7.3.4 Test tab
Fig. 20: Test tab
Item
Part
Item
Part
1
Grounding contact
4
Test tab
2
O-ring
5
Insulated bushing with pin
3
Removable cap
The last grading layer of the capacitive grading is directed out using the test tab (4) (insulated
bushing (5)).
The removable cap (3) has an o-ring seal (2) to ensure that the inner space of the test tab
remains free from humidity.
In operation, the screwed-on removable cap grounds the pin with the help of a grounding
contact (1).
► Connect the measuring lead to the pin.
► Carry out the measurements.
NOTICE
Material damage from missing removable cap
The test tab is not self-grounding. If the bushing is operated with an open test tab, then
the insulated bushing in the test tab will be destroyed followed by inner fault of the entire
bushing.
► Always screw the removable cap in place after a measurement.
► Make sure that the removable cap is always screwed in place before operating.
Range STARIS®-Sia+