TP48200A-D17A5-2 Telecom Power
User Manual
3 Components
Issue 04 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
22
Figure 3-5
Rectifier
(1) Run indicator
(2) Alarm indicator
(3) Fault indicator
(4) Locking latch
(5) Handle
Table 3-2
Rectifier indicators
Indicator
Color
Status
Description
Run indicator
Green
Steady on
The rectifier has an AC power input.
Off
The rectifier has no AC power input.
The rectifier is faulty.
Blinking at 0.5 Hz
The rectifier is being queried.
Blinking at 4 Hz
The rectifier is loading an application program.
Alarm indicator
Yellow
Off
No alarm is generated.
Steady on
The rectifier generates an alarm for power
limiting due to ambient overtemperature.
The rectifier generates an alarm for shutdown
due to ambient overtemperature or
undertemperature.
The rectifier protects against AC input overvoltage
or undervoltage.
The rectifier is hibernating.
Blinking at 0.5 Hz
The communication between the rectifier and the
SMU is interrupted.
Fault indicator
Red
Off
The rectifier is running properly.
Steady on
The rectifier locks out due to output overvoltage.
The rectifier has no output due to an internal fault.