TP48200A-D17A5-2 Telecom Power
User Manual
C Associations Between Alarms and Dry Contacts on the
UIM
Issue 04 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
60
C
Associations Between Alarms and Dry
Contacts on the UIM
Table C-1
Associations between dry contacts and alarms
Port Type
Silk Screen
Associated Alarm
Dry contact input ports DIN1
Dry contact input 1
DIN2
Dry contact input 2
DIN3
Dry contact input 3
DIN4
Dry contact input 4
DIN5
Dry contact input 5
DIN6
Dry contact input 6
Dry contact output
ports
The default setting
(closed: alarm; open:
normal) can be
modified.
ALM1
High battery temperature/high ambient temperature/TCU
alarm/Rectifier fault/rectifier communication failure
ALM2
Door status alarm
ALM3
Battery fuse blown/Multi-rectifier fault/AC SPD fault
ALM4
Battery fault
ALM5
DC low voltage alarm
ALM6
Smoke alarm
ALM7
AC power failure
Default mode (closed:
normal; open: alarm)
ALM8
SMU fault