background image

Table 5-17

 Equipment Grounding Specifications

No.

Description

1

All communication devices and auxiliary devices (such as mobile base stations,
transmission and switching devices, power supply devices) in the equipment room
should be grounded for protection. Connect all protective ground for various
devices jointly to a general ground bar, and then to the same protective ground bar
in the room together with the protective ground (PGND) of the device.

2

The PGND of the equipment is shorted to the copper ground bar provided by the
customer. The short-circuiting cable used should be a yellow-green plastic
insulated cable with a copper core and a cross-sectional area greater than 25 sq.
mm (0.039 sq. in.).

3

There are grounding terminals and grounding lugs at the lower part of the front
door, rear door and side panel of the cabinet, connected to the grounding terminals
of the cabinet framework through connection cables with cross-sectional area of no
less than 1.6 sq. mm (0.002 sq. in.).

4

Ensure that all metal components of the cabinet conduct well. No insulating
coating should be sprayed on the connection part of the metal components.

5

Connect the cabinets in the same row by fastening captive screws and gaskets on
the top of the cabinets. Do not spray any coating into a rectangular area measuring
30 mm x 50 mm (1.18 in. x 1.97 in.) around the connection hole for a captive bolt.
Measures to prevent rust and corrosion must be taken for this area. Zinc
electroplating with iridescent yellow chromate conversion coating should be
applied to the gasket and nut to ensure good electrical contact.

6

When combining cabinets of the same type, short-circuiting cables are required to
connect the ground busbars (if any) of the cabinets. The cross-sectional area of the
short-circuiting cable is 6 sq. mm (0.009 sq. in.) and is no more than 300 mm (11.8
in.) long. Connect the two ends of the short-circuiting cable to the ground busbar
terminals of neighboring cabinets and fix them firmly.

 

5.3.4 Grounding Specifications for Communications Power
Supply

Table 5-18

 shows the grounding specifications for communication power supplies.

Table 5-18

 Grounding specifications for communication power supplies

No.

Description

1

The inlet for the AC power cable at the equipment room should be equipped with a
surge protection device (C-level) with a nominal discharge current no less than 20
kA.

2

The protective ground for the power supply and that for communication equipment
share the same grounding conductor. If the power supply and the equipment are in
the same equipment room, use the same protective ground bar for them if possible.

R250D-E
Hardware Installation and Maintenance Guide

5 Appendix

Issue 01 (2016-09-30)

Huawei Proprietary and Confidential

Copyright © Huawei Technologies Co., Ltd.

76

Summary of Contents for 50082922

Page 1: ...R250D E Hardware Installation and Maintenance Guide Issue 01 Date 2016 09 30 HUAWEI TECHNOLOGIES CO LTD ...

Page 2: ... be within the purchase scope or the usage scope Unless otherwise specified in the contract all statements information and recommendations in this document are provided AS IS without warranties guarantees or representations of any kind either express or implied The information in this document is subject to change without notice Every effort has been made in the preparation of this document to ens...

Page 3: ...ion which if not avoided will result in death or serious injury Indicates a potentially hazardous situation which if not avoided could result in death or serious injury Indicates a potentially hazardous situation which if not avoided may result in minor or moderate injury Indicates a potentially hazardous situation which if not avoided could result in equipment damage data loss performance deterio...

Page 4: ...d environment deterioration Change History Changes between document issues are cumulative The latest document issue contains all changes made in previous issues Issue 01 2016 09 30 Initial commercial release R250D E Hardware Installation and Maintenance Guide About This Document Issue 01 2016 09 30 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd iii ...

Page 5: ...n the Device 15 3 Logging In to the Device 16 3 1 Logging In to the Device Using STelnet Telnet 17 4 Hardware Failures 18 4 1 A Device Fails to Be Powered On 19 5 Appendix 21 5 1 On site Cable Assembly and Installation 22 5 1 1 Cable Assembly Precautions 22 5 1 2 Assembling Power Cables 23 5 1 3 Assembling Ethernet Cables 31 5 1 4 Installing Cable Accessories 45 5 1 5 Replacing the Mold of the Cri...

Page 6: ...for Laying Out Grounding Cables 77 5 4 Engineering Labels for Cables 78 5 4 1 Introduction to Labels 78 5 4 2 Engineering Labels for Optical Fibers 86 5 4 3 Engineering Labels for Network Cables 89 5 4 4 Engineering Labels for User Cables 90 5 4 5 Engineering Labels for Power Cables 91 5 5 Guide to Using Optical Modules 94 5 6 Fault Tag 97 5 7 Installation Checklist 98 R250D E Hardware Installatio...

Page 7: ...ns or designs It also has an IEEE 802 11a b g n ac ac Wave 2 wireless module and can work on both 5 GHz and 2 4 GHz frequency bands It supports PoE power supply and can be directly connected to a central AP and deployed in a room The central AP and the R250D E are connected through network cables which greatly extends the coverage range enhances flexibility in AP deployment and planning and reduce...

Page 8: ...upported 3 Default Reset button restores factory settings and restarts the device if you hold down the button more than 3 seconds 4 Pass Through Pass Through port connects to a network cable or phone cable for transparent transmission 5 GE2 to GE4 10 100 1000M port connects to the wired Ethernet 6 GE1 PoE_OUT 10 100 1000M port connects to the wired Ethernet and supports PoE output 7 GE0 PoE_IN 10 ...

Page 9: ...ator GE1 PoE_OUT GE2 GE3 Pass Through GE4 Indicator NOTE l The indicator is located inside the panel which turns on after the AP is powered on l Indicator colors may vary slightly at different temperature Table 1 2 Indicator description Type Color Status Description Default status after power on Green Steady on The AP is just powered on and the software is not started yet R250D E Hardware Installa...

Page 10: ...unning properly the Ethernet connection is normal and no STA is associated with the AP The system is in low power consumption state Alarm Green Blinking once Alarm Green every 0 25s 4 Hz l The software is being upgraded l After the software is uploaded and started the AP working in Fit AP mode requests to go online on the AC and maintains this state until it goes online successfully on the AC befo...

Page 11: ...er specifications Power input l DC 48V 5 l PoE power supply in compliance with IEEE 802 3af at Maximum power consumption 11 5 W excluding the output power of the USB port and PoE_OUT port NOTE The actual maximum power consumption depends on local laws and regulations Environment specifications Operating temperature l 60 m to 1800 m 0 C to 40 C l 1800 m to 5000 m Temperature decreases by 1 C every ...

Page 12: ...er contact technical support personnel Part Number Description 50082922 R250D E Mainframe 11ac 2x2 Double Frequency Built in Antenna R250D E Hardware Installation and Maintenance Guide 1 Product Overview Issue 01 2016 09 30 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 6 ...

Page 13: ...2 4 Determining the Installation Position 2 5 Installing the Device 2 6 Cable Connection 2 7 Checking the Device After Installation 2 8 Powering on the Device R250D E Hardware Installation and Maintenance Guide 2 AP Installation Issue 01 2016 09 30 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 7 ...

Page 14: ...the aisles CAUTION Only the qualified personnel are permitted to install and remove the device and its accessories Before installation and operation read the safety precautions carefully Tool Preparation To install APs prepare tools listed in Table 2 1 Table 2 1 Tools Phillips screwdriver Protective gloves ESD gloves Slip proof glove Marker Hammer drill Claw hammer Diagonal pliers Wire stripper R2...

Page 15: ...met Safety belt Anti skid shoes 2 2 Installation Flowchart The following figure shows the process for installing an AP R250D E Hardware Installation and Maintenance Guide 2 AP Installation Issue 01 2016 09 30 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 9 ...

Page 16: ...t l Screws l Quick Start Guide l Warranty card l MAC address label l SN label NOTE If a PoE adapter or a DC power adapter is required you need to purchase it separately 2 4 Determining the Installation Position l Do not deploy the device in places with high temperature dust noxious gas unstable voltage much vibrations or strong noise or in places near flammable or explosive materials and interfere...

Page 17: ...ance Requirement Indoor installation l There should be at least a 7 m distance between antennas l The antennas should be placed at least 2 m from the 4G antennas of the carrier l The antennas should be placed far away from electronic devices that may produce interference such as microwave ovens NOTE If antennas are embedded into APs the deployment distance requirements on the antennas are those on...

Page 18: ...wo screws 1N m M4 GE1 PoE_OUT GE2 GE3 Pass Through GE4 5 Close the cover If torx security screws are used to prevent theft use a T9 torx security screwdriver to tighten the torx security screws into the device GE1 PoE_OUT GE2 GE3 Pass Through GE4 0 16N m ST2 5 GE1 PoE_OUT GE2 GE3 Pass Through GE4 NOTE You need to separately prepare the T9 torx security screwdriver R250D E Hardware Installation and...

Page 19: ...the AP along the rail until the stand reaches the end of the grooves Place the stand with the AP on the desk steadily NOTE You need to separately purchase a desktop stand 2 6 Cable Connection Table 2 3 describes the cable connections Figure 2 2 Appearance of the R250D E 1 2 3 5 4 Pass Through GE0 PoE_IN R250D E Hardware Installation and Maintenance Guide 2 AP Installation Issue 01 2016 09 30 Huawe...

Page 20: ... port of an upper layer PSE through the uplink network port l The GE0 PoE_IN port supports PoE input l CAT5e cables or higher must be used l The length of a network cable cannot exceed 100 m NOTE l If the R250D E needs to connect to the Ethernet ensure that the Ethernet cable is working properly If the Ethernet cable is not working properly the R250D E may fail to be powered on or fail to work Bef...

Page 21: ...ved 2 The device is securely installed 3 The power cables are intact and not spliced 4 Terminals of the power cables are welded or cramped firmly 5 All power cables are not short circuited or reversely connected and must be intact with no damage 6 The power cables and ground cables are separated from other cables and bundled separately 7 Connectors of signal cables are complete intact and tightly ...

Page 22: ...is Chapter 3 1 Logging In to the Device Using STelnet Telnet R250D E Hardware Installation and Maintenance Guide 3 Logging In to the Device Issue 01 2016 09 30 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 16 ...

Page 23: ...on the AC you can remotely log in to the AC on a local terminal and run the display ap all command to check the IP address of the device The following example uses the default parameters and is used for reference only Step 1 Use network cables and a LAN switch to connect the PC to the network interface of the device Step 2 Assign the PC with an IP address on the same network segment as the default...

Page 24: ...common methods for troubleshooting typical hardware faults 4 1 A Device Fails to Be Powered On R250D E Hardware Installation and Maintenance Guide 4 Hardware Failures Issue 01 2016 09 30 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 18 ...

Page 25: ... fail If the device has a built in power supply the device itself may be faulty PoE power supply l The power sourcing equipment does not support the PoE function or is faulty l The power sourcing equipment is incorrectly configured the PoE function is disabled or the power off time range is improperly set l The line is faulty the network cable or distribution frame is damaged l The device is fault...

Page 26: ...echnical support personnel or Huawei agent and ask them to replace the device PoE power supply 1 Check whether the power sourcing equipment supports PoE or is faulty 2 Check whether the configuration on the power sourcing equipment causes PoE power supply errors such as the PoE function is disabled or the power off time range is incorrectly set 3 Check whether the network cable or distribution fra...

Page 27: ...Operation 5 3 Equipment Grounding Specifications 5 4 Engineering Labels for Cables 5 5 Guide to Using Optical Modules 5 6 Fault Tag 5 7 Installation Checklist R250D E Hardware Installation and Maintenance Guide 5 Appendix Issue 01 2016 09 30 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 21 ...

Page 28: ...assembly l Hold terminals of cables instead of pulling the cables themselves when installing or removing cable components l Take the following precautions when cutting or stripping cables Make cables slightly longer than necessary Coil cables longer than 2 m 6 56 ft after cutting Bind and fasten the coils using bundling ropes The inner diameters of the coils should be larger than 20 times the oute...

Page 29: ...mponents of an OT terminal and a power cable Figure 5 1 Components of an OT terminal and a power cable A Heat shrinkable tubing B Bare crimping terminal C Insulation D Conductor Procedure Step 1 Based on the cross sectional area of the cable conductor strip a length of insulation coating C to expose the conductor D of length L1 as shown in Figure 5 2 The recommended values of L1 are listed in Tabl...

Page 30: ...al Area of Conductor mm2 in 2 Value of L1 mm in 1 0 002 7 0 28 10 0 015 11 0 43 1 5 0 002 7 0 28 16 0 025 13 0 51 2 5 0 004 7 0 28 25 0 039 14 0 55 4 0 006 8 0 31 35 0 054 16 0 63 6 0 009 9 0 35 50 0 077 16 0 63 NOTE If you are proficient in assembling OT terminals and power cables you can obtain the value of L1 by comparing the part to be crimped with the power cable Step 2 Put the heat shrinkabl...

Page 31: ...n Step 4 Crimp the joint parts of the bare crimping terminal and the conductor as shown in Figure 5 4 NOTE The shapes of crimped parts may vary with the crimping dies Figure 5 4 Crimping the joint parts of the bare crimping terminal and the conductor OT terminal Step 5 Push the heat shrink tubing A toward the connector until the tube covers the crimped part and then use a heat gun to heat the tube...

Page 32: ...Assembling the JG Terminal and Power Cable Context Figure 5 6 shows the components of a JG terminal and a power cable Figure 5 6 Components of a JG terminal and a power cable A JG terminal B Heat shrinkable tubing C Insulation layer of a power cable D Conductor of a power cable R250D E Hardware Installation and Maintenance Guide 5 Appendix Issue 01 2016 09 30 Huawei Proprietary and Confidential Co...

Page 33: ...alue of L as required Figure 5 7 Stripping a power cable JG terminal Table 5 2 Mapping between the cross sectional area of the conductor and the value of L Cross Sectional Area of Conductor mm2 in 2 Value of L mm in 16 0 025 13 0 51 25 0 039 14 0 55 35 0 054 16 0 63 50 0 077 16 0 63 Step 2 Put the heat shrink tubing onto the bare crimping terminal as shown in Figure 5 8 R250D E Hardware Installati...

Page 34: ...rminal and the conductor as shown in Figure 5 9 Figure 5 9 Crimping the joint parts of the bare crimping terminal and the conductor JG terminal Step 5 Push the heat shrink tubing toward the connector until the tube covers the crimped part and then use a heat gun to heat the tube as shown in Figure 5 10 Figure 5 10 Heating the heat shrink tubing JG terminal R250D E Hardware Installation and Mainten...

Page 35: ... power cable Procedure Step 1 Strip a part of the insulation to expose the cable conductor with a length of L1 as shown in Figure 5 12 The recommended values of L1 are listed in Table 5 3 NOTICE When you strip a power cable do not damage the conductor of the cable Figure 5 12 Stripping a power cable cord end terminal R250D E Hardware Installation and Maintenance Guide 5 Appendix Issue 01 2016 09 3...

Page 36: ...e cord end terminal onto the conductor and ensure that the conductor is aligned with the edge of the cord end terminal as shown in Figure 5 13 NOTICE After the conductor is fed into the cord end terminal the protruding part of the conductor must not be longer than 1 mm 0 04 in Figure 5 13 Putting the cord end terminal onto the conductor Step 3 Crimp the joint parts of the cord end terminal and the...

Page 37: ... 2 Maximum Width of Crimped Terminal W1 mm in 0 25 0 0004 1 0 04 0 5 0 0008 1 0 04 1 0 0 0015 1 5 0 06 1 5 0 0023 1 5 0 06 2 5 0 0039 2 4 0 09 4 0 006 3 1 0 12 6 0 009 4 0 16 10 0 015 5 3 0 21 16 0 025 6 0 24 25 0 039 8 7 0 34 35 0 054 10 0 39 End 5 1 3 Assembling Ethernet Cables Assembling the Shielded RJ45 Connector and Ethernet Cable R250D E Hardware Installation and Maintenance Guide 5 Appendi...

Page 38: ...ires Procedure Step 1 Fit the jacket of the connector onto the Ethernet cable as shown in Figure 5 16 Figure 5 16 Fitting the jacket of the connector onto the Ethernet cable Step 2 Remove a 30 mm 1 18 in long section of the jacket cut off the nylon twine inside the jacket and cut a no more than 5 mm 0 20 in cleft in the jacket as shown in Figure 5 17 R250D E Hardware Installation and Maintenance G...

Page 39: ...l shell as shown in Figure 5 18 Figure 5 18 Fitting the metal shell onto the twisted pair cable Step 4 Fit the metal shell onto the twisted pair cable until the shield layer is covered completely Along the edge of the metal shell cut off the aluminum foil shield layer and ensure that there is no surplus copper wire The exposed twisted pair cable is about 20 mm 0 79 in long as shown in Figure 5 19 ...

Page 40: ...ires through the wire holder C G Figure 5 21 Cable locations in a wire holder White Green Green White Orange Orange Blue White Blue White Brown Brown Step 6 Align the four pairs of cables in the holder as shown in Figure 5 22 The connections between the wires and the pins are shown in Figure 5 23 and listed in Table 5 5 R250D E Hardware Installation and Maintenance Guide 5 Appendix Issue 01 2016 0...

Page 41: ...n 8 Pin 1 Table 5 5 Connections between wires and pins using a straight through cable as an example Matching Pins of Wires Wire Color 1 White Orange 2 Orange 3 White Green 4 Blue 5 White Blue 6 Green 7 White Brown R250D E Hardware Installation and Maintenance Guide 5 Appendix Issue 01 2016 09 30 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 35 ...

Page 42: ... Figure 5 25 NOTE Ensure that the wire holder is in good contact with the connector body Figure 5 25 Putting the connector body onto the wire holder Step 9 Push the metal shell toward the connector body until the wire holder and the connector body are engaged completely Crimp the connector as shown in Figure 5 26 R250D E Hardware Installation and Maintenance Guide 5 Appendix Issue 01 2016 09 30 Hu...

Page 43: ...ushing the metal shell Step 11 To complete the assembly of the other end repeat Step 1 through Step 10 End Assembling an Unshielded RJ45 Connector and Ethernet Cable Context Figure 5 28 shows the components of an unshielded RJ45 connector and cable R250D E Hardware Installation and Maintenance Guide 5 Appendix Issue 01 2016 09 30 Huawei Proprietary and Confidential Copyright Huawei Technologies Co...

Page 44: ...9 Removing the jacket of a twisted pair cable unit mm in Step 2 Align the four pairs of wires and cut the ends neatly as shown in Figure 5 30 The connections between the wires and the pins are listed in Table 5 6 Figure 5 30 Connections between wires and pins unit mm in C 16 White Orange White Green Orange Blue White Blue Green White Brown Brown Pin 8 Pin 1 R250D E Hardware Installation and Mainte...

Page 45: ...ng the connector Step 4 To complete the assembly of the other end repeat Step 1 through Step 3 End Checking the Appearance of Contact Strips Context l To ensure proper contact between the crimped wires and the wire conductors the heights and sizes of the contact strips must be standard and the same l The contact strips must be parallel to each other with an offset of less than 5 The top margin of ...

Page 46: ...ntact strips are of the same height The height should be 6 02 0 13 mm 0 237 0 005 If a measuring tool is not available you can compare the connector with a standard connector Figure 5 32 shows an unqualified piece and Figure 5 33 shows a qualified piece NOTE All unqualified pieces must be crimped again Figure 5 32 Contact strips of different heights Figure 5 33 Contact strips of the same height St...

Page 47: ...tors are well aligned and intact If a separator is skewed and cannot be fixed replace it with a new RJ45 connector Figure 5 36 shows an unqualified piece Figure 5 36 Skewed plastic separators Step 5 Hold the connector with the side facing towards you and check whether you can see the cross sections of the wires Ensure that the ends of the wires are in good contact with the edge R250D E Hardware In...

Page 48: ...itch to network devices Table 5 7 lists the connections of core wires in a straight through cable Table 5 7 Connections of core wires in a straight through cable RJ45 Connector 1 RJ45 Connector 2 Core Wire Color Twisted or Not 2 2 Orange Twisted 1 1 Orange White 6 6 Green Twisted 3 3 Green White 4 4 Blue Twisted 5 5 Blue White 8 8 Brown Twisted 7 7 Brown White l Crossover cables are connected in a...

Page 49: ... Feed both connectors of the cable into the ports of the cable tester Step 2 After the connectors are properly inserted turn on the tester If the indicators from 1 to G turn on simultaneously you can infer that the pins work normally and the wires are correctly connected NOTE Turn the switch to the S position to slow down lighting of the indicators so that you can see the indicators more clearly a...

Page 50: ...which the indicators turn on which depends on the wire connections of a crossover cable The Ethernet cable is qualified if the indicators turn on in the following sequence At the master left section of the tester the indicators turn on in the sequence of 1 8 G At the slave right section of the tester the indicators turn on in the sequence of 3 6 1 4 5 2 7 8 G If the indicators do not come on in th...

Page 51: ... the same For example in this document the adapters of cable connectors have separate interfaces In the actual situation the adapters may have interfaces fixed on equipment Use dedicated tools provided or specified by Huawei and follow the installation procedure described here Bending Radius Unless otherwise specified bending radius R of cables or fibers must meet the requirements listed in Table ...

Page 52: ...or adapter may be damaged l When removing densely aligned cables or fiber connectors use dedicated pliers such as cable pulling pliers and fiber pulling pliers l Do not twist bend stretch or extrude fibers during installation l Cover the idle fiber connectors with dust caps Remove the dust caps before using the fiber connectors Requirements for Cable Routing l To protect cables remove the burrs in...

Page 53: ...g sleeve is installed as shown in Figure 5 43 where A is correct and B is incorrect Figure 5 43 Installing an OT terminal showing the orientation of crimping sleeve b Place the spring washer and flat washer in turn mount a matching screw and fasten it clockwise as shown in Figure 5 44 R250D E Hardware Installation and Maintenance Guide 5 Appendix Issue 01 2016 09 30 Huawei Proprietary and Confiden...

Page 54: ...e you install two OT terminals on a post ensure that the two terminals can be installed on the post and that the electrical connecting pieces have a large contact area Two OT terminals can be installed using any of these methods Bend the upper OT terminal at a 45 or 90 degree angle as shown in Figure 5 46 Cross the two terminals as shown in Figure 5 47 R250D E Hardware Installation and Maintenance...

Page 55: ... To remove an OT terminal loosen the screw counterclockwise End Installing the Cord End Terminal Procedure Step 1 Hold a cord end terminal upright and place it on a terminal jack as shown in Figure 5 48 To ensure bump contact and dense connection place the plain side of the terminal outwards R250D E Hardware Installation and Maintenance Guide 5 Appendix Issue 01 2016 09 30 Huawei Proprietary and C...

Page 56: ... the terminal is less than 2 mm 0 079 in in length l Do not press the insulation of the terminal l Insert only one terminal into one jack Step 3 Move the cable slightly and ensure that it is securely connected Step 4 Before you remove a cord end terminal loosen the screw counterclockwise End Installing Ethernet Adapters R250D E Hardware Installation and Maintenance Guide 5 Appendix Issue 01 2016 0...

Page 57: ...Figure 5 51 Figure 5 51 Feeding the male shielded connector into the female shielded connector Step 3 When you hear a click the cable connector is completely inserted in the port The clip on the cable connector pops up to fix the connector in the port Pull the connector slightly and ensure that it is securely connected as shown in Figure 5 52 R250D E Hardware Installation and Maintenance Guide 5 A...

Page 58: ... Removing a shielded Ethernet connector End Installing an Unshielded Ethernet Connector Procedure Step 1 Hold the male and female connectors with the male connector facing the female connector as shown in Figure 5 54 R250D E Hardware Installation and Maintenance Guide 5 Appendix Issue 01 2016 09 30 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 52 ...

Page 59: ...ector Step 3 A crisp click indicates that the connector is locked by the locking key Pull the connector slightly and ensure that it is securely connected Figure 5 56 shows an installed Ethernet connector Figure 5 56 Installed unshielded Ethernet connector R250D E Hardware Installation and Maintenance Guide 5 Appendix Issue 01 2016 09 30 Huawei Proprietary and Confidential Copyright Huawei Technolo...

Page 60: ...r connectors you must use a dedicated tool if the connectors are densely installed Cleaning Fiber Connectors Procedure Step 1 Clean the pins of a fiber connector by using lint free cotton and alcohol Step 2 Clean the pins again by using dust free cotton If necessary clean the pins by using an air gun Ensure that the pins are free from any fiber or debris End Installing an FC Fiber Connector R250D ...

Page 61: ...onnector with the female connector and gently push the male connector until it is completely seated in the female connector as shown in Figure 5 59 Figure 5 59 Feeding the male connector into the female connector Step 4 Fasten the locking nut clockwise and ensure that the connector is securely installed as shown in Figure 5 60 R250D E Hardware Installation and Maintenance Guide 5 Appendix Issue 01...

Page 62: ... fiber connector End Installing an LC Fiber Connector Procedure Step 1 Remove the dustproof cap of the LC fiber connector and store it for future use Step 2 Align the core pin of the male connector with that of the female connector as shown in Figure 5 62 R250D E Hardware Installation and Maintenance Guide 5 Appendix Issue 01 2016 09 30 Huawei Proprietary and Confidential Copyright Huawei Technolo...

Page 63: ...e fiber connector as shown in Figure 5 63 Figure 5 63 Feeding the male connector into the female connector Step 4 A clicking sound indicates that the male connector is locked as shown in Figure 5 64 Figure 5 64 Installed LC connector R250D E Hardware Installation and Maintenance Guide 5 Appendix Issue 01 2016 09 30 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 57 ...

Page 64: ...emale connector as shown in Figure 5 66 Figure 5 66 Aligning the male connector with the female connector Step 3 Feed the fiber connector into the female connector with your fingers holding the shell of the fiber connector not the pigtail When you hear a click the fiber connector is secured by the clips internal parts not illustrated in the figure Pull the fiber connector gently If the connector d...

Page 65: ...ell as shown in Figure 5 68 Figure 5 68 Disassembling an SC fiber connector End Installing an MPO Connector Procedure Step 1 Remove the dustproof cap of the MPO fiber connector and store it for future use Step 2 Align the core pin of the male connector with that of the female connector as shown in Figure 5 69 R250D E Hardware Installation and Maintenance Guide 5 Appendix Issue 01 2016 09 30 Huawei...

Page 66: ... and female connectors are securely installed as shown in Figure 5 70 Figure 5 70 Installed MPO fiber connector Step 4 To disassemble an MPO fiber connector hold the shell labeled PULL and remove the male connector as shown in Figure 5 71 R250D E Hardware Installation and Maintenance Guide 5 Appendix Issue 01 2016 09 30 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 60 ...

Page 67: ...terclockwise as shown in Figure 5 72 Figure 5 72 Loosening two fastening screws Step 2 Hold the handles of the COAX crimping tools to open the self locking mechanism The jaw of the COAX crimping tools opens automatically as shown in Figure 5 73 R250D E Hardware Installation and Maintenance Guide 5 Appendix Issue 01 2016 09 30 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd...

Page 68: ... Removing the mold from the COAX crimping tools Step 4 Place the mold to be installed into the jaw of the COAX crimping tools and align the screw holes as shown in Figure 5 75 R250D E Hardware Installation and Maintenance Guide 5 Appendix Issue 01 2016 09 30 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 62 ...

Page 69: ...y to match the mold and the jaw completely Align the screw holes as shown in Figure 5 76 Figure 5 76 Aligning the screw holes Step 6 Hold the handles of the COAX crimping tools with one hand Tighten the two fastening screws clockwise Figure 5 77 and Figure 5 78shows the mold installed in the COAX crimping tool R250D E Hardware Installation and Maintenance Guide 5 Appendix Issue 01 2016 09 30 Huawe...

Page 70: ...ation factors Construction structure heating and ventilation power supply lighting and fire proof construction of the equipment room should be designed by specialized construction designers to suit the environmental requirements of devices The equipment room should also follow local regulations concerning the industrial construction environmental protection fire safety and civil air defense Constr...

Page 71: ... The doors and windows of the equipment room must be kept closed to maintain an airtight room l Using steel doors to ensure sound insulation is recommended l No cracks or openings are allowed on the walls or floors The outlet holes on the walls or windows must be sealed Walls must be constructed such that they are smooth wear resistant dustproof flame retardant sound insulated heat absorptive and ...

Page 72: ...pment with the largest capacity Net height The minimum height of the equipment room should not be less than 3 m 9 84 ft The minimum height of the equipment room is the net height below overhead beams or ventilation pipes Floor The floor in the equipment room should be semi conductive and dustproof A raised floor with an ESD covering is recommended Cover the raised floor tightly and solidly The hor...

Page 73: ... not place a fire hydrant in the equipment room but place it in the corridor or near the staircase Internal partition wall Separate the area where the equipment is installed from the equipment room door The partition wall can block some outside dust Installation position of the air conditioner Install air conditioner vents so that the air does not blow directly on equipment Other requirements Avoi...

Page 74: ...s for ground wall and ceiling construction l Use screens on the door and windows facing outside The outer windows should be dust proof l Clean the equipment room regularly and clean the air filter monthly l Wear shoe covers and ESD clothing before entering the equipment room Requirements for Corrosive Gases The room should be free from dusts and corrosive gases such as SO2 H2S and NH3 Table 5 12 l...

Page 75: ... Equipment Room All interference sources inside or outside the equipment room can cause equipment problems with capacitive coupling inductive coupling electromagnetic wave radiation and common impedance including grounding system coupling Prevent the interference using these approaches l Take effective measures against electrical interference from the power supply system l Do not use the working g...

Page 76: ...connect the power equipment to the collective ground cable of the telecommunication site or the protective ground bar of the equipment room Equipotential connection l Properly ground the devices and auxiliary devices in the room such as mobile base station transmission switching equipment power supply equipment and cable distribution frame Connect all PGND cables to the collective protective groun...

Page 77: ...ound cable l Do not use aluminum cables as ground cables Adopt measures to prevent electrification corrosion when connecting different metal parts together l Use a copper busbar as the collective ground cable with a cross sectional area of no less than 120 mm2 0 19 in 2 or use the galvanized flat steel of the same resistance Insulate the collective ground cable from the reinforcing steel bars of t...

Page 78: ...res must be taken on the ground terminals l The fiber reinforcing rib can be directly connected to the ground bar of the cabinet Before wrapping the reinforcing rib with insulation tape cut a 0 5 m 1 64 ft segment from the reinforcing rib Wrap the reinforcing rib with at least five layers of insulation tape Keep the reinforcing rib at least 5 cm 1 969 in from the cabinet surface 5 2 2 Requirements...

Page 79: ... voltage of the power mains that supply power directly to devices exceeds the rated voltage by 10 to 5 or exceeds the voltage range that devices can support a voltage regulating device or voltage stabilizing device is required l If the mains do not supply power for the device directly or if the mains voltage exceeds the rated voltage by 15 to 10 or exceeds the input voltage range of the DC power s...

Page 80: ...ated current Regulated voltage precision If the AC input voltage is in the range of 85 to 110 of the rated value and the load current is in the range of 5 to 100 of the rated value the output voltage of the rectifier ranges from 46 0 V to 56 4 V with the regulated voltage precision less than or equal to 1 Overshoot amplitude of switch on off Integral value of the DC output voltage 5 Peak noise vol...

Page 81: ...are the same grounding conductor 2 The cable trays shells metal ventilation pipes metal doors and windows in the equipment room should be grounded for protection 3 The metal parts of the equipment which are electrically floating in normal conditions should be grounded for protection 4 The ground cable must be connected securely to the protective ground bar of the equipment room 5 Do not use other ...

Page 82: ...area measuring 30 mm x 50 mm 1 18 in x 1 97 in around the connection hole for a captive bolt Measures to prevent rust and corrosion must be taken for this area Zinc electroplating with iridescent yellow chromate conversion coating should be applied to the gasket and nut to ensure good electrical contact 6 When combining cabinets of the same type short circuiting cables are required to connect the ...

Page 83: ...of the equipment room For cables inside the equipment room install surge protection devices at the interface to the equipment The PGND cable for the surge protection devices should be as short as possible 2 The incoming and outgoing signal cables to and from the office and unused wires inside the cable should be grounded for protection 3 The Tone Data Access TDA cable must pass through the Main Di...

Page 84: ...the cables facilitate correct and orderly connection of cables and easy maintenance after installation Engineering labels are specialized for power cables and signal cables l Signal cables include network cables optical fibers and user cables l Power cables include the AC power cables and DC power cables NOTE Fill in labels according to specified requirements to keep consistency of labels in the e...

Page 85: ...label when affixed to the cable and its size is 1 mm x 2 mm 0 04 in x 0 08 in The word TO upside down in the figure at the lower right corner of the label is used to identify the opposite end of the cable on which the label is affixed Power Cable Label The label for power cables should be attached to the identification plate on the cable ties that are attached to the cable The identification plate...

Page 86: ...in a template from the Huawei local office to print labels The template is made in Microsoft Word Follow these instructions to use the template l You can modify the contents of the template Do not change settings of centered characters direction and fonts R250D E Hardware Installation and Maintenance Guide 5 Appendix Issue 01 2016 09 30 Huawei Proprietary and Confidential Copyright Huawei Technolo...

Page 87: ...rection have been set correctly If the printout conforms to the sheet of labels print the labels on the label paper If the printout does not conform adjust the page setup and try printing again until the correct printout is produced The method for adjusting the page setup is as follows 1 Select File Page Setup 2 Select Layout and set Header and Footer as 0 3 Select the Margins tab page Select Left...

Page 88: ...en printing the text Use the space bar to move the text to the next line Writing Labels Writing Tools To make sure the printouts are clear and legible use black markers instead of ball point pens to write the labels If no marker is available black ball point pens are allowed although not recommended Compared with ball point pens water proof markers are better When writing with a ball point pen do ...

Page 89: ...es for example to avoid cable bending or affecting other cables other positions are allowed to attach the labels The rectangular part with text is attached facing right or downward as shown in Figure 5 85 The details are as follows The identification card is to the right of the cable in vertical cabling The identification card should be downward when you lay out the cable horizontally Figure 5 85 ...

Page 90: ...es Cable ties should be bound on both ends of a cable After the bundling the finished identification plate should be on top of the cable in horizontal cabling or on the right side of the cable in vertical cabling as shown in Figure 5 87 The details are as follows l The identification card is to the right of the cable in vertical cabling l The identification card is on the top of the cable in horiz...

Page 91: ...carry information about the location of the ports connected to both ends of the cable Figure 5 88 shows the information on both sides of the labels affixed to the signal cables l Area 1 contains the location information of the local end of the cable l Area 2 with the word TO contains the location information of the opposite end of the cable l Area 3 has been folded up inside the label Figure 5 88 ...

Page 92: ...t the optical interfaces on the boards in a chassis or on the device boxes There are two types of labels for optical cables l One is for the fiber that connects the optical interfaces on two devices l The other is for the fiber that connects the device and the ODF Labels for the Optical Fibers Connecting Devices Meaning of the Label Table 5 22 lists information on both sides of the labels affixed ...

Page 93: ...e room l G01 01 01 01 T indicates that the opposite end of the optical fiber is connected with optical transmitting interface 01 in slot 01 chassis 01 in the cabinet in row G column 01 in the machine room Labels for the Optical Fibers Connecting the Device and an ODF Meaning of the Labels Table 5 23 shows information on both sides of labels attached to an optical fiber between a device and an opti...

Page 94: ...numbered from A to Z N The cabinet columns from left to right are numbered from 01 to 99 For example G01 is the ODF of row G and column 01 B row number of the terminal device Range from 01 to 99 for example 01 01 C column number of the terminal device R Optical receiving interface T optical transmitting interface Example of the Label Figure 5 90 shows a sample label on an optical fiber Figure 5 90...

Page 95: ... For example A01 is the first cabinet in row A B chassis number Numbered in bottom up order with two digits for example 01 C physical slot number Numbered with two digits in top down and left right order For example 01 D network port number Numbered in top down and left right orders For example 01 MN Z MN cabinet number For example B02 is the second cabinet in row B Z Location number Fill in the l...

Page 96: ...o actual connections Label Example Figure 5 91 shows a sample label on an Ethernet cable Figure 5 91 Sample label on an Ethernet cable A01 TO 03 01 01 B02 03 01 Meaning of the label in Figure 5 91 l A01 03 01 01 indicates that one end of the network cable is connected to network interface 01 in slot 01 chassis 03 of the cabinet in row A column 01 in the equipment room l B02 03 01 indicates that an...

Page 97: ...99 for example 01 01 C column number of the terminal device Example of the Label Figure 5 92 shows a sample label on a user cable Figure 5 92 Sample label on a user cable A01 TO 03 01 01 MDF G01 01 01 The meaning of the label in Figure 5 92 is as follows l A01 03 01 01 indicates that the local end of the user cable is connected to port 1 in slot 1 chassis 03 of the cabinet in row A column 01 in th...

Page 98: ...w number or column number or the connector can be identified without them BC can be omitted It is unnecessary to identify the row and column number for BGND and PGND MN BC B BGND MN BC B PGND The label only carries location information about the destination direction of the power cable whereas information about the local end is unnecessary That is the label only carries location information about ...

Page 99: ... labels for PGND cables should be given in a similar way Engineering Labels for AC Power Cables These labels are affixed to both ends of an AC power cable that provides AC power supply to cabinets including 110 220 V PGND and BGND cables The 110 220 V AC cables and related PGND and BGND cables are covered with an insulating sheath so the labels need to contain only the word AC and the cabinet numb...

Page 100: ... use Huawei certified optical modules Obtain the electronic label of the optical module and contact technical support personnel to confirm whether it is a Huawei certified optical module 1 An optical module is not completely installed in position If the optical module is not completely installed in position and the latch boss is not secured the device cannot identify the optical module After the o...

Page 101: ...al module when it is open and closed When inserting the optical module make sure that the release handle is closed At this time the latch boss locks the optical module After the optical module is inserted try pulling it out to see if it is installed in position If the optical module cannot be pulled out it is secured Figure 5 95 State of the release handle Close the release handle Open the release...

Page 102: ... Using fibers to protect an optical module 3 Cover unused optical connectors with protective caps as shown in Figure 5 99 and then lay out fibers on the fiber rack or coil them in a fiber management tray to prevent fibers from being squeezed Figure 5 99 Installing a protective cap on a fiber 4 If a receptacle or an optical connector has not been used for a long time and is not covered with a prote...

Page 103: ...erwise the optical module will be burnt 2 When performing a self loop test use an optical attenuator Do not loosen the optical connector instead of the optical attenuator Precautions 1 The optical connector should be vertically inserted in the receptacle to avoid damages to the receptacle 2 Fibers must be inserted into optical modules of the corresponding type That is multimode fibers must be inse...

Page 104: ...rface cards returned the optical interfaces should be covered with protection caps l In general the analysis card will not be returned to you If you have any special requirements please contact Huawei l One Fault Tag should be adapted in one return category such as RMA Return Analysis l The items marked with are the mandatory fields that you must fill in 5 7 Installation Checklist Com pone nt No A...

Page 105: ...Ps location IDs of the APs are provided at the cable connection points PoE power supply 1 General The proper PoE switch or power adapter is selected meeting AP power supply and onsite environment requirements 2 General To ensure that the PoE power meets requirements the PoE power supply device and APs must be connected through CAT5E and CAT6E network cables and the cable length cannot exceed 100 m...

Page 106: ...overall layout of the environment 6 Indoor AP Indoor APs are placed far away from windows and in dry environments with little dust and good ventilation There should be no inflammable materials in rooms The indoor temperature and humidity must be within acceptable ranges 7 Indoor AP When being mounted to a ceiling the APs must be fixed using the matching mounting brackets The APs cannot be hung in ...

Page 107: ...l with a ground point must be properly grounded 16 Outdoor AP Unused radio ports should be installed with 50 Ω RF loads 17 Outdoor AP Take lightning protection measures on outdoor APs the outdoor APs have built in 5 kV surge protectors If customers require a higher surge protection capability on the feeder ports they can purchase additional surge protective devices which need to be separately grou...

Page 108: ...cables on the air vents of the cabinet to avoid affecting subrack heat dissipation or cable lifetime 9 General Pigtail layout should meet the following requirements l Pigtails are not strained or twisted at the bent parts They are bundled by binding tape with appropriate force l Pigtails can be pulled back and forth easily inside the cable tie and are not bent at a right angle l Pigtails are not s...

Page 109: ...ll be attached evenly and neatly The network cables shall be covered with waterproof PG tubes 16 Outdoor AP Cable connectors are secured on cables and sealed to prevent water intrusion The outlets of cable conduits on a wall are sealed by waterproof and flame retardant materials Drip loops meeting the minimum bending radius requirement are made on the network cable segment that stretches indoor 17...

Page 110: ...the antennas and feeder cables and keep the drain holes of antennas downwards 7 Outdoor antenna The pole used in antenna mounting should meet the following requirements Pole height 2000 mm Bottom pole diameter 220 mm Top pole diameter 120 mm Pole thickness 6 mm Depth of foundation 1500 mm The pole deployed outdoors must be reinforced with hot dip zinc to prevent water corrosion and rust 8 Outdoor ...

Page 111: ... General Power cables and ground cables are routed straightly and properly bundled with sufficient slack at the bend part If the cables are fixed on a sharp mechanical part take protection measures 7 General The equipotential cables between the attaching cabinets shall be securely connected 8 General The lugs for the power cables and ground cables are soldered or crimped securely 9 General The lug...

Page 112: ...al modules 3 General If a short distance optical fiber is used for a long distance optical module especially in loopback scenarios use an optical attenuator to prevent the optical module from being burnt R250D E Hardware Installation and Maintenance Guide 5 Appendix Issue 01 2016 09 30 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 106 ...

Page 113: ...R250D R250D E Product Description Issue 01 Date 2016 07 05 HUAWEI TECHNOLOGIES CO LTD ...

Page 114: ... Huawei and the customer All or part of the products services and features described in this document may not be within the purchase scope or the usage scope Unless otherwise specified in the contract all statements information and recommendations in this document are provided AS IS without warranties guarantees or representations of any kind either express or implied The information in this docum...

Page 115: ...ation engineers On site maintenance engineers Network monitoring engineers System maintenance engineers Symbol Conventions The symbols that may be found in this document are defined as follows Symbol Description Indicates an imminently hazardous situation which if not avoided will result in death or serious injury Indicates a potentially hazardous situation which if not avoided could result in dea...

Page 116: ...injury Calls attention to important information best practices and tips NOTE is used to address information not related to personal injury equipment damage and environment deterioration Change History Changes between document issues are cumulative The latest document issue contains all the changes made in previous issues Changes in Issue 01 2016 07 05 This is the initial commercial release ...

Page 117: ...g 1 1 2 Product Characteristics 2 2 Hardware Structure 5 2 1 R250D 5 2 2 R250D E 9 3 Product Features 13 3 1 WLAN Features 13 3 2 Network Features 14 3 3 QoS Features 14 3 4 Security Features 14 3 5 Maintenance Features 15 3 6 BYOD 15 3 7 Locating Service 15 3 8 Spectrum Analysis 16 4 Technical Specifications 17 4 1 Basic Specifications 17 4 2 Radio Specifications R250D 18 4 3 Radio Specifications...

Page 118: ...e for users The RU uses an 86 mm plate in compliance with international standards and can be easily installed into a junction box in a room It is equipped with a built in antenna and a hidden indicator therefore installation of the RU does not affect indoor decorations and designs It also has an IEEE 802 11a b g n ac ac wave2 wireless module and can work on both 5 GHz and 2 4 GHz frequency bands T...

Page 119: ...AP which allows for a maximum feeder length of 15 m the central AP uses network cables to replace feeder cables and supports up to 100 m distance from the RUs The network coverage range is therefore expanded by several times No Wall Penetration Loss No Coverage Hole Restricted by feeder length or installation requirements signals have to pass through walls in some scenarios resulting in large sign...

Page 120: ... the indicator has soft light The AC controls the switch of the indicator and turns off the indicator at nights to prevent blinking lights from affecting sleep of guests Four Downlink Ethernet Interfaces Supporting Wired Access from Multiple Users The R250D E has four downlink 1000M Ethernet interfaces that can process data concurrently The interfaces can be connected to multiple terminals through...

Page 121: ...l AP can use RUs to cover dozens of rooms Hierarchical Processing Technology High Wireless Forwarding Capability Huawei distributed solution uses innovative hierarchical processing technology The central AP manages RUs in a centralized manner and concurrently forwards service traffic while the RUs only process radio signals The hierarchical design makes the network structure clearer and reduces th...

Page 122: ...uawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 5 2 Hardware Structure 2 1 R250D Appearance The actual device appearance may be different from the following device appearance these differences will not affect device functions Figure 2 1 R250D appearance ...

Page 123: ...own in Figure 2 2 each port can be described as follows 1 GE1 10 100 1000M port connects to the wired Ethernet 2 Default Reset button used to restore factory settings and restarts the device if you hold down the button more than 3 seconds 3 GE0 PoE_IN 10 100 1000M port connects to the wired Ethernet and supports PoE input The R250D provides only one indicator as shown in Figure 2 3 ...

Page 124: ...or description Type Color Status Description Default status after power on Green Steady on The AP is just powered on and the software is not started yet Software startup status Green Steady on after blinking once After the system is reset and starts uploading the software the indicator blinks green once Until the software is uploaded and started the indicator remains steady green Running status Gr...

Page 125: ...larm Green Blinking once Alarm Green every 0 25s 4 Hz The software is being upgraded After the software is uploaded and started the AP working in Fit AP mode requests to go online on the AC and maintains this state until it goes online successfully on the AC before the CAPWAP link is established The AP registration fails the CAPWAP link is disconnected Fault Red Steady on A fault that affects serv...

Page 126: ...05 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 9 2 2 R250D E Appearance The actual device appearance may slightly differ from the following device appearance but these differences will not affect device functions Figure 2 4 AP2050DN E appearance ...

Page 127: ...he storage space of the AP The USB2 0 standard is supported 3 Default Reset button restores factory settings and restarts the device if you hold down the button more than 3 seconds 4 Pass Through Connects to a network cable or phone cable for transparent transmission 5 GE2 to GE4 10 100 1000M port connects to the wired Ethernet 6 GE1 PoE_OUT 10 100 1000M port connects to the wired Ethernet and sup...

Page 128: ... Default status after power on Green Steady on The AP is just powered on and the software is not started yet Software startup status Green Steady on after blinking once After the system is reset and starts uploading the software the indicator blinks green once Until the software is uploaded and started the indicator remains steady green Running status Green Blinking once every 2s 0 5 Hz The system...

Page 129: ... 25s 4 Hz The software is being upgraded After the software is uploaded and started the AP working in Fit AP mode requests to go online on the AC and maintains this state until it goes online successfully on the AC before the CAPWAP link is established The AP registration fails the CAPWAP link is disconnected Fault Red Steady on A fault that affects services has occurred such as a DRAM detection f...

Page 130: ... Rx only 802 11 dynamic frequency selection DFS Short guard interval GI in 20 MHz 40 MHz and 80 MHz modes Priority mapping and packet scheduling based on a Wi Fi Multimedia WMM profile to implement priority based data processing and forwarding Automatic and manual rate adjustment WLAN channel management and channel rate adjustment For details about WLAN channel management see the Country Code Chan...

Page 131: ...rwarding upon CAPWAP channel disconnection Unified authentication on the AC AC dual link backup IPv6 3 3 QoS Features QoS features supported by the AP are as follows Priority mapping and packet scheduling based on a Wi Fi Multimedia WMM profile to implement priority based data processing and forwarding WMM parameter management for each radio WMM power saving Priority mapping for upstream packets a...

Page 132: ...ion loading and plug and play PnP Batch upgrade Telnet STelnet using SSH v2 Real time configuration monitoring and fast fault location using the NMS System status alarm 3 6 BYOD BYOD features supported by the AP are as follows Identifies the device type according to the organizationally unique identifier OUI in the MAC address Identifies the device type according to the user agent UA information i...

Page 133: ...um analysis features supported by the AP are as follows Identifies interference sources such as baby monitors Bluetooth devices digital cordless phones at 2 4 GHz frequency band only wireless audio transmitters at both the 2 4 GHz and 5 GHz frequency bands wireless game controllers and microwaves Works with eSight to locate and perform spectrum analysis on interference sources ...

Page 134: ...ht 0 2 kg System memory 256 MB DDR3L 32MB Flash Power specifications Power input PoE power supply in compliance with IEEE 802 3af at Maximum power consumption 10 1 W NOTE The actual maximum power consumption depends on local laws and regulations Environment specifications Operating temperature 60 m to 1800 m 0 C to 40 C 1800 m to 5000 m Temperature decreases by 1 C every time the altitude increase...

Page 135: ...tion 11 5 W excluding the output power of the USB port and PoE_OUT port NOTE The actual maximum power consumption depends on local laws and regulations Environment specifications Operating temperature 60 m to 1800 m 0 C to 40 C 1800 m to 5000 m Temperature decreases by 1 C every time the altitude increases 300 m Storage temperature 40 C to 70 C Operating humidity 5 to 95 non condensing IP rating I...

Page 136: ...40 MHz 6 802 11ac 20 MHz 13 40 MHz 6 80 MHz 3 NOTE The table uses the number of non overlapping channels supported by China as an example The number of non overlapping channels varies in different countries For details see the Country Codes Channels Compliance Channel rate 802 11b 1 2 5 5 and 11 Mbit s 802 11a g 6 9 12 18 24 36 48 and 54 Mbit s 802 11n 6 5 to 300 Mbit s 802 11ac 6 5 to 867 Mbit s ...

Page 137: ... 72 dBm MCS7 89 dBm MCS8 86 dBm MCS9 83 dBm MCS10 81 dBm MCS11 78 dBm MCS12 74 dBm MCS13 73 dBm MCS14 70 dBm MCS15 5 GHz 802 11a 91 dBm 6 Mbit s 91 dBm 9 Mbit s 89 dBm 12 Mbit s 88 dBm 18 Mbit s 85 dBm 24 Mbit s 82 dBm 36 Mbit s 77 dBm 48 Mbit s 76 dBm 54 Mbit s 5 GHz 802 11n HT20 91 dBm MCS0 88 dBm MCS1 87 dBm MCS2 84 dBm MCS3 80 dBm MCS4 76 dBm MCS5 74 dBm MCS6 72 dBm MCS7 89 dBm MCS8 86 dBm MCS...

Page 138: ...S1 89 dBm MCS0NSS2 86 dBm MCS1NSS2 85 dBm MCS2NSS2 81 dBm MCS3NSS2 78 dBm MCS4NSS2 74 dBm MCS5NSS2 72 dBm MCS6NSS2 5 GHz 802 11ac VHT40 88 dBm MCS0NSS1 85 dBm MCS1NSS1 82 dBm MCS2NSS1 80 dBm MCS3NSS1 77 dBm MCS4NSS1 73 dBm MCS5NSS1 71 dBm MCS6NSS1 69 dBm MCS7NSS1 66 dBm MCS8NSS1 64 dBm MCS9NSS1 86 dBm MCS0NSS2 83 dBm MCS1NSS2 80 dBm MCS2NSS2 78 dBm MCS3NSS2 75 dBm MCS4NSS2 71 dBm MCS5NSS2 5 GHz 80...

Page 139: ...Typical Maximum number of concurrent users 256 Maximum number of VAPs for each radio 16 Maximum transmit power 2 4 GHz 21 dBm combined power 5 GHz 20 dBm combined power NOTE The actual transmit power depends on local laws and regulations You can adjust the transmit power from the maximum transmit power to 1 dBm with a step of 1 dB Maximum number of non overlap ping channels 2 4 GHz 802 11b g 20 MH...

Page 140: ...it s 95 dBm 2 Mbit s 94 dBm 5 5 Mbit s 91 dBm 11 Mbit s 2 4 GHz 802 11g 93 dBm 6 Mbit s 92 dBm 9 Mbit s 90 dBm 12 Mbit s 89 dBm 18 Mbit s 87 dBm 24 Mbit s 84 dBm 36 Mbit s 80 dBm 48 Mbit s 78 dBm 54 Mbit s 2 4 GHz 802 11n HT20 93 dBm MCS0 89 dBm MCS1 88 dBm MCS2 85 dBm MCS3 82 dBm MCS4 78 dBm MCS5 76 dBm MCS6 74 dBm MCS7 91 dBm MCS8 87 dBm MCS9 86 dBm MCS10 83 dBm MCS11 80 dBm MCS12 76 dBm MCS13 7...

Page 141: ... dBm MCS2 85 dBm MCS3 81 dBm MCS4 77 dBm MCS5 75 dBm MCS6 74 dBm MCS7 90 dBm MCS8 88 dBm MCS9 86 dBm MCS10 83 dBm MCS11 79 dBm MCS12 75 dBm MCS13 73 dBm MCS14 72 dBm MCS15 5 GHz 802 11n HT40 89 dBm MCS0 87 dBm MCS1 85 dBm MCS2 82 dBm MCS3 79 dBm MCS4 75 dBm MCS5 73 dBm MCS6 72 dBm MCS7 87 dBm MCS8 85 dBm MCS9 83 dBm MCS10 80 dBm MCS11 77 dBm MCS12 73 dBm MCS13 71 dBm MCS14 70 dBm MCS15 5 GHz 802 1...

Page 142: ... MCS3NSS1 78 dBm MCS4NSS1 74 dBm MCS5NSS1 73 dBm MCS6NSS1 71 dBm MCS7NSS1 67 dBm MCS8NSS1 65 dBm MCS9NSS1 88 dBm MCS0NSS2 85 dBm MCS1NSS2 83 dBm MCS2NSS2 79 dBm MCS3NSS2 76 dBm MCS4NSS2 72 dBm MCS5NSS2 71 dBm MCS6NSS2 69 dBm MCS7NSS2 65 dBm MCS8NSS2 63 dBm MCS9NSS2 79 dBm MCS3NSS1 76 dBm MCS4NSS1 71 dBm MCS5NSS1 70 dBm MCS6NSS1 68 dBm MCS7NSS1 65 dBm MCS8NSS1 62 dBm MCS9NSS1 84 dBm MCS0NSS2 81 dBm...

Page 143: ... 301 489 1 EN 301 489 17 ETSI EN 60601 1 2 FCC Part 15 ICES 003 YD T 1312 2 2004 ITU k 21 GB 9254 GB 17625 1 EN 55022 EN 55024 CISPR 22 CISPR 24 IEC61000 4 6 IEC61000 4 2 IEEE standards IEEE 802 11a b g IEEE 802 11n IEEE 802 11ac IEEE 802 11h IEEE 802 11d IEEE 802 11e Security Standards 802 11i Wi Fi Protected Access 2 WPA2 and WPA 802 1X Advanced Encryption Standards AES and Temporal Key Integrit...

Page 144: ...nterference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is...

Page 145: ...Ltd 28 following two conditions 1 this device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation Caution Any changes or modifications not expressly approved by the party responsible for compliance could void the user s authority to operate the equipment ...

Reviews: