(The information  displayed  in the following  figure  is for reference  only.)

Run the 

display ip interface  brief [ interface-type 

[ interface-number  ] ]

command to view  the brief 

information  about  the IP address  for the interface.

NOTE

1. Run the 

user-interface 

tty

2

command  to access the TTY user interface  view.  For the  RS422/485  serial  port,  the TTY value  is 

2

.

2. Run the 

mode raw

command  to set the serial  port service  mode  to 

RAW

and  access the RAW service  view,  or access the existing  RAW 

service  view.

3. Run the 

undo raw-transport  enable

command  to disable  the RAW service  function.

By default,  the serial  port service  mode  is 

NONE

.

Configuring Serial Port Transparent Transmission

4. Run the 

raw-transport tcp server server-port 

5000 command  to appoint  the device  as the server  and  to transparently  transmit  serial  port 

data  over  TCP. The appointed  listening  port of the  server  is 5000.

5. Run the 

raw-transport enable

command  to enable  the RAW service  function.

(The information  displayed  in the following  figure  is for reference  only.)

6. Run the 

quit 

command.

In the system  view,  run the following  commands:

Check the configuration  result and  verify  that the  server  can receive  data  collected  by the function  module.

Run the 

display transport info

command  to check the serial  port service  configuration.

Run the 

display transport mode

command  to check the serial  port service  mode.

Run the 

display transport session

command  to check the serial  port session  information.

Run the 

display transport stat

command  to check the serial  port status information.

NOTE

NOTE

By default,  the RAW service  function  is disabled.

The device  working  mode  and  the basic properties  of the  serial  port transparent  transmission  service  configured  in the 
RAW service  view  take  effect only  after the RAW service  is enabled.

NOTE

By default,  the RAW service  function  is disabled.

The device  working  mode  in the serial  port transparent  transmission  service  and  the basic properties  of the  service 
should  be configured  when  the RAW service  is disabled.

Summary of Contents for PowerCube 500 V200R001C10

Page 1: ...itoring equipment Alarm indicator ALM Red Off There is no alarm Steady on The lithium battery has generated a fault alarm and needs to be replaced Blinking slowly 0 5 Hz The lithium battery has generated a protection alarm which can be cleared Function Module Indicator Color Status Meaning Run indicator Green Off The function module has no power input or is faulty Blinking slowly 0 5 Hz The functi...

Page 2: ...cable alarm cable and ground cable Routing Cables Through the Cantilever Camera ground cable Routing Cables Through the Solar Hybrid Pole Mains AC cable and optical fiber Module ground cable Mains AC cable module ground cable optical fiber camera cable CPE cable and PV cable CPE cable Camera signal cable power cable and alarm cable PV DC input cable CPE cables can be used only in scenarios where C...

Page 3: ...ybrid Scenario 1 Remove the connective kit adjust the PV module direction based on the PV module direction principles and then reinstall the connective kit 2 Install the PV module support 3 Adjust the tilt angle of the PV module support based on the site latitude 4 Loosen the bolt at the base of the PV module support 5 Install the angle adjustment bracket and tighten the bolt at the base of the PV...

Page 4: ...9 Install spacing shims for the PV modules Spacing shim Raking strut beam Keep the slots of horizontal beams facing inwards for installing PV modules Partially tighten the bolts so that PV modules can be adjusted during installation NOTE Ensure that the junction boxes on the rear of PV modules are positioned consistently NOTE Ensure that the openings of the raking strut beams face outwards Partial...

Page 5: ... on the site latitude Wear protective gloves during installation Do not place a module with its bottom against the ground Never install a module with power on Ensure that the angle between a module and the line vertical to the ground is within 10 degrees The paint on the module exterior should be intact If paint has flaked off repaint the area to avoid corrosion Ensure that the arrow on the top of...

Page 6: ... No lithium battery is required in the grid only scenario NOTE If two lithium batteries are required install one above the other Install the pole mounting kit after using a positioning sticker at the cable hole in the upper part of the pole to mark its installation position For the method see steps 1 and 2 NOTE The wall must be made of reinforced concrete and be able to bear at least 800 N The wal...

Page 7: ... kit 7 Install a function module onto the wall 8 Install the lithium battery hanging kit Level Marker One wall mounting kit A and one wall mounting kit B are used for each module Determine the number of wall mounting kits based on the number of modules to be installed NOTE The option to install a lithium battery depends on the scenario No lithium battery is required in the grid only scenario NOTE ...

Page 8: ...red install them onto two adjacent wall hanging kits NOTE Route inter device cables through the pole NOTE Module ground cable 2 Connect the other end of the module ground cable to the pole ground bar Pole ground bar function module Lithium battery Lithium battery Cable Hole Diameter Requirements No Cable Hole Silk Screen Cable Type Cable Outer Diameter 1 GE PoE network cable optical fiber 6 8 0 3 ...

Page 9: ...ution terminal The power cable for the dome camera can only be connected to the 24VAC port Use waterproof tape to protect the cable distribution terminal and put it inside the pole 6 Optional Install the door status sensor 7 Optional Install the dome camera alarm linkage cable Dome camera alarm cable Installation Procedure Cables for the dome camera can only be connected to the PoE 0 1 ports Bulle...

Page 10: ...f connectors may be exposed to water leakage Before assembling cables with waterproof connectors ensure that the connections between the cables and terminals are secure and reliable Negative blue Positive red PE green N L2 blue L L1 brown Cable Type Core Cross Sectional Area Cable Outer Diameter Battery cable 2 core 3 3 6 mm2 9 0 14 5 mm PV input cable 2 core 1 5 4 mm2 AC input cable 3 core 1 5 4 ...

Page 11: ...m Flat head screwdriver Scale line Installing an RJ45 Communications Cable for a Lithium Battery Ensure that caps and waterproof connectors are installed at all idle ports on the modules Connecting Cables Between the Function Module and Lithium Batteries PV input AC input Function module Lithium battery Lithium battery ...

Page 12: ...cting the Solar Hybrid Pole 1 Check whether the pole needs to be repainted Repaint the damaged area of the pole and then use the crane to hoist the pole to the foundation 2 Secure the pole to the foundation 1 Check whether the pole needs to be repainted Repaint the damaged area of the pole and then use the crane to hoist the pole to the foundation 2 Secure the pole to the foundation ...

Page 13: ...ystems view the port information in Device Manager and select the connected port Ensure that communications parameter settings on the terminal emulation software are the same as the default values on the device transmission rate 9600 bit s 8 data bits 1 stop bit no parity check and no traffic control Parameter Default Value Transmission rate 9600 bit s Traffic control No Parity check No Stop bit 1...

Page 14: ...un the ip address 10 0 0 1 255 255 255 0 command to set the IP address for the VLANIF interface 12 Run the quit command to exit the VLANIF interface view 13 Run the interface gigabitethernet 0 0 0 command to set a service interface Access the 0 0 0 interface view and set other service ports by referring to this interface setting The value of interface number depends on the interface number For exa...

Page 15: ...enable command to enable the RAW service function The information displayed in the following figure is for reference only 6 Run the quit command In the system view run the following commands Check the configuration result and verify that the server can receive data collected by the function module Run the display transport info command to check the serial port service configuration Run the display...