7.3.5 Voltage tap
All bushings in the range
Sia+
having a nominal voltage greater than 69 kV have a voltage
tap.
Fig. 21: Voltage tap (example illustration)
Item
Part
Item
Part
1
Insulated bushing with pin
4
Removable cap
2
Voltage tap
5
Grounding contact
3
Oil filling hole
6
O-ring
The penultimate grading layer of the capacitive grading is directed out using the voltage tap
(2), with the help of an insulated bushing (1).
The removable cap (4) has an o-ring seal (6) to ensure that the inner space of the voltage tap
remains free from humidity.
In operation, the screwed-on removable cap grounds the pin with the help of a grounding
contact (5).
► Connect the measuring lead to the pin.
► Carry out the measurements.
Range STARIS®-Sia+
47/53