VEGA
76
EN - 20
5.5. RESET
This option re-establishes the default settings of the instrument.
The default settings of the instrument consist of:
•
ANALYZER
CONFIG:
Frequency: 50Hz
Full scale of the clamps:
1000A
Transforming ratio of voltmetric transformers:
1
Clamp Type:
FLEX
Type of electrical equipment:
4-wire
Password: enabled
•
RECORDER
CONFIG:
Start:
Manual (the recording is started
at 00 sec mark on clock after pressing
the START/STOP key)
Stop: Manual
Integration period:
15min
Recording of harmonics:
ON
Recording of Voltage anomalies (Sag and Surge):
ON
Voltage Reference for Sag and Surge detection:
230V
Upper Limit for Sag and Surge detection:
6%
Lower Limit for Sag and Surge detection:
10%
Selected voltages:
V1, V2, V3
Selected voltage harmonics:
THD, 01, 03, 05, 07
Selected currents:
I1, I2, I3, IN
Selected current harmonics:
THD, 01, 03, 05, 07
CO-GENERATION: OFF
Powers, Pf and cos
ϕ
selected:
Pt, P1, P2, P3
Qti, Q1i, Q2i, Q3i
Qtc, Q1c, Q2c, Q3c
St, S1, S2, S3
Pft, Pf1, Pf2, Pf3
dpft, dpf1, dpf2, dpf3
Energies:
Eat, Ea1, Ea2, Ea3
Erit, Eri1, Eri2, Eri3
Erct, Erc1, Erc2, Erc3
Est, Es1, Es2, Es3
The RESET command will not erase the instrument’s memory.