Page 6
Description of the setting items of the three interfaces above:
Address: This includes the addresses of the detectors, the modules, the horn/strobe and other
equipment, ranging from 001 to 324. The User may set the parameters of a piece of equipment by
inputting its address number through the numeric keys or obtain it through auto login.
Register: This refers to the operating conditions of the equipment with its address: When it is 1, it means
that the equipment has been accessed to the system and can operate normally; and when it is 0, it
means that the equipment has not yet been accessed to the system, or that the equipment has been
accessed to the system but is shielded (the detectors give no alarms, or the modules fail to input, output,
etc.). During auto login, the Register option will be set as 1 automatically. The User may set this option
manually by pressing the numeric keys 1 or 0.
Zone : The system may be set with zones from 01 to 15 through the numeric keys.
Floor : The system may be set with 98 floors ranging from -
9 to 89. Press the numeric key 9 to input “-” in
front of floor numbers 1 to 9.
Room : The system may be set with 255 room numbers ranging from 001 to 255 through the numeric
keys.
Type: This refers to the types of equipment. They may be identified through auto login. The types of
equipment that may be identified through auto login include:
Ion detector and photoelectric detector;
Heat detector (constant temperature);
Heat detector (rate-of-rise and fixed temperature);
Combined detector (photoelectric and constant temperature);
Combined detector (photoelectric and rate-of-rise and fixed temperature);
Input module (interface);
Input module (monitoring);
Output module (control);
I/O module (control and monitoring);
Multi-input model (interface);
Multi-input model (monitoring);
Multi-output module (control);
Multi-I/O module (control and monitoring);
Manual call point;
Hydrant call point;
Horn
Beacon
Horn/strobe
User may also set manually through
▲
and
▼
. The following types are available for selection by user.
Horn/Strobe
Back
Sounder
Broadcast
Air-conditioner
Roll door
Elevator
City power exchange
Fire water electromotor
Sprinkler electromotor
Generator
Sprinkler valve
Fireproof door
Fireproof valve
Air in valve