UPS2000-G-(3 kVA-20 kVA)-V2
User Manual (Two Live Wires)
3 Installation
Issue 07 (2019-12-19)
Copyright © Huawei Technologies Co., Ltd.
35
Model
Wiring
Termin
al
Numb
er of
Phases
Rated
Voltage
External
Circuit
Breaker
Cross-s
ectional
Area
Termin
al Type
Torqu
e for
Tighte
ning
Bolts
se output)
AC
Mains
input
3
380 V
AC, 400
V AC, or
415 V
AC
50 A (the
characteri
stics of D)
10 mm
2
10 mm
2
M6 OT
terminal
2.8 N
m
Battery
N/A
±240 V
DC
63 A
16 mm
2
16 mm
2
M6 90°
OT
terminal
4.8 N
m
Output
1
220 V
AC, 230
V AC, or
240 V
AC
100 A
(the
characteri
stics of D)
25 mm
2
25 mm
2
M6 OT
terminal
4.8 N
m
15 kVA
(three-pha
se input
three-phas
e output)
Bypass
input
3
380 V
AC, 400
V AC, or
415 V
AC
50 A (the
characteri
stics of D)
10 mm
2
10 mm
2
M6 OT
terminal
2.8 N
m
Mains
input
3
Battery
N/A
±240 V
DC
63 A
16 mm
2
16 mm
2
M6 90°
OT
terminal
4.8 N
m
Output
3
380 V
AC, 400
V AC, or
415 V
AC
50 A (the
characteri
stics of D)
10 mm
2
10 mm
2
M6 OT
terminal
2.8 N
m
20 kVA
(dual-live-
wire input
dual-live-
wire
output)
Dual-liv
e-wire
input
2
208 V
AC, 220
V AC
125 A
(the
characteri
stics of D)
25 mm
2
25 mm
2
M6 OT
terminal
4.8 N
m
Battery
NA
±240 V
DC
63 A
16 mm
2
16 mm
2
M6 90°
OT
terminal
4.8 N
m
Dual-liv
e-wire
Output
2
208 V
AC, 220
V AC
125 A
(the
characteri
stics of D)
25 mm
2
25 mm
2
M6 OT
terminal
4.8 N
m