![HT 400 Series User Manual Download Page 36](http://html1.mh-extra.com/html/ht/400-series/400-series_user-manual_2178071036.webp)
400
Series
EN - 34
8. If the instrument detects that
the phase and neutral leads
are inverted, the message
reported here to the side is
displayed. Rotate the shuko
plug or check the connection
of the single cables
R C D
0°
---ms
FRQ=50.0Hz
Ut=1.4V
VP-N=228V
VP-Pe= 1V
REVERSE P-N
The phase and neutral conductors
are inverted
x1 30mA
50V
Func
IdN RCD UL
9. If the instrument detects that
the phase and earth leads
are inverted, the message
reported here to the side is
displayed. Check the
connection of the cables
R C D
0°
---ms
FRQ=50.0Hz
Ut=1.4V
VP-N= 1V
VP-Pe=231V
REVERSE P-PE
The phase and earth conductors are
inverted
x1 30mA
50V
Func
IdN RCD UL
10. If the instrument detects a
phase-to-neutral voltage and
a phase-to-earth voltage
lower than the limit, the
message reported here to
the side is displayed. Check
that the system being tested
is energized
R C D
0°
---ms
FRQ=50.0Hz
Ut=1.4V
VP-N= 1V
VP-Pe= 1V
Low voltage
Insufficient voltage
x1 30mA
50V
Func
IdN RCD UL
11. If the instrument detects a
phase-to-neutral voltage or a
phase-to-earth voltage higher
than the limit, the message
reported here to the side is
displayed. Check that the
instrument is not phase-to-
phase connected
R C D
0°
---ms
FRQ=50.0Hz
Ut=1.4V
VP-N=281V
VP-Pe=280V
High voltage
High voltage detected
x1 30mA
50V
Func
IdN RCD UL
12. If the instrument detects a
phase-to-neutral voltage
lower than the minimum limit,
it does not perform the test and
displays the message
reported here to the side.
Check the efficiency of the
neutral conductor
R C D
0°
---ms
FRQ=50.0Hz
Ut=1.4V
VP-N= 1V
VP-Pe=231V
MISSING N
Missing neutral conductor
x1 30mA
50V
Func
IdN RCD UL