5 Maintenance
Issue 04 (2020-02-29)
Copyright © Huawei Technologies Co., Ltd.
38
Solution
1.
Check whether the load exceeds the maximum power of the lithium battery (see the
appendix "Technical Specifications"). If so, expand the lithium battery capacity or
reduce the load of the power system.
2.
Check whether the load is short-circuited. If so, rectify the fault.
5.2.19 Charge Overcurrent Protection
Possible Cause
Internal hardware is faulty.
Solution
Replace the faulty module.
5.2.20 Heater Fault
Possible Cause
The heater is faulty.
Solution
Replace the faulty module.
5.2.21 BMU Missing
Possible Causes
The battery communications cable is loose.
The battery power cable is loose.
Solution
Check whether the battery communications or power cable is loose. If so, secure the cable.
5.3 Component Replacement