420010970304 - LP-700 Rev. 000 Rel. 002 Date 4.21.21
24
F. By-Pass Valve
ELU-85WBN - ELU-120WBN
ELU120WCN - ELU150WCN
This boiler has a by-pass valve which requires no adjustment.
The by-pass valve protects the heat exchanger from overheating
by guaranteeing a minimum flow rate of 2 gpm within the primary
heat exchanger. This protects the primary heat exchanger from
overheating when water circulation is insufficient or heating system
load is reduced (ex: due to the response of thermostatic valves or
zone valves).
The by-pass valve is located:
- in the left hydraulic block for ELU-85WBN and ELU-120WBN.
- in the right hydraulic block , behind the three-way valve, for
ELU120WCN and ELU150WCN
By-pass valve
location
Figure 16 - By-Pass Valve Location
Figure 17 - By-Pass Valve Assembly
G. CH and DHW Pressure Relief Valves
This boiler has a high-temperature shut-off switch built in as a standard
safety feature. Therefore, a “pressure only” relief valve is required.
DO NOT operate this appliance before the supplied pressure relief
valve is installed with sufficient relieving capacity in accordance
with the ASME rating plate on the appliance.
The pressure relief valve must be installed with the provided
adaptor pipe in the top of the boiler as detailed in Figure 20. No
other valves should be placed between the pressure relief valve
and the appliance. Failure to comply with these guidelines can
result in substantial property damage, personal injury, or death.
WARNING
!
E. Internal Circulation Pump
To calculate the size of the heating installation refer to the graph below.
Table 11 - Internal Circulation Pump Head Curve
0
4
8
12
16
20
24
0
1
2
3
4
5
6
7
gal/min
feet
Graph Representing the Available Circulation Pump Head
Figure 15 - Internal Circulation Pump NOTE: Ensure the Air Vent on the
Internal Circulation Pump Remains Open after Installation