Troubleshoot (technician)
Complaint
LED indication light
Cause
Solution
Coupling nut is loose
Fasten coupling nut
Gasket is missing
Place gasket
O ring is missing
Replace temperature sensor
O ring is damaged
Replace temperature sensor
Other components or pipes
are showing leakage
Component or pipe is damaged
Replace component or pipe
Check/open main water supply valve
Check flow sensor for contamination or obstruction
Check heat exchanger for contamination or obstruction
Supply and return valves are closed
Open supply and return valves
Heat exchanger obstipated
Check heat exchanger for contamination or obstruction
LED does not light up
Unit is not connected to power supply
Connect the unit to the power supply
LED does not light up
Power cables not properly connect to electronic
regulator
Connect the power cables to the electronic regulator
Green flashing LED
Tapping threshold is to low, minimal 1 L/min. has
not been reached
Increase water draw off to at least 2 L/min. by opening
the valve at the tapping point further.
Green flashing LED
Flow sensor is not installed correctly or defect
Check mounting direction of flow sensor, replace cable
or replace flow sensor
Blue flashing LED
Differential pressure or supply temperature of the
district heating system is too low
Check supply temperature and differential pressure of
the district heating system (clean DH filters)
Check and connect all cable connections
Close all faucets and valves in the residence. Green
flashing LED should return after approximately 1 min.
Cables are in between unit and casing
Keep cables free of any obstructions
Metal flap closing the heat exchanger in position is
not closed
Close metal flap closing the heat exchangers into
position
Electronics are not properly placed
Check mounting of electronics
Rattling sound
Red or green flashing LED
Flow sensor not installed correctly
Install flow sensor properly
Other errors
Contact your supplier
No tapping water
Leakage
postscript: Close all valves and close the main water supply valve.
Coupling nut shows leakage
Temperature sensor shows
leakage
Casing will not close properly
Casing does not close
properly
Other faults
postscript: It is normal for the unit to generate a light noise during tapping. The regulator valve can also make a light humming sound
No tapping water
No water pressure
Domestic hot water not at the right temperature
Domestic water does not
warm up
Red flashing LED
Possible defect in electronics, electronic cables,
temperature sensors or regulator valve