14
System Settings
Description
Time
Set the local time zone, date, and time.
IP Address
Set the IP address, subnet mask, and default gateway of the iBOX. Set
this parameter based on the IP address assigned by the administrator.
Battery Curve
Sets the battery curve based on the battery brand and format.
Parallel Net Join Config
Sets this parameter when you connect iBOXs in parallel.
7. Access the
System Settings
page, and set the
Time
,
IP Address
,
Battery Curve
, and
Parallel
Net Join Config
parameters according to the following table.
1. Enter https://
NetEco IP address
in the address box of
Internet Explorer to log in to the NetEco homepage.
2. Access the
Configuration
>
Data Center Planning
page,
and select the site where the iBOX is located.
3. Choose
Device
>
Battery Detector
and drag the BMU
icon to the creation area.
4. On the
Management Info
pane, set the
Name
,
IP
Address
,
Port
, and
Connection Mode
for the iBOX.
5. Click
Connection Test
and save the setting after a
message indicating successful connection appears.
• IP address: Must be the same as the iBOX IP address.
• Port: Set to 502.
• Connection mode: Must be consistent with the iBOX
setting.
• When multiple iBOXs are connected in parallel, you
need to set parameters on the NetEco for each iBOX.
Logging In to the NetEco and Setting Parameters
5.3
iBOX Parameters:
ModbusTCP encryption
and
ModbusTCP authentication
NetEco Parameter:
Connection Mode
Disable
Non-SSL Connection
Enable
SSL Connection
NetEco page
NOTE
6
Networking the iBOX and iBAT
Networking switch ALM indicator RF_Z indicator Networking switch RUN/ALM indicator