Replacing an Optimizer

1. Power off the solar inverter and remove the 

faulty optimizer.

2. Install a new optimizer and correctly 

connect its cables.

3. Power on the solar inverter. On the Device 

Commissioning screen, choose 

Maintenance > Add/Delete device

, and 

tap 

Auto search 

to add the new optimizer.

4. On the Device Commissioning screen, 

choose 

Maintenance > Physical layout 

design of PV modules

, select the 

corresponding PV module, and bind the new 
optimizer. Click 

Submit

.

1

2

3

4

7

FAQ

Does the Optimizer Support Partial Configuration Scenarios?

7.1

The optimizer supports partial configuration scenarios. It can communicate with the solar inverter to 
implement module-level management but does not support module-level shutdown.

The optimizer uses Staubli MC4 DC connectors. Ensure that the DC connectors to be connected 
are of this model. If the DC connectors to be connected are not of the Staubli MC4 model, the 
connector compatibility report and third-party lab (TUV, VED, or Bureau Veritas) report from the 
DC connector manufacturer must be available. Using incompatible DC connectors may result in 
serious consequences. The resulting device damage is beyond the warranty scope.

Full configuration scenario: For a single-phase solar inverter, the number of PV modules 
connected in series in a PV string cannot exceed 25 and the maximum power of a PV string 
cannot exceed 5 kW under any condition. For a three-phase solar inverter, the number of PV 
modules connected in series in a PV string cannot exceed 50 and the maximum power of a PV 
string cannot exceed 10 kW under any condition. Otherwise, the solar inverter may be damaged 

and even a fire may occur.

Partial configuration scenario: The total open-circuit voltage of the PV modules in a PV string 
cannot exceed the maximum input voltage of the solar inverter under any condition.

8

Precautions

Summary of Contents for SUN2000-450W-P

Page 1: ...oduct Overview Type II apparatus enhanced insulation Burn warning Electric shock warning Mounting bracket 2 Install the optimizer based on the selected installation mode Properly plan the installation position of optimizers to ensure that the cables between the optimizer and the PV module and between adjacent optimizers can be properly connected and the maximum communication distance between the o...

Page 2: ...hole has been reserved on the PV module frame Prepare the bolt assembly and nut by yourself Ensure that the bolt length meets the installation requirements of the PV module frame PV module Installed on a PV Module Frame Frame Mounting Bracket Front mounted Do not press the optimizer mounting ear against the positioning pole of the frame mounting bracket Purchase the frame mounting bracket separate...

Page 3: ...the output voltage and resistance of a single optimizer PV module connection box Resistance Cause Suggestions 0 9 kΩ R1 1 1 kΩ The optimizer is normal N A R1 0 9 kΩ If the probes of the multimeter are correctly connected the optimizer is faulty Replace the optimizer 1 1 kΩ R1 The sunlight is weak The optimizer input is not connected The optimizer output is connected to the PV module output The opt...

Page 4: ...t is weak 1 1 kΩ R1 The optimizer input is not connected 1 1 kΩ R1 The optimizer output is connected to the PV module output 1 1 kΩ R1 PV string PV string a If R is infinite an open circuit occurs in the PV string or the cables are connected to different PV strings Rectify the PV string open circuit fault and correctly group the PV string cables b If R4 is less than R3 A is the positive cable of t...

Page 5: ...he optimizer status 5 Troubleshooting Optimizer status Status Description Green The optimizer is running properly Gray The optimizer is offline Check that the SN and location information are correct and search for the device again Red The optimizer is faulty Fault alarm Fault Alarm Cause Suggestions Input overvoltage The output voltage of the PV module exceeds the maximum input voltage of the opti...

Page 6: ...re of this model If the DC connectors to be connected are not of the Staubli MC4 model the connector compatibility report and third party lab TUV VED or Bureau Veritas report from the DC connector manufacturer must be available Using incompatible DC connectors may result in serious consequences The resulting device damage is beyond the warranty scope Full configuration scenario For a single phase ...

Page 7: ...regulations specified in this document and the solar inverter user manual Use insulated tools when installing the device For personal safety wear proper personal protective equipment PPE If an optimizer does not connect to any other device connect the OUT and OUT ports of the optimizer respectively to the IN and IN ports to protect the terminals from water It is recommended that the positive and n...

Page 8: ...8 Huawei Technologies Co Ltd Huawei Industrial Base Bantian Longgang Shenzhen 518129 People s Republic of China solar huawei com ...

Reviews: