UPS2000-G-(3 kVA-20 kVA)-V2
User Manual (Two Live Wires)
B LCD Menus and Parameters
Issue 07 (2019-12-19)
Copyright © Huawei Technologies Co., Ltd.
114
Main
Menu
Second-Level
Menu
Third-Level
Menu
Fourth-Level
Menu
Value Range
Preset Value
Converter mode
Enabled and
Disabled
Disabled
Bypass
(configurable
after the
inverter shuts
down)
Max. voltage
10%, 15%, 20%,
25%, and 30%
15%
Min. voltage
10%, 20%, 30%,
40%, 50%, and 60%
20%
Frequency range
±0.5 Hz, ±1 Hz, ±2
Hz, ±3 Hz, ±4 Hz,
±5 Hz, and ±6 Hz
±2 Hz
ECO
(configurable
after the
inverter shuts
down)
Max. voltage
5%, 6%, 7%, 8%,
9%, and 10%
10%
Min. voltage
5%, 6%, 7%, 8%,
9%, and 10%
10%
Frequency range
±0.5 Hz, ±1 Hz, ±2
Hz, and ±3 Hz
±2 Hz
Single UPS ECO
Enabled and
Disabled
Disabled
Power segment
Dis. time thres.
(configurable in
non-battery mode)
0–999 minutes
30 Min
Dis. volt. thres.
(configurable in
non-battery mode)
1.90–2.25 V/cell
2.00 V/cell
Power Segment
(configurable after
the inverter shuts
down)
Enabled and
Disabled
Disabled
Self-Load
(configurable
after the
inverter shuts
down)
Output power ratio
20%–100%
80%
Self-load mode
Enabled and
Disabled
Disabled
Others
(configurable
after the
inverter shuts
down)
Recovery delay
time
0–900 seconds
5S
Max. BPS
transfers
1–3
3
Output transformer Enabled and
Disabled
Disabled
Generator mode
Weak adaptability
mode, Balanced
mode, and Strong
Balanced mode