Profinet
LED
State
Status
COM.STATUS
off
Offline - no connection with the IO-controller
green light
Online RUN - connection with IO-controller established
(IO-controller in RUN-Mode)
green blinking
Online STOP - connection with IO-controller established
(IO-controller in STOP-Mode)
MOD:STATUS
off
off or not initialized
green light
Initialized, no error
green 1x blinking
Diagnostic data available
green 2x blinking
Flashing, used by engineering tools for identification
red 1x blinking
Configuration error (too many modules / submodules
or I/O size/configuration different)
red 3x blinking
No station name entered in the IP address
red 4x blinking
Internal error
LINK
off
No connection or switched off
green light
connected
green blinking
Receipt/transmission of data
NOT USED
-
-
SUBNET STATUS
1
off
off
green blinking
Running correctly, but one or more transaction errors
occurred
green light
RUN
red light
Transaction error / timeout or subnet stopped
DEVICE STATUS
off
off
switch red/green
Incorrect or missing configuration
green light
initialization
green blinking
RUN
red light
Bootloader Modus²
red blinking
If the Device Status LED flashes and the sequence starts
with the red LED flashing once or several times, please
note the sequence pattern and contact support.
1
This LED lights up green when all transactions have been active at least once. This includes all transactions that use State Change or State Change
on Trigger. When a transaction times out, this LED will glow red.
²
The gateway is in bootloader mode and the firmware needs to be restored in order for it to function properly. In this case, please contact our
service: [email protected]