UPS2000-A-(6 kVA-10 kVA)
User Manual
B Alarm Handling
Issue 04 (2019-05-05)
Copyright © Huawei Technologies Co., Ltd.
130
Alarm
Name
Alar
m
Ident
ifier
(Alar
m ID)
Web
UI
Deci
mal
Syste
m
Alarm
Identi
fier
(Alar
m ID)
LCD
Heuri
sticim
al
Syste
m
Alarm
level
Alarm
Clear
Mode
Impact on the
System
Repair Proposal
Measure: Contact Huawei technical
support.
Batt.
reverse
14-1
20-1
Critical
Autom
atic
clear
This alarm does
not affect the
UPS or the
power supply.
Possible cause: The positive and
negative battery terminals are reversely
connected.
Measure: Check the battery
installation, and install batteries again.
No
battery
16-1
22-1
Minor
Autom
atic
clear
This alarm does
not affect the
power supply.
Possible cause: No batteries are
connected.
Measure: Connect batteries.
Possible cause: The batteries are in
poor contact.
Measure: Check the battery cable
connection. If battery cables are
loose, connect them securely.
Battery
overtemp
erature
17-1
23-1
Minor
Autom
atic
clear
An alarm is
generated, and
the battery
lifespan is
affected.
Possible cause: The temperature inside
the UPS of the standard version or the
ambient temperature exceeds the
battery overtemperature alarm
threshold (default value: 50º
C).
Measure: Reduce the ambient
temperature and keep the air intake and
exhaust vents of the UPS unblocked.
Battery
overvolta
ge
19-1
25-1
Minor
Autom
atic
clear
An alarm is
generated, and
the battery
lifespan is
affected.
Possible cause: The battery voltage
reaches the alarm threshold due to
continuous charge.
Measure: When batteries are in
charge mode, wait for 2 minutes
and check whether the alarm is
cleared.
Possible cause: The number of
batteries configured is less than the
actual number of batteries.
Measure: Check whether the
number of batteries is correctly set.