Error description:
No data are being received from the transducer via Ethernet.
Action:
Check the IP address of the receiver (see Section 13) and the Ethernet
cable connection (see Section 7.4).
Error description:
The PROFIBUS master cannot connect to the transducer.
Action:
Check the slave address and check that the correct GSD file has been
selected (see document “Transducer Data Protocol”).
Error description:
The transducer is signaling “EEPROM error” or “Incorrect
calibration values”.
Action:
Return the device to the manufacturer.