LL-1148  Issue 8 

DF528

 

 

 

 

 

 

 

Wolf ATEX Splitter Box  
Operation and Maintenance Instructions

  

Please Retain – Read Before Use 
Models 

LL-260/(suffixes define enclosure, cable, plug, socket and fuse options) 

The  Wolf  ATEX  splitter  box  meets  all  relevant  provisions  of  the  2014/34/EU 
Explosive Atmospheres (ATEX Equipment) Directive by virtue of the issued EU 
type examination certificate confirming compliance with all relevant harmonised 
standards and essential health and safety requirements.  
 
The Wolf ATEX Splitter Box range use GRP and 316 stainless steel enclosures 
protected with a 316 Stainless Steel Skid. The splitter box is approved as Group 
II,  equipment  for  use  in  zone  1  &  2  potentially  explosive  gases,  vapours  and 
mists  where  a  T5  temperature  class  is  permitted  and  in  zone  21  &  22  dusts 
where  the  surface  temperature  T90ºC  permits.  ATX,  CEAG,  STAHL  or 
Marechal  sockets  may  be  fitted.  SY,  SB  and  HOFR  can  be  used  when 
connecting into the splitter box via approved glands. 
 

CERTIFICATION/APPROVAL CODE  
 

 

II 2 GD*

 

Ex d e IIC T5 Gb

 

Ta -20ºC** to +50ºC***

 

 

 

Ex tb IIIC T90ºC Db

 

IP66****

 

* When CEAG GHG 54.. range of sockets are used the splitter box is only 
certified safe to use at 50V and in potential explosive Gas atmospheres. 
**When SY cable is used, T amb min = -15ºC. 
***  When  total  input  current 

10A  T  amb  max  =  +55ºC  (CEAG,  STAHL, 

MARECHAL sockets only). 
**** When CEAG GHG 5118.. range of sockets are used the splitter box is 
IP64 rated and when CEAG GHG 54 range of sockets are used the splitter 
box is IP54 rated, 

 
Check  product  label  for  specific  voltage  information,  approval  codes, 
certification, IP and fuse ratings. 
 
CERTIFICATION (see product label for code). 

EU Type examination certificate: 

Baseefa12ATEX0268X 

Notified Body    

SGS Fimko OY, P.O.Box 30 
(Särkiniementie 3) 00211 HELSINKI. Finland 
Notified body number: 

0598 

Specific Conditions For Use (‘X’ Conditions) 

1. 

Unused terminals are to be tightened to values below – 

Din Rail - 0.6Nm 

ATX Socket - 2Nm 

CEAG Socket - 2.5Nm 

STAHL Socket - 1.2Nm 

Marechal Socket - 2Nm 

2. 

Only one conductor per terminal. 

3. 

The  uninsulated  part  of  the  conductor  must  not  extend  beyond  the 
terminal throat. 

Harmonised standards applied: 

EN60079-0: 2012+A11: 2013 

EN60079-1: 2014 

EN60079-7: 2015 

EN60079-31: 2014 

 

 

Alex Jackson – Managing Director  
Wolf Safety Lamp Company Ltd. 
 

IECEx Scheme Certification 

Certificate Number: 

IECEx BAS 16.0073X

 

 

 

Ex d e IIC T5 Gb

 

Ta -20ºC* to +50ºC**

 

 

 

Ex tb IIIC T90ºC Db

 

IP66***

 

When  CEAG  GHG  54..  range  of  sockets  are  used  the  splitter  box  is  only 
certified safe to use at 50V and in potential explosive Gas atmospheres. 
*When SY cable is used, T amb min = -15ºC 
**When total input current 

10A T amb max = +55ºC 

*** When CEAG GHG 5118.. range of sockets are used the splitter box is 
IP64 rated and When CEAG GHG 54 range of sockets are used the splitter 
box is IP54 rated, 

IECEx  scheme  certification  only  covers  Splitter  boxes  fitted  with 
CEAG, STAHL, MARECHAL sockets only 

 
IEC60079-0: 2011 

IEC60079-1: 2007 

IEC60079-7: 2006 

IEC60079-31: 2008 

European Design N

o

 

001 425 201 

UK Patent 2 526 256 B

IMPORTANT  

1. 

Read  the  instruction  leaflet  carefully  before  commencing  to  use  the 
splitter box and retain it for future use. 

2. 

Check  the  rating  label  to  ensure  the  splitter  box  is  suitable  for  the 
supply voltage, T class, ambient temperature present and IP rating. 

3. 

Splitter boxes constructed from GRP (Glass Reinforced Polyester) and 
their mounted sockets are plastic, the end user must ensure that these 
materials are suitable for the atmosphere the splitter box will be used 
in. Excessive force should not be used on plastic components. 

4. 

The Splitter box must not be opened when energised and if fitted with 
a fuse, a delay of 5 mins after disconnection from the electrical supply 
must be observed before opening. 

5. 

Splitter Box must not be moved  whilst  energised. Always disconnect 
the Splitter Box from the electrical supply before moving. 

USER GUIDANCE FOR WOLF SPLITTER BOXES 

1. 

This product is Class 1 equipment and must be earthed. 

2. 

It is the user's responsibility to ensure there is no potential difference 
between the earth supply to the splitter box and the earth where it is 
sited. Where this is not possible the splitter box should also be locally 
earth bonded. A flexible cable with a conductor area of 6mm

2

 minimum 

which  is  no  longer  than  two  metres  is  recommended  for  this.  The 
splitter box must be de-energised during connection or disconnection 
of the local earth bond. 

3. 

The user must consider the effect of voltage losses on the input cable 
to the splitter box, to ensure that products connected to the splitter box 
are operating within their specified voltage tolerance. 

4. 

The supply cable must be inspected on a regular basis to ensure there 
is no damage to the cable or gland. 

5. 

Splitter boxes have terminal blocks suitable for up to 4mm

2

 live, neutral 

and earth.  

6. 

Approved cable glands must be used and be suitable for the type of 
cable used and the environment to be used in. 

7. 

Do  not  overload  the  source  supply.  It  is  the  user's  responsibility  to 
ensure products connected to the splitter box do not exceed the 15A 
maximum input current rating of the splitter box.  

8. 

If  the Wolf  Splitter  Box  is  fitted  with  a  fuse,  it  will  be  an  IEC  60269, 
80kA  breaking  capacity  cartridge  fuse.  The  fuse  type  and  maximum 
value must not be exceeded. Replace with like for like fuse and secure 
the screwed cover on fully. 

Details  of  the  fuse  fitted  is  found  on  the  splitter  model 
identification label which is attached to the lid

 

Replacing these with fuses of a different type or of a higher rating could 
result in an unsafe condition occurring in the safe or hazardous area. 
To  prevent  nuisance  tripping,  the  total  power  of  apparatus  operated 
from the splitter box should not exceed the rated maximum amperage 
of  the  fuse.  Where  apparatus  other  than  Wolf  lighting  products  are 
connected, its load should be checked to ensure it is suitable for use 
with type gG (general) fuses. 

9. 

Where the splitter box is connected to a Wolf Safety ATEX transformer, 
ensure  that  the  connected  circuits  do  not  exceed  total  maximum 
loading  and  maximum  cable  lengths  permissible  (see  transformer 
instructions for details). When calculating the maximum cable length, 
the total must include the length of the splitter box input cable. Where 
cables  with  different  conductor  areas  are  combined,  the  maximum 
cable length should be selected based on the smallest conductor area. 
Exceeding  recommended  cable  lengths  could  result  in  an  unsafe 
condition in the safe or hazardous area in the event of a fault occurring. 

For additional advice regarding the permissible maximum cable 
lengths 

Suggested 

lighting 

layouts 

for 

splitter 

e-mail 

[email protected]

 

 

 

MAINTENANCE 

1. 

Disconnect the splitter  box from the electrical supply before carrying 
out any maintenance. 

2. 

It  is  essential  that  the  splitter  is  maintained  in  accordance  with  the 
requirements of EN60079-17 

3. 

A visual check should be carried out to ensure all internal cables are 
in  good  condition,  and  not  suffering  any  sign  of  damage  or 
degradation. All internal connections should be checked to ensure that 
they are correctly secured. 

4. 

The  splitter  box  input  cable  and  any  attached  cables  should  be 
inspected before each use. Any damaged cables should be replaced 
immediately. 

5. 

The condition of the gaskets on the enclosure and sockets should be 
inspected to ensure there is no breakdown in the units IP rating. 

6. 

IMPORTANT.   

No  modifications  are  permitted  to  the  splitter  box  or 

sockets.  

 

 