The actual number of batteries does not meet specifications The charger is abnormal Measures Check that the configured number of batteries matches the actual number Check that the actual number of batteries meets requirements Disconnected the external battery charger check whether t...

Page 134: ...orm a shallow discharge test The alarm will be automatically cleared no matter whether test conditions are met 0040 01 Rectifier fault Critical Manual clear Power off clear The UPS shuts down The UPS transfers to another working mode or shuts down Possible cause The soft start resistor is damaged Measure Contact Huawei technical support for repair 0040 02 Rectifier fault Critical Manual clear Powe...

Page 135: ...wer off clear Automatic clear The UPS shuts down The UPS transfers to another working mode or shuts down Possible cause The hardware is damaged Measure Contact Huawei technical support for repair 0040 06 Rectifier fault Critical Power off clear The UPS shuts down The UPS transfers to another working mode or shuts down Possible cause The hardware is damaged Measure Contact Huawei technical support ...

Page 136: ...anual clear Power off clear The UPS shuts down Possible cause The digital signal processing DSP or complex programmable logical device CPLD chip is faulty Measure Contact Huawei technical support for repair 0041 01 Rectifier alarm Minor Manual clear Power off clear N A Possible cause The EEPROM chip is faulty Measure Contact Huawei technical support for repair 0041 02 Rectifier alarm Minor Automat...

Page 137: ...ected Possible cause The NTC is not connected or is damaged Measure Contact Huawei technical support for repair 0042 09 Internal fault Critical Automatic clear The inverter shuts down Possible cause Self load cable connections are incorrect Measure Reconnect cables 0042 10 Internal fault Critical Automatic clear If the inverter has not started the UPS has no output and inverter startup is not allo...

Page 138: ...hree phase power cable lengths vary greatly Measure Ensure that the lengths of three phase power cables vary within a difference of 5 0042 13 Internal fault Critical Manual clear Power off clear The UPS startup is not allowed Possible cause The inverter is faulty Measure Contact Huawei technical support for repair 0043 01 Fan fault Critical Automatic clear The power supply from the UPS and system ...

Page 139: ...nd hardware versions do not match Measure Contact the manufacturer to load software 0044 04 Incompatible ver Critical Manual clear Power off clear The UPS startup is not allowed Possible cause An error occurred during software loading Measure Contact the manufacturer to load software 0044 05 Incompatible ver Critical Manual clear Power off clear The UPS startup is not allowed Possible cause Softwa...

Page 140: ...act Huawei technical support for repair 0045 08 Charger alarm Critical Manual clear Power off clear Automatic clear The charger in the UPS stops 0045 09 Charger alarm Critical Manual clear Power off clear 0045 10 Charger alarm Critical 0049 01 Battery qty wrong Minor Manual clear Power off clear Automatic clear An alarm is displayed and the battery service life may be shortened Possible causes The...

Page 141: ...ossible cause The inverter output is short circuited Measure Rectify output port short circuits After you clear the alarm restart the UPS If the alarm persists contact Huawei technical support for repair 0060 05 Inverter fault Critical Automatic clear Possible causes The mains experiences instantaneous high voltage impact The output has special loads such as sensitive loads and rectification loads...

Page 142: ... 01 Inverter alarm Minor Manual clear Power off clear Automatic clear The UPS shuts down The UPS may transfer to another working mode or shut down Possible causes Parallel cables are incorrectly connected The lengths of parallel cables vary greatly Measures Reconnect cables The lengths of parallel cables vary within a range of 5 0061 02 Inverter alarm Minor Manual clear Power off clear N A Possibl...

Page 143: ...on voltage The battery discharge time exceeds the battery protection time Measures Check the battery voltage Modify the power segment settings on the LCD 0066 01 Output overload Minor Automatic clear Continuous overload causes the UPS to transfer to bypass mode or supply no power Possible cause The load exceeds the rated loading capacity Measure Reduce the load or replace the UPS with a larger cap...

Page 144: ...ct Huawei technical support for repair 0083 02 Paral cable fault Critical 0083 04 Paral cable fault Critical Manual clear Power off clear Automatic clear The UPS shuts down The parallel system transfers to another working mode 0083 05 Paral cable fault Critical 0084 02 Paral cable alarm Minor Automatic clear N A Possible causes The parallel cable is loose The parallel cable is damaged Measures Che...

Page 145: ...ECO volt Minor Automatic clear Transfer to bypass mode is prohibited If the bypass is supplying power the UPS transfers to another working mode Possible cause The ECO input is abnormal Measure Check whether the ECO input voltage or frequency exceeds the configured range If yes change the range or wait until the bypass input recovers 0105 05 Comm failed Minor Automatic clear The monitoring module c...

Page 146: ...e causes The ambient temperature in the UPS equipment room exceeds the alarm threshold default value 40 C The temperature and humidity transducer is faulty Measures Check the ambient temperature in the UPS equipment room Replace the temperature and humidity transducer 0133 01 Ambient undertempera ture Minor Possible causes The ambient temperature in the UPS equipment room is below the alarm thresh...

Page 147: ... UPS equipment room is below the alarm threshold default value 10 The temperature and humidity transducer is faulty Measures Check the ambient humidity of the UPS equipment room Replace the temperature and humidity transducer 0136 01 Faulty temperature and humidity module Minor Possible causes The temperature and humidity module is faulty Measures Check parameter settings of the temperature and hu...

Page 148: ... battery self check state The mains loading capability is insufficient Measures Check the mains input If the mains input is abnormal wait until the mains input recovers Check whether the UPS is in battery self check state Reduce the load or replace the UPS with a larger capacity UPS 0340 01 Maint breaker ON Minor Automatic clear The UPS transfers to bypass mode Possible cause The maintenance circu...

Page 149: ... on the info key are blinking red and alarms are generated intermittently Procedure Step 1 Clear the Batt maint notif alarm 1 Press the i key on the UPS control panel to display the Active Alarms page If multiple active alarms exist use the or key to select the alarm record on the top the latest alarm is on the top by default Press to view the alarm ID and name Figure D 1 Viewing alarms 2 Press to...

Page 150: ...o not want the battery maintenance notification 0036 01 to appear again perform the following steps 1 On the Main Menu screen select Settings and press The Settings login screen is displayed The preset password is 000001 After you enter the correct password and press the Settings screen is displayed 2 Choose Battery Parameters and Shallow Discharge and then change the value of Test notification fr...

Page 151: ...n the Status screen locate Battery Status Figure E 1 Battery Status menu Status The battery status is NA battery not connected or reversely connected Equalized charging Float charging Hibernating or Discharging Capacity indicates the remaining battery capacity Backup time indicates the estimated discharge duration The value is NA during battery charging 2 Batteries in Hibernating state cannot star...

Page 152: ... 3 Shallow Discharge screen Discharge ratio indicates the percentage of discharge capacity to the total dischargeable capacity The parameter can be set to a value between 10 and 50 and the default value is 20 The parameter is configurable in any mode It is recommended that the value of Discharge ratio not exceed 20 with the load is light For example the value can be 10 or 15 Step 3 Start the shall...

Page 153: ...UPS2000 G 3 kVA 20 kVA V2 User Manual Two Live Wires E Battery Shallow Discharge Test Issue 07 2019 12 19 Copyright Huawei Technologies Co Ltd 146 Figure E 5 Stop Test screen End ...

Page 154: ...attery Status menu Status The battery status is NA battery not connected or reversely connected Equalized charging Float charging Hibernating or Discharging Capacity indicates the remaining battery capacity Backup time indicates the estimated discharge duration The value is NA during battery charging 2 Batteries in Hibernating state cannot start a capacity test Choose Control and Maintain Batterie...

Page 155: ...lower limit Figure F 3 Viewing the load rate Step 3 Start the capacity Test Partially discharge the batteries and ensure that the load rate is between 20 and 80 After all required conditions are met the test command is successfully delivered and the LCD displays a Succeeded message Figure F 4 Shallow Discharge screen If the load rate and battery capacity do not meet the requirements the system dis...

Page 156: ...er Manual Two Live Wires F Capacity Test Issue 07 2019 12 19 Copyright Huawei Technologies Co Ltd 149 Figure F 5 Load not met Figure F 6 Batt not fully charged Step 4 Stop the capacity Test forcibly Figure F 7 Stop Test screen End ...

Page 157: ...l area network CPLD complex programmable logical device D DIP dual in line package DOD depth of discharge DSP digital signal processing E EPO emergency power off ECO economy control operation EOD end of discharge ESD electrostatic discharge ESN equipment serial number H HTTPS Hypertext Transfer Protocol Secure L LCD liquid crystal display LSI large scale integrated M MIB management information bas...

Page 158: ...E protective earthing PL parallel load PVC polyvinyl chloride R RS232 Recommend Standard 232 RS485 Recommend Standard 485 S SELV safety extra low voltage SNMP Simple Network Management Protocol T THDv total harmonic distortion of output voltage TNV telecommunication network voltage U UPS uninterruptible power system USB Universal Serial Bus V VRLA valve regulated lead acid ...