UPS2000-A-(6 kVA-10 kVA)
User Manual
5 Operations
Issue 04 (2019-05-05)
Copyright © Huawei Technologies Co., Ltd.
87
Figure 5-20
UPS power-on and entering the default screen
Step 4
Set the voltage level based on the actual output voltage. The voltage level can be set to 208 V,
220 V (default), 230 V, or 240 V.
Figure 5-21
Setting the voltage level
Step 5
Set the voltage frequency based on the actual output frequency. The frequency can be set to
50 Hz (default), 60 Hz, or AUT (automatic).
Figure 5-22
Setting the voltage frequency
Step 6
(This step is required only for the UPS with long backup time.) Set the number of batteries
based on the actual battery capacity. The default value is 16 for the UPS with long backup
time, and the value can range from 16 to 20.
Figure 5-23
Setting the number of batteries