UPS2000-A-(6 kVA-10 kVA)
User Manual
3 Installation
Issue 04 (2019-05-05)
Copyright © Huawei Technologies Co., Ltd.
22
3
Installation
3.1 Preparations
3.1.1 Site
Floor Bearing
The floor can bear the weight of the UPS and its optional components. In the case of rack
installation, ensure that the floor can also bear the weight of the rack.
Environment
Do not install the UPS in an environment outside the specifications.
Keep the UPS far away from water, heat sources, and flammable and explosive
substances. Install the UPS in an environment free of dust, volatile gas, salt, and
corrosive materials. Avoid direct sunlight.
Do not install the UPS in environments with conductive metal scraps in the air.
The ideal operating temperature for batteries is 20–30º
C. Temperatures higher than 30º
C
shorten the battery lifespan and temperatures lower than 20º
C reduces the backup time.