maximum of two IT or network cabinets. One power distribution unit provides
two power outputs to route A, and the other power distribution unit provides
two power outputs to route B for the corresponding cabinets.
●
The figures use single-phase power distribution units as an example.
Figure 3-7 Layout diagram
(1) General input unit
(2) Power distribution unit
(3) Aisle containment
Figure 3-8 Cabling diagram
3.2.5 Layout and Cable Routing Principles: Dual-Row Aisle
Containment, Crossing Rows (N+1 Scenario)
●
The number of power distribution units allocated to each row of cabinets
must be an even number.
●
If the power density per cabinet is less than or equal to 10 kW, single-phase
power distribution units are used and each power distribution unit supports a
maximum of six IT or network cabinets. One power distribution unit provides
six power outputs to the cabinets in the current row and route A in the other
row, and the other power distribution unit provides six power outputs to the
current row and route B in the other row.
●
The figures use single-phase power distribution units as an example.
New Main Way 2.0
User Manual
3 Installation
Issue 05 (2020-10-15)